Kaisai KMS-8243 Operating instructions

Type
Operating instructions
InverterCondensingUnit
ControlModule
TechnicalManual
Model:KA8243
refrigerant pipes
PQE signal
communication with
outdoor unit
heating
cooling
0-10V
Heat exchanger
L N Power supply 230V
Alarm
Defrost
KA8243
400V,50H,3Ph+T
010V‐‐‐analoginputterminaltocontroloutdoorunitcapacity.Warning:signalinputcannot
exceed10.5VDC,otherwiseitmaydestroythiscontrolmodule.
Capacitysteps:
00.5V0%(unitstopped)
0.51.5V,10%capacity(LEDdisplaydigit1)
1.52.5V,20%capacity(LEDdisplaydigit2)
...
9.510.5V,100%capacity(LEDdisplaydigit10)
COOL‐‐‐digitalinput.Whenterminalsareclosed,theunitwillrunincoolingmodeand"COOL"
LEDwillbeon.
HEAT‐‐‐digitalinput.Whenterminalsareclosed,theunitwillruninheatingmodeand"HEAT"
LEDwillbeon.
Note:HEATsignalhasthepriority.IfbothCOOLandHEATterminalsareclosed,unitwillrunin
HEATmode.
ENC1‐knobtoselectcondensingunitmodel.
KnobselectionCondensingunit
05,3kWunit
17,1kWunit
29,0kWunit
310,5kWunit
414,0kWunit
516,0kWunit
LEDlampsintroduction:
RUNLEDislightenedwhencontrollerispoweredon.
HEATLEDislightenedwhentheunitisoperatinginheatingmode.
COOLLEDislightenedwhentheunitisoperatingincoolingmode.
DEFLEDislightenedwhenunitisindefrostmode
4. MalfunctionandErrorCode
E1‐‐‐communicationerrorwithoutdoorunit
Ed‐‐‐outdoorunittemperaturesensormalfunctionoroutdoorunitprotection.Inthiscase,check
theerrorcodedisplayedonthePCBoftheoutdoorunit.
dF‐‐‐outdoorisdefrosting.