nVent.com | 5
Junction Box
Control Panel
Temp
Controller
Terminal Blocks
(refer to control panel
drawing for proper
connections)
RTD Lead / Extension Wire
Field Connections
(route wires to provide physical
protection and for aesthetics)
Note: When joining the small
gauge RTD lead wires to heavier
guage extension wires, strip back
the insulation far enough to
double over the R TD wires.
15 ft
Factory
Lead
Mounting
Screw
(by others)
Date TitleDrawn By
SL
Dwg SizeScale
None A
Drawing Number Rev
DateRev Description
10-June-2003
Ambient RTD Sensor
Installation
R50-052-A020 7
Place Ambient RTD Sensor in shaded area
(typically on North side of building under the
soffit) away from any heat source (such as
solar gain or heated vents) that would create
a false (and higher) reading.
Place Loop Strap around R TD, between
pieces of shrink tube. Secure with a mounting
screw (by others)
Route the R TD lead wire to junction box.
Route copper extension wire (note gauge vs
length) to the proper terminal blocks in the
control panel, as specified in the Control
Pane
l drawing.
IMPORTANT: Do not exceed maximum
extension wire length versus wire gauge.
(refer to listing at left)
1.
2.
3.
4.
1 01-Aug-2003 Change RTD lead to 15 ft
2 07-Dec-2009 Revised installation procedure Step 1
By
SL
SL
Installation Procedure:
Note: The NEC (National
Electrical Code) allows the
routing of control wiring in
the same conduit and
junction box as the power
wiring. The electrical
insulation rating on the
control wiring must be
equal to or greater than the
power wiring rating. For
example, if the power
wiring is 300Vac, then the
control wiring leads must
be 300Vac rated or greater.
Copper extension wire,
300 Vac rated insulation:
- 16 gauge up to 60 ft max
-
14 gauge up to 120 ft max
-
12 gauge up to 240 ft max
-
10 g
auge up to 480 ft max
3 19-Aug-2010 Added NEC Note SL
4 04-May-2011 Show RTD positioned under eave SL
Ambient
RTD
Sensor
BBl
ld
dg
g
W
Wa
al
ll
l
Loop
Strap
Mounting
Clip
SSooffffiitt
Ambient
RTD
Sensor
5 06-June-2011 Added RTD wire note SL
6 21-Oct-2014 Added "Typical Location" note SL
TYPIC AL
L O C ATIO N
Thermal Building Solutions
4800 Golden Foothill Parkway
El Dorado Hills, CA 95762
Phone: 916-933-5666 / Fax: 916-933-5959
7 16-June-2015 Contact and logo updates SL
AMBIENT TEMPERATURE SENSING WITH LOW TEMP CUTOUT FOR ROOF ICE MELT SYSTEMS ASD CONTROLLER
Ambient Temperature Sensing with Low Temp Cutout for Roof Ice Melt Systems
ASD Controller
Heater On Set Value
When the ambient temperature falls below the
Heater On set value (SEt 1), the Heater On
Indication Light will illuminate, indicating that the
heater circuits are energized (unless the
ambient temperature falls below the Low Temp
Cutout set value).
Adjusting Set Values
Two set values are available:
SEt 1 = Heater On
SEt 2 = Low Temp Cutout
To toggle between which set value is displayed,
press the up arrow. To change the displayed set
value, hold down the square button and press the
up or down arrow (the longer the arrow button is
held down, the faster the value will change).
TC544A DescPg AmbRIM LTcutout ASD 34F 10F v02 Page 1 of 1
Heater On
Indication
Light
Low Temp
Cutout
Indication
Light (light on
indicates low
temp cutout is
not activated)
Heater On
Set Value [SEt 1]
(SV=Set Value)
Ambient
Temperature
(PV=Process Value)
Low Temp Cutout Set Value
If the ambient temperature falls below the Low
Temp Cutout set value (SEt 2), the Low Temp
Cutout Indication Light will turn off, indicating that
the heater circuits have been de-energized (the
Heater On Indication Light remains on). The
heater circuits will be re-energized when the
ambient temperature rises above the Low Temp
Cutout set value.
Note: Low Temp Cutout can be avoided by
setting its value below the lowest expected
ambient temperature (
for example: –150).
Heater On
Indication
Light
Low Temp
Cutout
Indication
Light (light off
indicates low
temp cutout is
activated)
Low Temp Cutout
Set Value [SEt 2]
(SV=Set Value)
Ambient
Temperature
(PV=Process Value)
Temperature Controller
Thermal BuildingSolutions
4800 Golden Foothill Parkway, El Dorado Hills, CA 95762
Office: +1.916.933.5666 / Fax: +1.916.933.5959 / www.BylinUSA.com
Ambient Temperature Sensing with Low Temp Cutout for Roof Ice Melt Systems
ASD Controller
Heater On Set Value
When the ambient temperature falls below the
Heater On set value (SEt 1), the Heater On
Indication Light will illuminate, indicating that the
heater circuits are energized (unless the
ambient temperature falls below the Low Temp
Cutout set value).
Adjusting Set Values
Two set values are available:
SEt 1 = Heater On
SEt 2 = Low Temp Cutout
To toggle between which set value is displayed,
press the up arrow. To change the displayed set
value, hold down the square button and press the
up or down arrow (the longer the arrow button is
held down, the faster the value will change).
TC544A DescPg AmbRIM LTcutout ASD 34F 10F v02 Page 1 of 1
Heater On
Indication
Light
Low Temp
Cutout
Indication
Light (light on
indicates low
temp cutout is
not activated)
Heater On
Set Value [SEt 1]
(SV=Set Value)
Ambient
Temperature
(PV=Process Value)
Low Temp Cutout Set Value
If the ambient temperature falls below the Low
Temp Cutout set value (SEt 2), the Low Temp
Cutout Indication Light will turn off, indicating that
the heater circuits have been de-energized (the
Heater On Indication Light remains on). The
heater circuits
will be re-energized when the
ambient temperature rises above the Low Temp
Cutout set value.
Note: Low Temp Cutout can be avoided by
setting its value below the lowest expected
ambient temperature (for example: –150).
Heater On
Indication
Light
Low Temp
Cutout
Indication
Light (light off
indicates low
temp cutout is
activated)
Low Temp Cutout
Set Value [SEt 2]
(SV=Set Value)
Ambient
Temperature
(PV=Process Value)
Temperature Controller
Thermal BuildingSolutions
4800 Golden Foothill Parkway, El Dorado Hills, CA 95762
Office: +1.916.933.5666 / Fax: +1.916.933.5959 / www.BylinUSA.com
AMBIENT RTD SENSOR INSTALLATION