  • Hello! I am an AI chatbot trained to assist you with the Sika Durchflussanzeigen VA3K01 mit VMM Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
- 1 - © SIKA 08/2017
Connect display unit type “VA3K01to flow sensor type “VMM”
and programming
Example flow sensor VMM32D1110KAMA20 with the
data:
Measuring range: 010 m³/h
Pulse rate: 1000 pulses/m³
Current output: 420 mA
Frequency output: 0–1 kHz
Terminal assignment and connection of VA3K01 and VMM:
Terminal assignment VMM:
4 = pulse output (passive)
5 = pulse output (passive) +
6 = status output (passive)
7 = status output (passive) +
8 = current output (active)
9 = current output (active) +
Terminal assignment VA3K01:
1 = INP A (signal input A)
8 = 24V DC (sensor supply voltage)
9 = GND (sensor supply voltage)
Supply voltage VA3K01:
(see operating manual VA3K01, p. 21)
16 = 10…30 VDC (supply voltage)
17 = GND (supply voltage)
- 2 - © SIKA 08/2017
Programming sequence for the connection of VA3K01 and VMM
VMM
Use the left or right arrow key to select “Password”.
Use the down arrow key to select “Customer password” and confirm with ENTER.
Enter the password with the arrow keys and confirm with ENTER.
Use the left or right arrow key to select “Pulse output”.
Use the down arrow key to select “Output of pulses of frequency” and confirm with ENTER.
Set “Frequency” and confirm with ENTER.
Use ESC to return to “Measured values”.
VA3K01
Press the up and down arrow keys at the same time for 3 s to enter programming.
Use the up or down arrow key to select “YES” and confirm with the red key.
Use the up and down arrow keys to select “FUNCT” and confirm with the red key.
Set “TACHO” and confirm with the red key.
Use the left arrow key to return to the main menu.
Select “INPUT” and confirm with the red key.
Set “INP.POL” to “NPN” and “FILTER” to “OFF”.
Use the left arrow key to return to the main menu.
Select “CONFIG” and confirm with the red key.
Set “FACTOR” to the value1.000” and “DIVISOto the value6.000
(6.0000 Hz/l/min see example of calculation below).
Set “DP” (decimal point) to “0.0”.
Use the left arrow key to return to the main menu.
Select “END.PRG” and confirm with the red key.
Use the up or down arrow key to select “YES” and confirm with the red key.
Example of calculation for frequency
Frequency
/
Range
=
Frequency
Measuring unit
Hz
/
l/min
=
Hz
l/min
10 m³/h = 166.66 l/min
1 kHz = 1,000 Hz
1,000 Hz / 166.66 l/min = 6.0000 Hz/l/min
/