Figure 4
–
Exploded View of the Swivel Bracket
12 Functional Testing
Start walking across the detection zone. After 3
–
4 steps across
the detection zone, the detector must display the detection by the
red blink of the LED indicator. Wait for 10 sec and continue walking
across the detection zone. There must be no LED indication if there are
no moving objects in the room. If the detector fails to detect moving
objects in the detection zone, then it´s position on the swivel bracket
should be changed.
13 Detector Behavior
13.1 The Detector is powered on and off by the installation and
removal of the main power supply battery.
13.2 Upon the loss of communication with the CP, the Detector
continues to search for the CP. In case the CP is disabled for a long
time, it is recommended to power off the detector (see Cl. 13.1).
13.3 It must be taken into account that in case of the Detector
operation within +5
°
Ñ to minus 20
°
Ñ temperature range, the power
supply batteries life may be less than 5 years.
ATTENTION! Detectors «Foton-12-RK» and «Foton-12B-RK» must
be checked at least annually in order to test their functional ability.
14 Storage and Transportation
14.1 The Detectors in their original packing may be shipped by any
transport means in covered vehicles (in railway, cars, trucks, ship
cargo holds, etc). The Detector is resistant to:
à) transport jolting with the acceleration 30 m/sec2 with impact
frequency from 10 to 120 impacts/sec or 15000 impacts with the
same acceleration;
b) the ambient temperature minus 50 ¾ +50 °Ñ;
c) relative air humidity (95 ± 3) % at the ambient temperature +35 °Ñ.
14.2 After transportation under the conditions different to exploitation
conditions the Detector shall be ready to operate after a maximum
of six hours.
14.3 The storage room shall be free from current-conducting
dust, acid vapors, alkali and gases that cause corrosion and destroy
insulation.
15 Manufacturer’s Guarantees
15.1 The Manufacturer guarantees conformity of the Detector to the
requirements of specification if conditions of transportation, storage,
assembling and operation are observed.
The guaranteed shelf life is 63 months since the date of the Detector
manufacturing.
15.2 The guaranteed period of operation is 60 months since the date
of commissioning within the storage period guaranteed.
15.3 If non-confo rmity of the Detector to technical requirements
is detected during the guaranteed period if rules of operation are
observed it should be repaired by the Manufacturer.
Note
–
The guaranteed period for the Detectors isn´t applied to
the power supply batteries.
16 Acceptance and Packing Certificate
Wireless passive infrared detector:
«Foton-12-RK»
«Foton-12B-RK»
has been manufactured in compliance with the active technical
documentation and classified as fit for operation and packed by
«RIELTA» JSC.
_______________________________
month, year
9 Choosing the Installation Place
The detector must be located in the radio-coverage zone of it´s CP.
Therefore, it is advisable to appraise the quality of communication with
the receiver beforehand. The procedure of appraising the quality of
communication is described in Chapter 10.
When choosing the detector installation place, it is advisable
to take note of the fact that the detection zone may be limited by
non-transparent objects (curtains, houseplants, cabinets, bookcases,
etc.), as well as by glass and mesh partitions. There must be no
windows, air conditioners, space heaters or heating radiators in the
detector visibility zone.
When installing the detector, choose it´s orientation in the effect
that the expected paths of intrusion would cross the sensing zones
of the detector.
The detector should be installed at a distance not closer than
0.5 m from electric cables.
There must be no animals or birds in the protected premises.
10 Communication Quality Appraising
Before installing the detector, it is advisable to check the Detector
communication quality with the CP. The following must be done for
that purpose.
10.1 Prepare the detector for operation and put it on it´s place of
operation with a closed cover.
10.2 Open the detector case, whereupon the detector will indicate
the quality of communication with CP.
Table 6
LED Indication Communication
Quality Appraisal Recommendations
LED indicator blinks green
three times Excellent Install the detector at
this place
LED indicator blinks green
two times Good
LED indicator blinks green
one time
Communication
established Choose another place
for installation or use a
repeater*)
LED indicator blinks red
four times No communication
*)
– «Ladoga-RK» system repeater
11 Installing the Detector
- Remove the detector cover after depressing the latch located at
the bottom of the detector base with a screwdriver (Figure 3).
- If the detector is installed without a bracket, the PCB must be
removed.
- Choose the installation place, mark out and drill the installation
openings in the wall with regard to the position of the holes on the
detector base (or swivel bracket).
- Fasten the detector base in the chosen place; In case the
detector is fastened to the swivel bracket (see Figure 4), remove the
M3x20 screw from the swivel bracket. Holding the parts of the bracket
together, put the square lug on the outer sphere of the bracket with the
corresponding recess in the base of the detector and fasten the
detector to the bracket with the screw. Tighten the screw slightly, so
that the base stays in position o the swivel bracket, but can still be
turned.
- Reinstall the PCB.
- Close the cover.
«RIELTA» JSC, www.rielta.ru,
Tel./fax. +7 (812) 233-0302, 703-1360,
Made in Russia
Rev. 6 of 17.10.17