Tripp Lite SMART2500XLHG User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

This manual is also suitable for

1
Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2012 Tripp Lite. All rights reserved. SmartPro
®
is a registered trademark of Tripp Lite.
SMART2500XLHG
(AG-8589)
Intelligent, Line-Interactive,
Medical-Grade UPS System
Full Isolation: Less than 100µA leakage
Important Safety Instructions 2
Package Contents 3
Quick Installation 4
User Interface 5
Optional Installation 5
Basic Operation 7
Guidance and Manufacturer’s Declaration 10
Storage and Service 12
Battery Replacement 12
Warranty Registration 13
Español 14
Français 27
WARRANTY
REGISTRATION
Register online today for a
chance to win a FREE Tripp Lite
product! www.tripplite.com/warranty
12-10-307-93-3181.indb 1 11/2/2012 9:27:37 AM
2
Important Safety Instructions
Statement of Intended Use
Tripp Lite Medical-Grade UPS Systems are intended to support and protect non-medical
computer equipment and medical devices that require leakage current reduction, surge
protection, voltage regulation, line noise filtering and battery backup during power outages and
generator testing, both inside and outside patient care areas. Tripp Lite’s Medical-Grade UPS
Systems come with hospital-grade plugs and receptacles that reduce leakage to below 100µA.
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation,
operation and storage of all Tripp Lite UPS Systems. Failure to heed these warnings will void
your warranty.
Note: Your UPS incorporates fusing only in the ungrounded phase conductor. UL 60601-1 certified UPS
systems must not be used in countries other than the United States and Canada and must be used only in
healthcare facilities on grounded systems where conditions of maintenance and supervision ensure that only
qualified persons will service the electrical distribution system.
UPS Location Warnings
• Relevantsymbols
Denotes that information in the manual should be reviewed before use.
Used to signal as a warning that a statement is particularly important and could pose
a safety risk.
Denotes that instructions should be followed for proper use.
Warns that users should not sit or step on the unit.
Indicates that you should not push the unit.
• Donotusethisequipmentwithinoxygen-enrichedatmospheres,orwithin0.3m(1ft.)ofa
pointatwhichanoxygen-enrichedatmosphereisintentionallyvented.
• UsecautionwhenliftingUPS.BecauseoftheconsiderableweightofallUPSsystems,at
least two people should assist in lifting and installing them.
• InstallyourUPSindoors,awayfromexcessmoistureorheat,dustordirectsunlight.
•Forbestperformance,theUPSshouldbeusedinalocationthatmeetsthefollowing
conditions:Temperature:0to40°C(32to104°F);Humidity:0to95%(non-condensing);
Elevation:<6,562ft.(2,000m)abovesealevel;Pressure:<95kPA
• LeaveadequatespacearoundallsidesoftheUPSforproperventilation.Donotobstructits
vents or fan openings.
UPS Connection Warnings
•TheUPScontainsitsownenergysource(battery).Theoutputterminalsmaybeliveeven
when the UPS is not connected to an AC supply.
•ConnectyourUPStoaproperlygroundedACpoweroutlet.DonotmodifytheUPS’splugin
a way that would eliminate the UPS's connection to ground. Do not use adapters that
eliminate the UPS’s connection to ground.
•DonotplugyourUPSintoitself;thiswilldamagetheUPSandvoidyourwarranty.
•IfyouareconnectingyourUPStoamotor-poweredACgenerator,thegeneratormustprovide
filtered, frequency-regulated computer-grade output. Connecting your UPS to a generator will
void its Ultimate Lifetime Insurance.
12-10-307-93-3181.indb 2 11/2/2012 9:27:37 AM
3
Important Safety Instructions
•ToisolatetheUPSfromthesupplymains,disconnecttheinputplug.
• Onceconnected,donotlimitaccesstotheinputplug.Theplugmustbeaccessibletobe
used as a means of disconnection.
CAUTION: To ensure proper grounding, the input cord must remain connected to the
supply mains at all times.
WARNING: No modification of this equipment is allowed.
•UPSdoesnotrequiremaintenance.Therearenouserserviceableparts.
Equipment Connection Warnings
•DonotuseTrippLiteUPSSystemsforlifesupportapplicationsinwhichamalfunctionor
failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of
a life-support device.
•DonotconnectsurgesuppressorsorextensioncordstotheoutputofyourUPS.Thismight
overload the UPS and will void the surge suppressor and UPS warranties.
CAUTION: The unit is for exclusive interconnection with IEC6060-1 certified
equipment in the patient environment and IEC 60950 certified equipment
outside of the patient environment. Do not contact SIP/SOP (such as the USB
port, RS232 port, etc.) and the patient at the same time.
Battery Warnings
•Batteriescanpresentariskofelectricalshockandburnfromhighshort-circuitcurrent.
Observeproperprecautions.Donotdisposeofthebatteriesinafire.DonotopentheUPS
or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off
theUPSbeforeperformingbatteryreplacement.Batteryreplacementshouldbeperformed
only by authorized service personnel using the same number and type of batteries (sealed
Lead-Acid). The batteries are recyclable. Refer to your local codes for disposal requirements
orintheUSAonlycall1-800-SAV-LEADor1-800-8-BATTERY(1-800-822-8837)orvisit
www.rbrc.com for recycling information. Tripp Lite offers a complete line of UPS System
ReplacementBatteryCartridges(R.B.C.).VisitTrippLiteontheWebatwww.tripplite.comto
locate the specific replacement battery for your UPS.
•Duringhot-swapbatteryreplacement,theUPSwillnotprovidebackuppowerintheeventof
a blackout or other power interruptions.
•DonotoperateUPSwithoutbatteries.
UPS Disposal
• Alwayscomplywithlocalordinancesforpropermethodsofrecyclinganddisposalof
electronic equipment.
• WhenpurchasinganewUPSfromTrippLite,youmaysendanoldUPSbackforrecyclingon
a one-for-one, like-for-like basis. The new equipment should also be sent back to Tripp Lite
when it ultimately becomes waste.
Package Contents
• SMART2500XLHGIntelligent,Line-Interactive,Medical-GradeUPSSystem
• ACPowerCord(C19toNEMA5-20P)
• 6-ft.DB9Cable
• 6-ft.USBCable
• 6-ft.RJ11Cable
• GroundingThumbscrew
• PowerCordRetentionBracketandScrew
• UserManual
12-10-307-93-3181.indb 3 11/2/2012 9:27:37 AM
4
Quick Installation
1
Plug the UPS into an
outlet on a dedicated
circuit.
TheSMART2500XLHGhasanIECC20
inlet to which the included cord set
(C19 to 5-20P) must be connected.
Attach the included power cord to the
UPS by inserting the IEC connector
A
of
the power cord into the IEC power inlet
B
located on the back of the UPS. Use
the included bracket
C
to secure the
power cord connection.
UL 60601-1 listed UPS systems only
meet UL standard 60601-1 for medical
equipmentwhenpluggedintoanNEC
517approvedandinstalledmedical-
grade outlet.
Note: After you plug the UPS into a live AC
outlet, the UPS (in “Standby” mode) will
automatically charge its batteries,* but will not
supply power to its outlets until it is turned ON
(see Step 3 below).
* The BATTERY CHARGE LED will be the only
LED illuminated.
2
Plug your equipment
into the UPS.
YourUPSisdesignedtosupportonly
electronicequipment.Youwilloverload
the UPS if the total VA ratings for all the
equipmentyouconnectexceedsthe
UPS'sOutputCapacity.Tofindyour
equipment's VA ratings, look on their
nameplates. If the equipment is listed in
amps, multiply the number of amps by
120todetermineVA.(Example:1amp
× 120 = 120 VA). If you are unsure if
you have overloaded the UPS's outlets,
see“OUTPUTLOADLEVEL”LED
description.
3
Turn the UPS ON.
Pressandholdthe“ON/OFF/STANDBY”
button for one second. The alarm will
beep once briefly after one second has
passed. Release the button.
1
1
2
3
A
B
C
12-10-307-93-3181.indb 4 11/2/2012 9:27:39 AM
5
User Interface
A
On/Off/StandbyButton
B
OutputLoadLevelLEDs
C
Power LED
D
Voltage Correction LED
Optional Installation
These connections are optional. Your UPS will function properly without these
connections.
1
USB and RS-232 Serial
Communications
UsetheincludedUSBcable(see
1a
)
andDB9serialcable(see
1b
) to
connect the communication port on your
computer to the communication port of
your UPS. Install the Tripp Lite
PowerAlert Software appropriate to your
computer’s operating system.
Load Level States LED Indicator Audible Alarm
0-75% Line, Invert Green
76-100% Line, Invert Yellow
101-110% Line, Invert BlinkingRed
>110% Line Red
>110% Invert Red On
Runtime Condition States LED Indicator Audible Alarm
>3minremaining Invert Green
3-2minremaining Invert Yellow
<2 min remaining Invert Red On
E
BatteryWarningLEDs
F
BatteryChargeLEDs
G
Mute/TestButton
A B C D E F G
1a
1b
12-10-307-93-3181.indb 5 11/2/2012 9:27:43 AM
6
Optional Installation
2
EPO Port Connection
This optional feature is only for those
applications which require connection to
afacility’sEmergencyPowerOff(EPO)
circuit. When the UPS is connected to
this circuit, it enables emergency
shutdown of the UPS’s inverter.
Using the cable provided, connect the
EPOportofyourUPS(see
2a
) to a user-
supplied normally closed or normally
open switch according to the circuit
diagram (see
2b
).TheEPOportisnota
phonelinesurgesuppressor;donot
connect a phone line to this port.
3
External Battery
Connection
TheSMART2500XLHGisequippedwith
anexternalbatterycapabilityfor
applicationsneedingextendedruntime.
The back of the unit includes the
externalbatterypackconnectorand
charger rate switch. To access the
connector, its factory-installed cover
must be removed.
The charger rate switch is set to the
internalbatterysetting(INT.BATT)by
default.Whenusinganexternalbattery
pack, the switch needs to be set to
externalbatterysetting(EXT.BATT).The
connection of a battery pack and setting
the switch can be done while the unit is
operational.
Note: Leaving the charger rate switch on INT.
BATT while connected to an external battery
will not damage the unit. However, it will
extend the time needed to recharge the
batteries after a power event.
2a
4-5
2b
3
External
Battery
Connector
Cover
Charger
Rate
Switch
12-10-307-93-3181.indb 6 11/2/2012 9:27:46 AM
7
Buttons (Front Panel)
Basic Operation
“ON/OFF/STANDBY” Button
To turn the UPS ON: With the UPS plugged into a live AC wall outlet*,
pressandholdthe“ON/OFF/STANDBY”buttonforonesecond.**Release
thebutton.Ifutilitypowerisabsent,youcan“cold-start”theUPS
(i.e.:turnitONandsupplypowerforalimitedtimefromitsbatteries***)
bypressingandholdingthe“ON/OFF/STANDBY”buttonforonesecond.**
To turn the UPS OFF: WiththeUPSONandreceivingutilitypower,press
andholdthe“ON/OFF/STANDBY”buttonforonesecond.**Thenunplug
theUPSfromthewalloutlet.TheUPSwillbecompletelyOFF.
* After you plug the UPS into a live AC outlet, the UPS (in ”Standby” mode) will
automatically charge its batteries, but will not supply power to its outlets until it is
turned ON.
** The alarm will beep once briefly after the indicated interval has passed.
*** If fully charged.
“MUTE/TEST” Button
To Silence (or “Mute”) UPS Alarms:BrieflypressandreleasetheMUTE/
TEST button.
Note: To permanently disable audible UPS alarms: Contact Tripp Lite support for
instructions.
To Run a Self-Test: WithyourUPSpluggedinandturnedON,pressand
hold the MUTE/TEST button. Continue holding the button until the alarm
beeps several times and the UPS performs a self test. See “Results of a
Self-Test”below.
Note: you can leave connected equipment on during a self-test. Your UPS, however,
will not perform a self-test if the UPS is not turned on (see “ON/OFF/STANDBY” Button
description).
CAUTION! Do not unplug your UPS to test its batteries. This will
remove safe electrical grounding and may introduce a damaging
surge into your network connections.
Results of a Self-Test: Thetestwilllastapproximately10secondsasthe
UPS switches to battery to test its load capacity and battery charge.
•Ifthered“OUTPUTLOADLEVEL”LEDremainslitandthealarmcontinues
to sound after the test, the UPS’s outlets are overloaded. To clear the
overload, unplug some of your equipment and run the self-test repeatedly
untilthered“OUTPUTLOADLEVEL”LEDisnolongerlitandthealarmis
no longer sounding.
CAUTION! Any overload that is not corrected by the user immediately
following a self-test may cause the UPS to shut down and cease
supplying output power in the event of a blackout or brownout.
•Ifthe“BATTERYWARNING”LEDremainslitandthealarmcontinuesto
sound after the test, the UPS batteries need to be recharged or replaced.
Allow the UPS to recharge continuously for 12 hours, and repeat the self-
test. If the LED remains lit, contact Tripp Lite for service. If your UPS
requires battery replacement, visit www.tripplite.com to locate the specific
Tripp Lite replacement battery for your UPS.
12-10-307-93-3181.indb 7 11/2/2012 9:27:47 AM
8
Basic Operation continued
Indicator Lights (Front Panel)
AllIndicatorLightdescriptionsapplywhentheUPSispluggedintoawalloutletandturnedON.
“POWER” LED: ThisgreenLEDlightscontinuouslywhentheUPSisONand
supplying connected equipment with AC power from a utility source. The
LED flashes and an alarm sounds (4 short beeps followed by a pause) to
indicate the UPS is operating from its internal batteries during a blackout or
severe brownout. If the blackout or severe brownout is prolonged, you
should save files and shut down your equipment since internal battery power
willeventuallybedepleted.See“BATTERYCHARGE”LEDdescriptionbelow.
VOLTAGE CORRECTION” LED: This green LED lights continuously
whenever the UPS is automatically correcting high or low AC voltage on the
utility line without the assistance of battery power. The UPS will also emit a
slight clicking noise. These are normal, automatic operations of the UPS, no
action is required on your part.
“OUTPUT LOAD LEVEL” LED: Thisstackof3LEDs(green,yellow,red)
indicatestheapproximateelectricalloadofequipmentconnectedtothe
UPS's AC outlets. It will turn from green (light load) to yellow (medium load)
to red (overload). If the LED is red (either illuminated continuously or
flashing), clear the overload immediately by unplugging some of your
equipment from the outlets until the LED changes from red to yellow (or
green).CAUTION!Anyoverloadthatisnotcorrectedbytheuserimmediately
may cause the UPS to shut down and cease supplying output power in the
event of a blackout or brownout.
“BATTERY CHARGE” LED: When the UPS is operating from utility power,
thisstackof3LEDs(green,yellow,red)indicatestheapproximatecharge
state of the UPS's internal batteries: red indicates the batteries are
beginningtocharge;yellowindicatesthebatteriesareroughlymidway
throughcharging;andgreenindicatesthebatteriesarefullycharged.When
the UPS is operating from battery power during a blackout or severe
brownout,theseLEDsindicatetheapproximateamountofenergy(ultimately
affecting runtime) which the UPS’s batteries will provide: red indicates a low
levelofenergy;yellowindicatesamediumlevelofenergy;andgreen
indicates a high level of energy. Since the runtime performance of all UPS
batteries will gradually deplete over time, it is recommended that you
periodicallyperformaself-test(seeMUTE/TESTButtondescription)to
determinetheenergylevelofyourUPSbatteriesBEFOREablackoutor
severe brownout occurs. During a prolonged blackout or severe brownout,
you should save files and shut down your equipment since battery power will
eventually be depleted. When the red LED is lit and an alarm sounds
continuously, it indicates the UPS's batteries are nearly out of power and
UPS shut down is imminent.
12-10-307-93-3181.indb 8 11/2/2012 9:27:47 AM
9
Basic Operation continued
“BATTERY WARNING” LED: This LED lights yellow and an alarm sounds
intermittentlyafteryouinitiateaselftest(See“MUTE/TEST”Button
description) to indicate the UPS batteries need to be recharged or replaced.
Allow the UPS to recharge continuously for 12 hours, and repeat the self-
test. If the LED continues to light, contact Tripp Lite for service. If your UPS
requires battery replacement, visit www.tripplite.com to locate the specific
Tripp Lite replacement battery for your UPS.
Other UPS Features (Rear Panel)
AC Receptacles: YourUPSfeaturesNEMA15/20andIECC13ACoutlets.
These output receptacles provide your connected equipment with AC line
power during normal operation and battery power during blackouts and
brownouts. The UPS protects equipment connected to these receptacles
against damaging surges and line noise.
Equipotential Connection: Use this to connect any equipment that
requires a chassis ground. Connect the equipment’s ground wire to the UPS
at this point and screw the included thumbscrew into the UPS to secure the
connection.
Communications Ports (USB or RS-232): These ports connect your UPS
to a workstation or server. Use with Tripp Lite’s PowerAlert Software and
included cables to enable your computer to automatically save open files
and shut down equipment during a blackout. Also use PowerAlert Software
to monitor a wide variety of AC line power and UPS operating conditions.
Consult your PowerAlert Software manual or contact Tripp Lite Customer
Supportformoreinformation.See“USBandRS-232Serial
Communications”inthe“OptionalInstallation”sectionforinstallation
instructions.
EPO (Emergency Power Off) Port:YourUPSfeaturesanEPOportthat
may be used to connect the UPS to a contact closure switch to enable
emergencyinvertershutdown.SeeOptionalInstallation.
Accessory Slot: Remove the small cover panel from this slot to install
optional accessories to remotely monitor and control your UPS. Refer to
your accessory’s manual for installation instructions. Contact Tripp Lite
CustomerSupportat(773)869-1234formoreinformation,includingalist
ofavailableSNMP,networkmanagementandconnectivityproducts.
IEC C13
RS-232
NEMA 15/20
USB
12-10-307-93-3181.indb 9 11/2/2012 9:27:49 AM
10
Basic Operation continued
Power Sensitivity Adjustment: This dial is normally set fully counter-
clockwise,whichenablestheUPStoprovidemaximumprotectionagainst
waveform distortions in its AC input. When such distortion occurs, the UPS
will normally switch to providing sine wave power from its battery reserves
for as long as the distortion is present. In areas with poor utility power or
where the UPS’s input power comes from a backup generator, chronic
waveform distortion could cause the UPS to switch to battery too frequently,
drainingitsbatteryreserves.YoumaybeabletoreducehowoftenyourUPS
switchestobatteryduetomoderatewaveformdistortionbyexperimenting
with different settings for this dial. As the dial is turned clockwise, the UPS
becomes more tolerant of variations in its input power’s AC waveform.
Note: The further the dial is adjusted clockwise, the greater the degree of waveform
distortion the UPS will allow to pass to connected equipment. When experimenting with
different settings for this dial, operate connected equipment in a safe test mode so
that the effect on the equipment of any waveform distortions in the UPS’s output can
be evaluated without disrupting critical operations.
Input Breakers: TheSMART2500XLHGusestwoinputbreakerstoprotect
yourelectricalcircuitfromovercurrentdrawfromtheUPSload.Onebreaker
protectsLINE,whiletheotherNEUTRAL.Ifthesebreakerstrip,removesome
of the load and reset them by pressing the breakers in.
Guidance and Manufacturer’s Declaration
Product Information
AC Input Voltage 120V
Input Amp(s) 16A
No.ofPhases Single
Class Type Class 1
Plug/Connector Type IEC inlet C20
Operation Continuous
AC Input Frequency 60Hz
AC Input Protection (Qty./Type/Rating) Inputbreaker(2x20Athermal)
MaxACLeakageCurrent(uA) Less than 100uA
Weight 73.3lbs(33.2kg)
Contraindication None
Guidance and Manufacturer’s Declaration—Electromagnetic Emissions
This Medical-Grade UPS is intended for use in the electromagnetic environment specified below. The
customer or the user of this Medical-Grade UPS should assure that it is used in such an environment.
Emissions Test Compliance Electromagnetic Environment - Guidance
RF Emissions CISPR 11 Group 1 The Medical-Grade UPS uses RF energy only for its internal
function. Therefore, its RF emissions are very low and unlikely
to cause any interference in nearby electronic equipment.
RF Emissions CISPR 11 ClassB The Medical-Grade UPS is suitable for use in all
establishments other than domestic and those directly
connected to the public low-voltage power supply network
that supplies buildings used for domestic purposes.
12-10-307-93-3181.indb 10 11/2/2012 9:27:49 AM
11
Guidance and Manufacturer’s Declaration cont.
Guidance and Manufacturer’s Declaration—Electromagnetic Immunity
This Medical-Grade UPS is intended for use in the electromagnetic environment specified below. The
customer or the user of this Medical-Grade UPS should assure that it is used in such an environment.
Immunity Test IEC 60601 Test Level
Compliance
Level
Electromagnetic
Environment - Guidance
Electrostatic Discharge (ESD)
IEC 61000-4-2
+ / - 6kV contact
+ / - 8kV air
Complies Floors should be wood,
concrete or ceramic tile. If
colors are covered with
synthetic material, the
relative humidity should be
atleast30%.
ElectricalFastTransient/Burst
IEC61000-4-3
+ / - 2kV for power supply
lines
+ / - 1kV for input/output
lines
Complies Mains power quality should
be that of a typical
commercial or hospital
environment.
Surge
IEC 61000-4-5
+ / - 1kV differential mode
+ / - 2kV common mode
Complies Mains power quality should
be that of a typical
commercial or hospital
environment.
Voltage dips, short
interruptions and voltage
variations on power supply
input lines
IEC 61000-4-11
<5%U
T
(>95%dipinU
T
) for .5 cycle
40%U
T
(60%dipinU
T
) for 5 cycles
70%U
T
(30%dipinU
T
) for 25 cycles
<5%U
T
(>95%dipinU
T
) for 5 seconds
Complies Mains power quality should
be that of a typical
commercial or hospital
environment.
PowerFrequency(50/60Hz)
Magnetic Field
IEC61000-4-B
3A/m Complies Power frequency magnetic
fields should be at levels
characteristic of a typical
location in a typical
commercial or hospital
environment.
Note:U
T
is the AC mains voltage prior to application of the test level.
Overcurrent Protection
The unit is equipped with 2 20A, branch-rated, circuit breakers.
Battery Pack
The unit comes with a 48VDC, rechargeable sealed lead-acid battery pack rated at 9 amp
hours.Yourbatteryshouldlastforseveralyears.Ifneeded,replacementbatterypacksforthis
UPSareavailablethroughTrippLite,modelnumberRBC48V-HGTWR.
12-10-307-93-3181.indb 11 11/2/2012 9:27:49 AM
12
Storage and Service
Storage
BeforestoringyourUPS,turnitcompletelyOFF:withtheUPSONandreceivingutilitypower,
pressandholdthe“ON/OFF/STANDBY”buttonforonesecond(analarmwillbeeponcebriefly
aftertheintervalhaspassed);then,unplugtheUPSfromthewalloutlet.IfyoustoreyourUPS
foranextendedperiodoftime,rechargetheUPSbatteriesonceeverythreemonths:plugthe
UPSintoawalloutlet;allowittochargefor12hours;andthenunplugitandplaceitbackin
storage.Note:afteryouplugtheUPSin,itwillautomaticallybeginchargingitsbatteries;
however, it will not supply power to its outlets (see Quick Installation section). If you leave your
UPSbatteriesdischargedforanextendedperiodoftime,theywillsufferapermanentlossof
capacity.
Permissible Storage and Transportation Conditions
Humidity 0-95%Non-Condensing
Temperature -15°Cto45°C;5°Fto113°F
Elevation 0 to 50,000 ft.
Service
BeforereturningyourUPSforservice,followthesesteps:
1. Review the installation and operation instructions in this manual to ensure that the service
problem does not originate from a misreading of the instructions. Also, check that the UPS
System's circuit breaker(s) are not tripped. This is the most common cause of service
inquiries which can be easily remedied by following the resetting instructions in this manual.
2. If the problem continues, do not contact or return the UPS to the dealer. Instead, call
TrippLiteat(773)869-1233.AservicetechnicianwillaskfortheUPS'smodelnumber,
serial number and purchase date and will attempt to correct the problem over the phone.
3.Iftheproblemrequiresservice,thetechnicianwillissueyouaReturnedMaterial
Authorization (RMA) number, which is required for service. If you require packaging, the
technician can arrange to send you proper packaging. Securely pack the UPS to avoid
damage during shipping. Do not use Styrofoam beads for packaging. Any damages (direct,
indirect, special, incidental or consequential) to the UPS incurred during shipment to Tripp
Lite or an authorized Tripp Lite service center is not covered under warranty. UPS Systems
shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation
charges prepaid. Mark the RMA number on the outside of the package. If the UPS System is
within the 2-year warranty period, enclose a copy of your sales receipt. Return the UPS for
service using an insured carrier to the address given to you by the Tripp Lite service
technician.
Battery Replacement Door: Under normal conditions, the original battery in your UPS will last
severalyears.Batteryreplacementshouldbeperformedonlybyqualifiedservicepersonnel.
Referto“BatteryWarnings”intheSafetysection.ShouldyourUPSrequirebattery
replacement,visitTrippLiteontheWebatwww.tripplite.com/support/battery/index.cfmtolocate
the specific replacement battery for your UPS.
Battery Replacement
1
Carefully pull the
front panel away from
the UPS.
Place front panel on top of the unit.
1
12-10-307-93-3181.indb 12 11/2/2012 9:27:50 AM
13
Warranty Registration
Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product.
You'llbeautomaticallyenteredintoadrawingforachancetowinaFREETrippLiteproduct!*
*Nopurchasenecessary.Voidwhereprohibited.Somerestrictionsapply.Seewebsitefordetails.
FCC RADIO/TV INTERFERENCE NOTICE: (FOR CLASS A MODELS)
Note:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,pursuanttoPart15ofthe
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when operated in a commercial
environment. This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance
withtheinstructionmanual,maycauseinterferencetoradiocommunications.Operationofthisequipmentislikelytocauseharmful
interferenceinwhichcasetheuserwillberequiredtocorrecttheinterferenceathisownexpense.Theusermustuseshieldedcables
andconnectorswiththisproduct.Anychangesormodificationstothisproductnotexpresslyapprovedbythepartyresponsiblefor
compliance could void the user's authority to operate the equipment.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique
series number. The series number can be found on the product nameplate label, along with all required approval markings and
information. When requesting compliance information for this product, always refer to the series number. The series number
should not be confused with the marking name or model number of the product.
Tripp Lite has a policy of continuous improvement. Product specifications are subject to change without notice.
Note on Labeling
Two symbols are used on the label.
V~ : AC Voltage V : DC Voltage
Battery Replacement continued
2
Remove battery cover.
Use a screwdriver to remove the screws
holding the battery cover to the unit and
carefully remove the cover. Remove the
battery support bar. Disconnect the
wiring harness connecting the batteries
to the unit.
3
Remove old batteries.
Carefully pull the batteries from the
UPS.
4
Connect new batteries.
Connectthenewbatteriesinexactlythe
same manner as the old ones: positive
(red) connectors together and negative
(black) connectors together. Carefully
push batteries back into the UPS.
5
Reassemble UPS.
Reinstall the battery support bar, battery
cover and front panel.
2
3
4-5
12-10-307-93-3181.indb 13 11/2/2012 9:27:53 AM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40