DESIGN and INSTALLATION SM 4.0
en
PROGETTAZIONE e INSTALLAZIONE SM 4.0
it
SYSTEM FOR MULTIPLE MANAGEMENT
OF BCF 231 COOLERS
SISTEMA PER LA GESTIONE MULTIPLA
DEI RAFFRESCATORI BCF 231
Contents
Contents
Introduction _________________________________________________________________ 1
Level and Temperature/Humidity sensors _________________________________________ 2
Hardware Set-Up ____________________________________________________________ 4
Hardware Configuration _______________________________________________________ 6
Plant Configuration ___________________________________________________________ 9
Fault Code ________________________________________________________________ 14
Software Update ____________________________________________________________ 16
Contact details _____________________________________________________________ 17
Page 01
Introduction
Introduction
This document aims to provide guidelines for the correct design and installation of the SM
4.0 system, which consists of the Weintek control panel and a variable number, from 1 to
31, of BCF231 coolers.
The user of this document will be responsible for:
1) defining the plant configuration, in particular:
- how many coolers to install and of what type (axial/centrifugal);
- defining for each one if it will work as a single machine or within an area;
- establishing the number of temperature/humidity probes;
2) checking that each machine communicates with its own control panel;
3) programming single or group operation;
4) programming manual or automatic operation;
5) programming the time slots in the event of automatic operation;
6) setting the temperature/humidity sensor on the selected parameter;
7) programming a limit for the aforementioned parameter;
8) programming the type of operation:
- Cool;
- Fan;
- Exhaust;
- Clean
9) sending the on-off command
10) checking any protections.
Page
02
Level and Temperature/Humidity sensors
LEVEL SENSOR
Each BCF231 cooler, regardless of the configuration it will assume inside the system, must
have its own water level sensor. This sensor provides information on the amount of water
present in each machine:
1) tank empty;
2) tank half-full;
3) tank full.
On the control panel, by accessing the page dedicated to every single cooler, it is possible to
find a graphic representation of the water level inside it.
TEMPERATURE/HUMIDITY SENSOR
The units that will be configured as single or master of an area must be equipped with the
temperature/humidity sensor which is essential for their management. For slave units the
latter is not required but its use is in any case recommended, in order to maintain the option
of changing the system configuration in the future.
The sensor reads the temperature and humidity and it is up to the user to choose which of
the two parameters to use for the operation of the cooler, through the relevant drop-down
Page
03
Level and Temperature/Humidity sensors
menu. Once the reference parameter has been selected, the target will refer to the latter. In
particular, the cooler will remain active until the set temperature or humidity is reached and
will then go into standby immediately afterwards. If the temperature or humidity deviate from
the target, the cooler will be reactivated again, restoring the conditions prior to standby.
SHARED SENSOR
Each unit belonging to one of the 4 configurable areas shares the same
temperature/humidity sensor connected to the cooler defined as “Master in the area and
determines its status. All other coolers assigned to the same area are defined as “Slave
coolers and copy the behaviour of the master cooler. The area master or area slave status is
assigned through the drop-down menu of the temperature/humidity sensor, in particular by
setting the sensor as:
- Local Temperature …. . to define the Master cooler;
- Local Humidity” ……… . to define the Master cooler;
- Area Temperature.. to define the Slave cooler;
- Area Humidity ……….. to define the Slave cooler.
-
Page 04
Hardware Set-Up
Hardware Set-Up
Through document BCF231_Configuration_V1 it is possible to create a mapping of the plant
that will be implemented by ticking the boxes prepared for the individual items, to define:
1) The type of machine to be installed;
2) Single or Area Operating Mode;
3) In the case of Area mode, which one;
4) If it is a Master or Slave Area;
5) With or without temperature/humidity sensor.
During installation it is advisable to set up a panel fitted with a circuit breaker at the base of
each cooler, to ensure the electrical safety of the device and facilitate maintenance
operations.
To minimise the length of the RS485 connection cable, a serial connection is recommended.
The electronic unit of each cooler is equipped with two ports for the serial line, to facilitate
this type of installation. The ports are fully interchangeable, both can be used as an input or
as an output from the cooler.
CABLE SPECIFICATIONS FOR RS485 SERIAL CONNECTION
It is particularly important for the correct operation of the system to make sure that the cable
chosen for the serial connection between the control panel and the coolers meets the project
specifications, otherwise it will not be possible to guarantee correct system operation.
In particular, the cable must be suitable for transmitting signals and commands for the
interconnection of instrumentation and control systems with digital signal transmission in
outdoor environments, requiring greater protection against electromagnetic (copper braid)
and electrostatic (aluminium/polyester tape) interferences.
Page
05
Hardware Set-Up
FEATURES
DESCRIPTION
STANDARDS
Conductors:
annealed red copper cl.5
IEC EN 60228
Insulation:
R2 quality PVC
IEC EN 50363
Shielding:
Al/Pet tape
Shielding:
annealed red copper
braid
Sheath:
Rz quality PVC
IEC EN 50363
Fire retardant:
CEI 20-22/II
Flame retardant:
IEC EN 60332-1-2
Reduced halogen emission:
(< 22 %
)
IEC EN 50267-2-1 - IEC
60754-1
Resistant to oils:
CEI 20-34/0-1
Resistant to UV Rays:
HD 605
Electrical resistance:
in relation to the section
IEC EN 60228
Test voltage:
2000 V
Max operating temperature:
70 °C
Short circuit temperature:
160 °C
Maximum standard twisting (2x
cable):
≥ 10 turns/metre
CLASS 5 Flexible copper conductors for unipolar and multipolar cables
Nominal Section
Maximum diameter of
the conductor wires
Maximum resistance of the
conductor at 20 °C
Bare wires
Coated wires
mm²
mm
Ω/km
Ω/km
0.5
0.21
39.0
40.1
Page
06
Hardware Configuration
Hardware Configuration
Each cooler must be assigned a progressive number from 1 to 31, this allows the system to
identify it and it is a crucial procedure. It is good practice to assign the coolers the number
corresponding to their position in the communication serial, this facilitates their identification
and helps to speed up the system. In the document BCF231_Configuration_V1 the position
of the dip-switches A0 and A1 is represented graphically for each cooler from No. 1 to No.
31. In a similar manner, the document presents the standard configuration for the T-
termination resistors, which involves their insertion only in the first and last machine of the
system. However, the final configuration must be verified in the field because a lot depends
on the type of cable used, its length and the number of machines in the plant.
Once the machines have been positioned, after having connected the water inlet and outlet
and the wiring of the power supply line and serial connection, it is advisable to proceed as
follows:
1) Connect machine No. 1 to the panel via the serial connection;
2) Power the panel and machine No. 1;
3) Log in to the panel by entering:
- “User Name” followed by “Enter”;
- “Password” followed by “Enter”;
- Select the desired language;
Page 07
Hardware Configuration
- Press the Home icon that appears at the bottom right to access the system.
- The first page accessed is called the Home page
4) From the Home page access the Configuration page to set the number of machines
in the system. To do this, click on the machines in the system that from grey will turn
blue. This step is extremely important because the scanning of the plant by the
control panel will only include the machines declared present. Machines that are not
declared as present will therefore be ignored by the system;
Page
08
Hardware Configuration
5) Go back to the Home page and check that the system recognises machine No. 1
correctly. (All the machines indicated as present will be white except for No. 1 which
will be light grey to indicate the fact that it is present but not configured).
6) Power machine No. 2, connect the serial line and check that it changes state on the
Main page;
7) Proceed in the same way for all the machines present.
This way of proceeding in steps allows problems on the communication line or on some
machines to be identified immediately, isolating the problem. The simultaneous activation of
the entire system, even if manageable by the system, requires a lot of time for
troubleshooting in the event of problems.
It is advisable to pay particular attention to the polarity of the contacts of the serial line, on
the panel and on the single machines, and to ensure that the cables are firmly inserted in the
terminals.
When configuring the hardware, check that the control panel shows the correct time, if this is
not the case, click on the arrow at the bottom right, select System Settings, enter the
password and access the Time/Date page to set the correct date and time.
Page
09
Plant Configuration
Plant Configuration
Using the previously completed document BCF231_Configuration_V1 as a guide, assign
each machine its own setting as follows:
Single Machine Configuration:
1) In the relevant drop-down menu select “Single”;
Set the reference parameter (Temperature or Humidity) and the Target. Since it is a
single machine, the parameters will be of the “Local type;
Page
10
Plant Configuration
2) Set Automatic” or “Manual” operation and in the first case also set the operating
time slots, by defining a switch-on time and a switch-off time for each day of the
week. The cooler will be active within the time slot, while it will be in Standby outside
the time slot.
3) Set a function;
4) Set the fan rotation speed;
5) Turn on the machine.
Area Machine Configuration:
When configuring an area it is good practice to start from the Master machine as follows:
1) In the relevant drop-down menu select “Area 1” or “Area 2” or “Area 3” or “Area 4”;
2) Set the reference parameter (Temperature or Humidity) and the Target. Since it is
the Master machine, the parameters will be of the “Local” type;
3) SetAutomatic or “Manual” operation and in the first case also set the operating
time slots, by defining a switch-on time and a switch-off time for each day of the
week. The cooler will be active within the time slot, while it will be in Standby outside
the time slot and so will all the Area slave coolers.
Page
11
Plant Configuration
4) Set a function;
Set the fan rotation speed;
Page
12
Plant Configuration
Turn on the machine.
Proceed as follows to configure the Slave machines
1) In the relevant drop-down menu select “Area 1” or “Area 2” or “Area 3” or “Area 4”;
2) Set the reference parameter (Temperature or Humidity). Since it is an Area but
Slave machine, the parameters will be of the “Area” type;
Since they are Slave machines, the other parameters will be inherited from the Area Master
machine
Important Note:
If a machine needs to be released from an “Area to be assigned to another “Area”, it must
first be “Uninstalled”, and only subsequently configured as a “Slave” machine of the new
area. Once the operation is complete, access the single menu of the “Master” of the new
Master” and reset the on and off times.
Page
13
Plant Configuration
Example: let’s suppose assume that the system is as shown in the table:
Address
Configuration
Configuration
Configuration
Configuration
Configuration
1
MasterArea1
2
MasterArea2
3
SlaveArea1
4
SlaveArea1
5
SlaveArea1
6
If you want to move unit 5 from SlaveArea1 to SlaveArea2 you must:
1) uninstall unit 5 obtaining the configuration in the table
Address
Configuration
Configuration
Configuration
Configuration
Configuration
1
MasterArea1
2
MasterArea2
3
SlaveArea1
4
SlaveArea1
5
Uninstalled
6
2) configure unit 5 as SlaveArea2
Address
Configuration
Configuration
Configuration
Configuration
Configuration
1
MasterArea1
2
MasterArea2
3
SlaveArea1
4
SlaveArea1
5 SlaveArea2
6
3) Access the single menu of MasterArea2 and set, even without modifying them, the on/off
times and Temperature/Humidity Target.
Page
14
Fault Code
Fault Code
In the event of a fault, the BCF231 generate an error code through which it is possible to
understand the nature of the problem.
Error
Code
Description
How to Reset the Fault
0
No Error
3
Indicates the presence of errors on the
internal communication line. This makes
the temperature and humidity readings
unreliable.
The protection is reset if the fault
disappears for at least 10 seconds,
alternatively On-Off from the
control panel
4
Unit configured as Area Slave that does
not receive communications from the Area
Master for at least 15 minutes.
Restart
On-Off from control panel
5
In Cool mode the humidity measurement is
incorrect for over 120 seconds.
On-Off from control panel
Page
15
Fault Code
On-Off from control panel
6
In Cool mode the temperature
measurement is incorrect for over 120
seconds.
On-Off from control panel
7
In Cool mode the DHT sensor does not
work properly for over 120 seconds.
On-Off from control panel
8
During the Clean function start-up stage,
the water level does not drop for 15
minutes
Power line on-off
9
During the Clean function drain stage, the
water level does not drop for 15 minutes
Power line on-off
10
During the Cool function start-up stage, the
water level remains at 0 for at least 20
minutes.
Power line on-off
11
During the Cool function, if there is no
water for at least 60 minutes.
Power line on-off
12
During the Cool function the tank remains
at the maximum level continuously for at
least 60 minutes.
Power line on-off
Page 16
Software Update
Software Update
Control Panel Update:
The update file (mt8000ie) is supplied in a compressed format; this file must be
decompressed and copied onto a USB flash drive. Insert the flash drive into the USB port at
the bottom of the panel, activate the “download” option and after entering the password,
specify the path for downloading the update files and confirm.
The system will automatically carry out the update at the end of which it will be ready for
normal operation.
Remove the flash drive when the login page appears.
BCF231 Firmware Update:
The update file is supplied in a compressed format, this file must be decompressed and
loaded on each machine of the plant through the ModbusHost program which can be
supplied together with the update file.
To interface with the system you must use a USB-RS485 cable equipped with a
D-sub 9-pin connector (code 4260.290), which allows you to connect directly to the serial
line controlling the SM 4.0 system
en - DISPOSAL OF THE PRODUCT
-This product has been designed and manufactured with top-quality materials and components, which can be re-cycled and re-used.
-When a crossed-wheely bin symbol is attached to the product, it means that the product is protected by the, 2012/19/UE European
Directive.
-Please obtain information regarding the local dierentiated collection system for electrical and electronic products.
-Respect local Standards in force and do not dispose of old products as normal domestic waste. Correct disposal of the product helps
to prevent possible negative consequences for health, the environment and mankind.
it - SMALTIMENTO DEL PRODOTTO
-Questo prodotto è stato progettato e fabbricato con materiali e componenti di alta qualità, che possono essere riciclati e riutilizzati.
-Quando ad un prodotto è attaccato il simbolo del bidone con le ruote segnato da una croce, signica che il prodotto è tutelato dalla
Direttiva Europea 2012/19/UE.
-Si prega di informarsi in merito al sistema locale di raccolta dierenziata per i prodotti elettrici ed elettronici.
-Rispettare le norme locali in vigore e non smaltire i prodotti vecchi nei normali riuti domestici. Il corretto smaltimento del prodotto
aiuta ad evitare possibili conseguenze negative per la salute dell’ambiente e dell’uomo.
de - ENTSORGUNG DES PRODUKTS
-Dieses Produkt wurde unter Verwendung von Qualitätsmaterialien und -bauteilen entwickelt und hergestellt, die recycelt und wieder
verwendet werden können.
-Ist ein Produkt gekennzeichnet durch die Mülltonne mit Rädern und einem Kreuz, wird hier angezeigt, dass dieses Produkt durch die
europäische Direktive 2012/19/UE überwacht ist.
-Es wird gebeten, sich über die vor Ort bestehende Mülltrennung bezüglich elektrischer und elektronischer Produkte zu informieren.
-Die vor Ort geltenden Vorschriften zur Müllentsorgung müssen eingehalten werden und alte Produkte dürfen nicht zusammen mit
dem Hausmüll entsorgt werden. Die ordnungsgemäße Entsorgung des Produkts hilft mögliche negative Folgen für Gesundheit und
Umwelt zu vermeiden.
es - ELIMINACIÓN DEL PRODUCTO
-Este producto ha sido diseñado y fabricado con materiales y componentes de alta calidad que se pueden reciclar y reutilizar.
-Cuando en el producto se encuentra el símbolo del contenedor con las ruedas tachado con una cruz, signica que el producto está
tutelado por la Directiva europea 2012/19/UE.
-Se ruega informarse acerca del sistema local de recogida selectiva para los productos eléctricos y electrónicos.
-Respete las normas locales vigentes y no elimine los productos viejos junto con los residuos domésticos normales. La eliminación
correcta del producto ayuda a evitar posibles consecuencias negativas para la salud del ambiente y del hombre.
fr - SE DÉBARRASSER DE VOTRE PRODUIT USAGÉ
-Ce produit a été conçu et fabriqué avec des matériaux et des composants de haute qualité, qui peuvent être recyclés et utilisés de
nouveau.
-Lorsque le symbole d’une poubelle à roue barrée est appliqué à un produit, cela signie que le produit est couvert par la Directive
Européenne 2012/19/UE.
-Veuillez vous informer du système local de séparation des déchets électriques et électroniques.
-Veuillez agir selon les règles locale set ne pas jeter vos produits usagés avec les déchets domestiques usuels. Jeter correctement
votre produit usagé aidera à prévenir les conséquences négatives potentielles contre l’environnement et la santé humaine.
nl - VERWIJDERING VAN HET PRODUCT
-Dit product werd ontworpen en gemaakt met hoogwaardige materialen en componenten, die gerecycleerd en herbruikt kunnen
worden.
-Wanneer op een product het symbool van de afvalbak op wielen met een kruis erdoor is aangebracht, betekent dit dat het product
valt onder de Europese Richtlijn 2012/19/UE.
-Gelieve inlichtingen in te winnen betreende het plaatselijke systeem voor gedierentieerde inzameling van elektrische en
elektronische toestellen.
-Respecteer de plaatselijke normen die van kracht zijn, en verwijder de oude toestellen niet als gewoon huishoudelijk afval. Een
correcte verwijdering van het product helpt om mogelijke negatieve gevolgen voor de gezondheid van mens en milieu te voorkomen.
pt - ELIMINAÇÃO DO PRODUTO
-Este produto foi projetado e fabricado com materiais e componentes de alta qualidade que podem ser reciclados e reutilizados.
-Quando for axado em um produto o símbolo do bidão com rodas marcado com uma cruz, signica que o produto é protegido pela
Diretiva Europeia 2012/19/UE.
-Solicitamos informar-se sobre o sistema local de recolha diferenciada para os produtos elétricos e eletrónicos.
-Respeitar as normas locais em vigor e não eliminar os produtos antigos como normais detritos domésticos. A correta eliminação do
produto ajuda a evitar possíveis consequências negativas para a saúde do ambiente e do homem.
4250.046 Edition 19 - Rev. 1
Dantherm S.p.A.
Via Gardesana 11, -37010-
Pastrengo (VR), Italy
Dantherm S.p.A.
Виа Гардесана 11, 37010
Пастренго (Верона), Италия
Dantherm Sp. z o.o.
ul. Magazynowa 5A,
62-023 Gądki, Poland
Dantherm Sp. z o.o.
ул. Магазинова, 5A,
62-023 Гадки, Польша
Dantherm LLC
ul. Transportnaya - 22 ownership 2,
142802, STUPINO, Moscow region, Russia
ООО «Дантерм»
Ул. Транспортная, владение 22/2,
142802, г.Ступино, Московская обл., РФ
Dantherm China LTD
Unit 2B, 512 Yunchuan Rd.,
Shanghai, 201906, China
Dantherm China LTD
Юньчуань роад, 512, строение 2В,
Шанхай, 201906, Китай
Dantherm SP S.A.
C/Calabozos, 6 Polígono Industrial, 28108
Alcobendas (Madrid) Spain
Dantherm SP S.A.
Ц/Калабозос, 6 Полигоно Индустриал,
28108 Алкобендас (Мадрит) Испания
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Master SM4.0 4250.046 E19R1 Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI