- 2 - © SIKA • 08/2017
Programming sequence for the connection of VA3K01 and VMM
VMM
Use the left or right arrow key to select “Password”.
Use the down arrow key to select “Customer password” and confirm with ENTER.
Enter the password with the arrow keys and confirm with ENTER.
Use the left or right arrow key to select “Pulse output”.
Use the down arrow key to select “Output of pulses of frequency” and confirm with ENTER.
Set “Frequency” and confirm with ENTER.
Use ESC to return to “Measured values”.
VA3K01
Press the up and down arrow keys at the same time for 3 s to enter programming.
Use the up or down arrow key to select “YES” and confirm with the red key.
Use the up and down arrow keys to select “FUNCT” and confirm with the red key.
Set “TACHO” and confirm with the red key.
Use the left arrow key to return to the main menu.
Select “INPUT” and confirm with the red key.
Set “INP.POL” to “NPN” and “FILTER” to “OFF”.
Use the left arrow key to return to the main menu.
Select “CONFIG” and confirm with the red key.
Set “FACTOR” to the value “1.000” and “DIVISO” to the value”6.000”
(6.0000 Hz/l/min see example of calculation below).
Set “DP” (decimal point) to “0.0”.
Use the left arrow key to return to the main menu.
Select “END.PRG” and confirm with the red key.
Use the up or down arrow key to select “YES” and confirm with the red key.
Example of calculation for frequency
10 m³/h = 166.66 l/min
1 kHz = 1,000 Hz
1,000 Hz / 166.66 l/min = 6.0000 Hz/l/min