  • Hello! I've reviewed the technical manual for the KA8243 Inverter Condensing Unit Control Module. This document outlines the device's features, such as its 0-10V analog input for capacity control, digital inputs for cooling and heating modes, and LED indicators for operation status. I'm ready to answer your questions about this device.
  • What voltage range can the 0-10V analog input signal have?
    What happens if both COOL and HEAT terminals are closed?
    What does error code E1 mean?
    What does error code Ed mean?
    What does error code dF mean?
InverterCondensingUnit
ControlModule
TechnicalManual
Model:KA8243
refrigerant pipes
PQE signal
communication with
outdoor unit
heating
cooling
0-10V
Heat exchanger
L N Power supply 230V
Alarm
Defrost
KA8243
400V,50H,3Ph+T
010V‐‐‐analoginputterminaltocontroloutdoorunitcapacity.Warning:signalinputcannot
exceed10.5VDC,otherwiseitmaydestroythiscontrolmodule.
Capacitysteps:
00.5V0%(unitstopped)
0.51.5V,10%capacity(LEDdisplaydigit1)
1.52.5V,20%capacity(LEDdisplaydigit2)
...
9.510.5V,100%capacity(LEDdisplaydigit10)
COOL‐‐‐digitalinput.Whenterminalsareclosed,theunitwillrunincoolingmodeand"COOL"
LEDwillbeon.
HEAT‐‐‐digitalinput.Whenterminalsareclosed,theunitwillruninheatingmodeand"HEAT"
LEDwillbeon.
Note:HEATsignalhasthepriority.IfbothCOOLandHEATterminalsareclosed,unitwillrunin
HEATmode.
ENC1‐knobtoselectcondensingunitmodel.
KnobselectionCondensingunit
05,3kWunit
17,1kWunit
29,0kWunit
310,5kWunit
414,0kWunit
516,0kWunit
LEDlampsintroduction:
RUNLEDislightenedwhencontrollerispoweredon.
HEATLEDislightenedwhentheunitisoperatinginheatingmode.
COOLLEDislightenedwhentheunitisoperatingincoolingmode.
DEFLEDislightenedwhenunitisindefrostmode
4. MalfunctionandErrorCode
E1‐‐‐communicationerrorwithoutdoorunit
Ed‐‐‐outdoorunittemperaturesensormalfunctionoroutdoorunitprotection.Inthiscase,check
theerrorcodedisplayedonthePCBoftheoutdoorunit.
dF‐‐‐outdoorisdefrosting.
/