Mitsubishi MFZ-KJ12NA-U1 Installation guide

Type
Installation guide
FLOOR TYPE AIR CONDITIONERS
MFZ-KJ09NA MFZ-KJ12NA MFZ-KJ15NA MFZ-KJ18NA
Français
Español
English
INSTALLATION MANUAL
For INSTALLER
• Wheninstallingmultiunits,refertotheinstallationmanual of the multi unit for
outdoorunitinstallation.
MANUAL DE INSTALACIÓN
PARA EL INSTALADOR
• Alinstalarunidadesmúltiples,consulteelmanualdeinstalacióndelaunidad
múltipleparaobtenerinformaciónsobrelainstalacióndelaunidadexterior.
NOTICE D’INSTALLATION
POUR L’INSTALLATEUR
• Lorsdel’installationd’unitésmultiples,consultezlanoticed’installationdesuni-
tésexternesmultiples.
JG79Y071H02_cover.indd 1 2016/01/21 13:10:40
En-1
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Besuretoreadthesesafetyprecautionsandinstructions.
• Besuretoobservethewarningsandcautionsspeciedhere.
• Afterreadingthismanual,besuretostoreitwiththeOPERATINGINSTRUCTIONSforfuturereference.
• Pleasereporttoyoursupplyauthorityorobtaintheirconsentbeforeconnectingthisequipmenttothepowersupplysystem.
CAUTION
(Couldleadtoseriousinjurywhenoperatedincorrectly.)
Required Tools for Installation
Tubebenders
Phillipsscrewdriver
Level
Scale
Utilityknifeorscissors
3in.(75mm)holesaw
Torquewrench
Wrench(orspanner)
5/32in.(4mm)hexagonal
wrench
FlaretoolforR410A
GaugemanifoldforR410A
VacuumpumpforR410A
ChargehoseforR410A
Pipecutterwithreamer
ENGLISH
Wheninstallingmultiunits,refertothe
installationmanualofthemultiunitfor
outdoorunitinstallation.
CONTENTS
1.BEFOREINSTALLATION......................1
2.INDOORUNITINSTALLATION.............4
3.OUTDOORUNITINSTALLATION..........8
4.FLARECONNECTION,PIPE
CONNECTION.......................................9
n Do not install the unit by yourself (user).
Improperorincompleteinstallationcouldcausere,electricshock,injury
duetotheunitfalling,orwaterleakage.Consultaqualiedinstallerorthe
dealerfromwhomyoupurchasedtheunit.
n Follow the instructions detailed in the installation manual.
Incompleteinstallationcouldcausereorelectricshock,injuryduetothe
unitfalling,orleakageofwater.
n When installing the unit, use appropriate protective equipment and tools
for safety.
Failuretodosocouldcauseinjury.
n Install the unit securely in a place that can bear the weight of the unit.
Iftheinstallationlocationcannotbeartheweightoftheunit,theunitcould
fallcausinginjury.
n Perform electrical work according to the installation manual and be sure
to use an exclusive circuit. Do not connect other electrical appliances to
the circuit.
Ifthecapacityofthepowercircuitisinsufcientorthereisincompleteelectri-
calwork,itcouldresultinareoranelectricshock.
n Ground the unit correctly.
Donotconnectthegroundwiretoagaspipe,waterpipe,lightningrodor
telephoneground.Defectivegroundingcouldcauseelectricshock.
n Do not damage the wires.
Damagedwirescouldcausere.
n Be sure to shut off the main power when setting up the indoor P.C. board
or wiring.
Failuretodosocouldcauseelectricshock.
n Usethespeciedwirestosecurelyconnecttheindoorandoutdoorunits.
Attachthewiresrmlytoavoidapplyingstresstotheterminalblock.
Improperconnectioncouldcausere.
n Donotinstalltheunitinaplacewhereammablegasmayleak.
Ifgasleaksandaccumulatesaroundtheunit,itcouldcauseanexplosion.
n Do not use intermediate connection of the power cord or the extension
cord. Do not connect many devices to one AC outlet.
Itcouldcauseareoranelectricshock.
n Usethepartsprovidedorspeciedpartsfortheinstallationwork.
Theuseofdefectivepartscouldcauseaninjuryorleakageofwaterduetoa
re,anelectricshock,theunitfalling,etc.
n When plugging the power supply plug into the outlet, make sure that there
is no dust, blockage, or loose parts both in the outlet and on the plug.
Verify that the power supply plug is completely in the outlet.
Ifthereisdust,blockage,orloosepartsonthepowersupplyplugortheoutlet,
itcouldcauseelectricshockorre.Ifloosepartsarefoundonthepowersupply
plug,replaceit.
n Securely attach the electrical cover to the indoor unit and the service
panel to the outdoor unit.
Iftheelectricalcoveroftheindoorunitand/ortheservicepaneloftheoutdoor
unitarenotattachedsecurely,dust,water,etc.couldcollectintheunitandcould
causeareoranelectricshock.
n When installing, relocating, or servicing the unit, make sure that no sub-
stanceotherthanthespeciedrefrigerant(R410A)enterstherefrigerant
circuit.
Anypresenceofforeignsubstancesuchasaircancauseabnormalpressure
riseandmayresultinexplosionorinjury.Theuseofanyrefrigerantother
thanthatspeciedforthesystemwillcausemechanicalfailure,systemmal-
function,orunitbreakdown.Intheworstcase,thiscouldleadtoaserious
impedimenttosecuringproductsafety.
n Do not discharge the refrigerant into the atmosphere. Check that the
refrigerant gas does not leak after installation has been completed. If
refrigerant leaks during installation, ventilate the room.
Ifrefrigerantcomesincontactwithare,harmfulgascouldbegenerated.
Ifrefrigerantgasleaksindoors,andcomesintocontactwiththeameofa
fanheater,spaceheater,stove,etc.,harmfulgaseswillbegenerated.
n Use appropriate tools and piping materials for installation.
ThepressureofR410Ais1.6timeshigherthanR22.Notusingtheappropri-
atetoolsandmaterials,orimproperinstallationcouldcausethepipesto
burstcausinganinjury.
n When pumping down the refrigerant, stop the compressor before discon-
necting the refrigerant pipes.
Iftherefrigerantpipesaredisconnectedwhilethecompressorisrunning
andthestopvalveisopen,aircouldbedrawninandthepressureinthe
refrigerationcyclecouldbecomeabnormallyhigh,causingthepipestoburst.
n When installing the unit, securely connect the refrigerant pipes before
starting the compressor.
Ifthecompressorisstartedbeforetherefrigerantpipesareconnectedand
thestopvalveisopen,aircouldbedrawninandthepressureintherefrig-
erationcyclecouldbecomeabnormallyhigh,causingthepipestoburst.
n Fastenaarenutwithatorquewrenchasspeciedinthismanual.
Iffastenedtootight,aarenutcouldbreakandcauserefrigerantleakage.
n Install the unit according to national wiring regulations.
n Depending on the installation area, install a Ground Fault Interrupt (GFI)
circuit breaker.
IftheGroundFaultInterrupt(GFI)circuitbreakerisnotinstalled,anelectric
shockcouldoccur.
n Perform the drainage/piping work securely according to the installation
manual.
Ifthereisdefectinthedrainage/pipingwork,watercoulddripfromtheunit,
anddamagehouseholditems.
n Donottouchtheairinletorthealuminumnsoftheoutdoorunit.
Thiscouldcauseinjury.
n Do not install the outdoor unit where small animals may live.
Ifsmallanimalsentertheunitanddamageitselectricalparts,itcouldcause
amalfunction,smokeemission,orre.Keeptheareaaroundtheunitclean.
WARNING
(Couldleadtodeathorseriousinjury.)
1. BEFORE INSTALLATION
5.
PURGINGPROCEDURES,LEAKTEST,
ANDTESTRUN
.....................................10
6.PUMPINGDOWN................................10
JG79Y071H02_en.indd 1 2016/01/21 13:19:59
En-2
Electricalspecications
MODEL
MFZ-KJ09NA
MFZ-KJ12NA
MFZ-KJ15NA MFZ-KJ18NA
INDOORUNIT
Powersupply(V,PHASE,Hz) 208/230,1,60
Min.CircuitAmpacity (A) 1.0
Fanmotor(F.L.A.) (A) 0.62 0.72
OUTDOORUNIT
Powersupply(V,PHASE,Hz) 208/230,1,60
Max.Fusesize(timedelay)(A) 15 20
Min.CircuitAmpacity (A) 11 16
Fanmotor(F.L.A.) (A) 0.50 0.93
Compressor
(R.L.A.) (A) 8.2 12.0
(L.R.A.) (A) 10.3 15.0
Controlvoltage
Indoorunit-Remotecontroller:(Wireless)
Indoorunit-Outdoorunit:DC12-24V(Polar)
Pipe
Outside
diameter
Minimum
wallthick-
ness
Insulation
thickness
Insulation
material
inch(mm)
Forliquid MFZ-KJ09/12/15/18NA 1/4(6.35)
0.0315
(0.8)
5/16(8)
Heatresistant
foamplastic
0.045Specic
gravity
Forgas
MFZ-KJ09/12NA 3/8(9.52)
0.0315
(0.8)
5/16(8)
MFZ-KJ15/18NA 1/2(12.7)
0.0315
(0.8)
5/16(8)
Limits
Pipelength
MFZ-KJ09/12NA 65ft.(20m)max.
MFZ-KJ15/18NA 100ft.(30m)max.
Heightdifference
MFZ-KJ09/12NA 40ft.(12m)max.
MFZ-KJ15/18NA 50ft.(15m)max.
No.ofbends 10max.
Pipelength
Upto25ft.(7.5m) Noadditionalchargeisrequired.
Exceeding25ft.(7.5m)
Additionalchargeisrequired.
(Refertothetablebelow.)
Refrigeranttobe
added
MFZ-KJ09/12NA 1.08ozeach5ft.(20g/m)
MFZ-KJ15/18NA 1.62ozeach5ft.(30g/m)
1-3. SPECIFICATIONS
1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR
WIRE CONNECTION
• Powershouldbetakenfromanexclusivebranchedcircuit.
•
Wiringworkshouldbebasedonapplicabletechnicalstandards.
• Wiringconnectionsshouldbemadefollowingthediagram.
• Securelytightenscrews.
Connecting wires and the ground wire
• Use solid conductor Min.AWG14 or stranded conductor
Min.AWG14.
• Usedoubleinsulatedcopperwirewith600Vinsulation.
• Usecopperconductorsonly.
*Followlocalelectricalcodes.
Power supply cable and ground wire
• Usesolidorstrandedconductor.
KJ09/12NA Min.AWG14
KJ15/18NA Min.AWG12
• Usecopperconductorsonly.
*Followlocalelectricalcodes.
Note:
Whentheindoorunitispoweredfromtheoutdoorunit,depend-
ingonlocalcode,adisconnectswitchneedstobeinstalledtoa
powersupplycircuit.
1-3-2. REFRIGERANT PIPES
• Topreventcondensation,insulatethetworefrigerantpipes.
• Refrigerantpipebendingradiusmustbe4in.(100mm)ormore.
CAUTION
Besuretousetheinsulationofspeciedthickness(tableonthe
right).Excessiveinsulationmaycauseincorrectinstallationof
theindoorunit,andtoolittleinsulationmaycausecondensate
toform.
• Theunit hasaredconnectionsonbothindoorandoutdoor
sides.
• Removethevalvecoverfromtheoutdoorunit,thenconnect
thepipe.
• Refrigerantpipesareusedtoconnecttheindoorandoutdoor
units.
• Becarefulnottocrushoroverbendthepipeinpipebending.
• Refrigerantadjustment...Ifpipelengthexceeds25ft.(7.5m),
additionalrefrigerant(R410A)chargeisrequired.
(Theoutdoorunitischargedwithrefrigerantforpipelengthup
to25ft.[7.5m])
1-2. SELECTING THE INSTALLATION LOCATION
INDOOR UNIT
• Whereairowisnotblocked.
• Whereairspreadsovertheentireroom.
• Rigidwallandatoorwithoutvibration.
• Whereitis notexposedtodirectsunlight.Do not
exposetodirectsunlightalsoduringtheperiodfol-
lowingunpackingtobeforeuse.
• Whereeasilydrained.
• Atadistance3ft.(1m)ormoreawayfrom your
TVandradio.Operationoftheairconditionermay
interferewithradioorTVreception.Anampliermay
berequiredfortheaffecteddevice.
• Inaplaceasfarawayaspossiblefromuorescent
andincandescentlights.Inordertomaketheinfrared
remotecontroloperatetheairconditionernormally.
Theheatfromthelightsmaycausedeformationor
theultravioletmaycausedeterioration.
• Wheretheairltercanberemovedandreplaced
easily.
• Whereitisawayfromtheotherheatorsteamsource.
REMOTE CONTROLLER
• Whereitiseasytooperateandeasilyvisible.
• Wherechildrencannottouchit.
• Selectthepositionwheretheindoorunitcanreceive
thesignalfromtheremotecontrollerproperly.Check
thatsignalsfromtheremotecontrolleraresurelyre-
ceivedbytheindoorunitfromthatposition(‘beep’or
‘beepbeep’receivingtonesounds).Afterthat,attach
remotecontrollerholdertoapillarorwallandinstall
wirelessremotecontroller.
Note:
Inrooms where inverter type uorescent lamps are
used, the signal from the wireless remote controller
maynotbereceived.
OUTDOOR UNIT
• Whereitisnotexposedtostrongwind.
• Whereairowisgoodanddustless.
• Whererainordirectsunlightcanbeavoidedasmuch
aspossible.
• Whereneighbours are not annoyed by operation
soundorhotair.
• Whererigidwallorsupportisavailabletoprevent
theincreaseofoperationsoundorvibration.
• Wherethereisnoriskofcombustiblegasleakage.
• Wheninstallingtheunitatahighlevel,besureto
securetheunitlegs.
• Whereitisatleast10ft.(3m)awayfromtheantenna
ofTVsetorradio.Operationoftheairconditionermay
interferewithradioorTVreceptioninareaswhere
receptionisweak.Anampliermayberequiredfor
theaffecteddevice.
• Installtheunithorizontally.
• Pleaseinstallitinanareanotaffectedbysnowfall
orblowingsnow.Inareaswithheavysnow,please
install a canopy, a pedestal and/or some bafe
boards.
Note:
Itisadvisabletomakeapipingloopnearoutdoorunit
soastoreducevibrationtransmittedfromthere.
Note:
Whenoperatingtheairconditionerinlowoutside
temperature,besuretofollowtheinstructions
describedbelow.
• Neverinstalltheoutdoorunitinaplacewhereitsair
inlet/outletsidemaybeexposeddirectlytowind.
• Topreventexposuretowind,installtheoutdoor
unitwithitsairinletsidefacingthewalland
abafe
boardontheairoutletside.
Avoidthefollowingplacesforinstallationwhereair
conditionertroubleisliabletooccur.
• Whereammablegascouldleak.
• Wherethereisanexcessiveamountofmachine
oilintheair.
• Whereoilissplashedorwheretheareaislled
withoilysmoke(suchascookingareasandfac-
tories,inwhichthepropertiesofplasticcouldbe
changedanddamaged).
• Saltyplacessuchastheseaside.
• Wheresuldegasisgeneratedsuchashotspring,
sewage,wastewater.
•
Wherethereishigh-frequencyor wireless equip-
ment.
• WherethereisemissionofhighlevelsofVOCs,
including phthalate compounds, formaldehyde,
etc.,whichmaycausechemicalcracking.
JG79Y071H02_en.indd 2 2016/01/21 13:19:59
En-3
Indoorunit
Wallhole
sleeve(C)
Cutoffthe
extralength.
Pipeattachment
strap(E)
Usethewallhole
sleeve(C)to
preventindoor/
outdoorconnect-
ingwire(A)from
contactingmetal
partsinthewall
andtoprotect
thewiringfrom
rodents.
Wallholecover(D)
Sealthewallhole
gapwithputty(H).
Attachthepipe
towallwithpipeat-
tachmentstrap(E).
Attachmentscrew(F)
1-4.INSTALLATIONDIAGRAM
ACCESSORIES
Checkthefollowingpartsbeforeinstallation.
<Indoorunit>
(1) Drainhose*1 1
(2) Remotecontrollerholder 1
(3) Screwsfor(2)3.5×16mm(Black) 2
(4) Pipecover 1
(5) Band 2
(6) Battery(AAA)for(12) 2
(7) Indoorunitmountingbracket 1
(8)
Fixingscrewsfor(7)4×25mm
5
(9) Woodscrewforindoorunitxation 4
(10) Washerof(9) 4
(11)
Felttape(Forleftorleft-rearpiping)
1
(12) Wirelessremotecontroller 1
Note:
*1TheDrainhoseisconnectedtotheunit.
FIELD-SUPPLIED PARTS
(A) Indoor/outdoorunitconnectingwire*2 1
(B) Extensionpipe 1
(C) Wallholesleeve 1
(D) Wallholecover 1
(E) Pipexingband 2to5
(F) Fixingscrewfor(E)4×20mm 2to5
(G) Pipingtape 1
(H) Putty 1
(J)
Drainhose
(orsoftPVChose,19/32in.(15mm)in-
nerdiameterorhardPVCpipeVP16)
1
(K) Refrigerationoil 1
(L) Powersupplycord*2 1
Note:
*2Placeindoor/outdoorunitconnectingwire(A)
andpowersupplycord(L)atleast3ft.(1m)
awayfromtheTVantennawire.
Unitsshouldbeinstalledbylicensedcontractor
accordingtolocalcoderequirements.
Aftertheleaktest,apply
insulatingmaterialtightlyso
thatthereisnogap.
Whenthepipingistobeat-
tachedtoawallcomprisedof
tinplateormetalnetting,use
chemically treated wooden
piece25/32 in. (20 mm) or
thickerbetweenthewalland
thepiping,orwrapinsulation
vinyltape7to8turnsaround
thepiping.
Touseexistingpiping,per-
form COOLoperation for
30minutesandpumpdown
beforeremovingtheoldair
conditioner.Remake flare
accordingtothe dimension
fornewrefrigerant.
(L)
(J)
4
in.
(100
mm)
or
more
14
in.
(350
mm)
or
more
8
in.
(200
mm)
*4
ormore
4in.
(100
mm)
or
more
Unit:inch Unit:mm
31-1/2
19-11/16
Airinlet
Airoutlet
13-9/16
11-1/4
2-3/8
×
13/16
slot
12~12-3/4
1-9/16
800
500
Airinlet
Airoutlet
2-10
×
21slot
344.5
285
150
40
304~325
5-15/16
<KJ09/12>
<KJ15/18>
(J)
(L)
Unit:inch Unit:mm
4
in.
(100
mm)
or
more
4
in.
(100
mm)
or
more
14
in.
(350
mm)
ormore
20
in.
(500
mm)
*6
or
more
Drain piping for outdoor unit
Installtheunithorizontally.
Donotusedrainsocketincoldregions.Drainmayfreezeandmakethefanstop.
Theoutdoorunitproducescondensateduringtheheatingoperation.Selecttheinstallationplacetoensuretopreventtheoutdoorunitand/orthegroundsfrom
beingwetbydrainwaterordamagedbyfrozendrainwater.
33-1/16
13-3/4~14-5/8
19-11/16
Airinlet
Airinlet
Airinlet
Airinlet
Airinlet
6-7/8
15-3/8
13
Airoutlet
2-3/8x13/16slot
1-9/16 40
840
175 500
Airinlet
390
330
349~371
Airoutlet
2-10x21slot
clear*3
*34in.(100mm)ormorewhenfront
andsidesofunitareclear
*4Whenany2sidesofleft,rightand
rearofunitareclear
clear*5
*520in.(500mm)ormorewhenfront
andsidesofunitareclear
*6Whenany2sidesofleft,rightand
rearofunitareclear
Obstacles above
It’spossibleto
installanobstacle
tothefollowing
area.
6in.(150mm)or
belowfromtheoor
4
in.
(100
mm)
or
more
Noobstruction
4
in.
(100
mm)
or
more
1-37/64in.
(40mm)or
less
30°orless
1-49/64in.(45mm)ormore
JG79Y071H02_en.indd 3 2016/01/21 13:20:00
En-4
5
5
Wall
Outdoor
side
2-2. HOLE DRILLING
1)Determinethewallholeposition.
2)Drillaø3in.(ø75mm)hole.Theoutdoorsideshouldbe6/32to9/32in.(5to
7mm)lowerthantheindoorside.
3)Insertwallholesleeve(C).
2-1. FIXING OF INDOOR UNIT MOUNTING BRACKET
• Findastructuralmaterial(suchasastud)inthewallandxbracket(7)horizontallywithxingscrews(8).
• Topreventbracket(7)fromvibrating,besuretoinstallthexingscrewsintheholesindicatedintheillustration.Foraddedsupport,xingscrewsmayalsobeinstalled
inotherholes.
2. INDOOR UNIT INSTALLATION
6-27/32
(174)
5-7/16
(138)
29-17/32 (750)
12-21/64
(313)
2-7/16
(62)
17-1/4
(438)
23/32 (18)
7/8 (22)
2-3/4
(70)
3-13/16
(97)
3-7/64 (79)
23-5/8 (600)
19/32 (15)
FORRIGHTDOWNWARDORLEFTDOWN-
WARDPIPING
(Thefollowinggureisaviewofthebottomof
theindoorunitfromabove.)
FORREARORLEFT-REARPIPING
(Thefollowinggureisafrontview
oftheindoorunitinstallationlocation.)
FORLEFTPIPING FORRIGHTPIPING
2-3/8
(60)
1-3/16
(30)
2-3/8
(60)
1-3/16
(30)
2-3/8
(60)
2-3/8
(60)
29-17/32 (750)
8-37/64
(218)
6-3/16
(157)
12-21/64
(313)
2-7/16
(62)
8-15/32
(215)
5-45/64
(145)
2-61/64
(75)
5-7/8
(150)
2-3/8
(60)
HOLE POSITIONS
ø3in.(ø75mm)
6/32-9/32in.
(5-7mm)
2-3. INDOOR UNIT PREPARATION
Removethefrontpaneloftheindoorunit.
1)Pushdownthetabonthebothsidesoftheunittoopenthefrontpanel.
2)Pullthefrontpaneltowardyoutoremoveit.
3)Removethe2screws.
4)Opentherearhorizontalvane.
5)Pushthe2locationsonthetopofthepanel,andthenpulltheupperpartofthepaneltowardyou.
6)Removethepanelwhileliftingitup(slightly).
Rearhorizontal
vane
Panel
Panel
Push
Indoorunit
Frontpanel
Frontpanel
Indoorunit
Indoor
side
Rearhorizontal
vane
inch(mm)
JG79Y071H02_en.indd 4 2016/01/21 13:20:01
En-5
2-4-3.EMBEDDINGTHEINDOORUNITINAWALL
1.Makeaholeinthewall.
2.Usingreinforcementmaterial,adjustthedepth.
3.Remove6screwsthatxthebasetotheunit.Removethebasefromtheunit.
4.Fixtheindoorunitat4pointswiththeincludedwoodscrews(9)andwashers
(10).Tightenthescrewssecurely.
3
3
3
3
3
3
4
22-41/64 (575)
29-9/64 (740)
2-3/4
(
70
)
4
27-3/4(705)
2-4.INDOORUNITINSTALLATION
2-4-1.INSTALLINGTHEINDOORUNITONTHEFLOOR
1.Placetheindoorunitontheatoor.
2.Fixtheindoorunitat4pointswiththeincludedwoodscrews(9)andwashers
(10).Tightenthescrewssecurely.
2-4-2.MOUNTINGTHEINDOORUNITONTHEWALL
1.Hookthetopoftheindoorunitontheindoorunitmountingbracket(7).
2.Fixtheindoorunitat4pointswiththeincludedwoodscrews(9)andwashers
(10).Tightenthescrewssecurely.
15-15/16(405)
5-25/64
(137)
15-15/64(387)
Reinforcement
material
Unit
Base
Wrapthefelttape(11)tightlyaroundthepipesandhosestartingnearwhere
thepipesandhoseareroutedfromtheindoorunit.(Theoverlapwidthofthe
felttape(11)shouldnotbemorethan1/2ofthetapewidth.)
Felttape(11)
Startwrappingthepipingtape(G)around
thepipesandhose25/64in.(10mm)
insidetheindoorunit.
Fastentheendofthefelttape(11)with
abandagestopper.
Makesurethatthedrainhose
isnotroutedupward.
FORLEFTORLEFT-REARPIPING
Bundletheconnectingpipesanddrainhosetogether,andthenwrapthemin
felttape(11).
Cutandusethelowersidepanelsontheleftandrightsidesoftheindoorunit
asshownbelow.
Smooththecutedgesofthesidepanelssothattheywillnotdamagetheinsula-
tioncoating.
• Forleftorrightpiping
• Installingushagainstawallwithmolding
Molding
Cutthelowersidepanelsto
matchtheheightofthemolding.
Piping
tape
Drainhose
Refrigerantpiping
Indoorunit
Push
Pipingbentoutward
• Besuretoinsulatetheconnectingpipessothattheydonotcontactthe
panel.
• Becarefulnottocrushtheconnectingpipeswhenbendingthem.
(Useatubebendersforleftorrightpiping.)
• Thepipecovercannotbeattachedwithoutconnectingtheconduitpipe
afterconnectingthepipes.
Removethecover.
RIGHTDOWNWARDPIPING OTHERPIPING
Band(5)
Pipecover(4)
Band(5)
Conduitpipe
8-5/64(205)
6-1/2(165)
inch(mm)
2-5. PIPE FORMING AND INSTALLATION
Note: Referto4.FLARECONNECTION,PIPECONNECTION.
Pipe Forming
• Routethedrainhosediagonallybelowtheconnectingpipes.
• Makesurethatthedrainhoseisnotroutedupwardandthatthereareno
wavesinthehose.
• Donotpullthehosewhenapplyingthetape.
• Routethepipingsothatitdoesnotprojectpasttherearoftheindoorunit.
(Refertotheguretotheright.)
Connecting Pipe Installation
• Installtheconnectingpipessothatthepipingcanmoveslightlytothe
front,back,left,andright.
JG79Y071H02_en.indd 5 2016/01/21 13:20:03
En-6
• Makeearthwirealittlelongerthanothers.(Morethan45mm)
• Forfutureservicing,giveextralengthtotheconnectingwires.
• Donotfoldtheexcesswire,orcramitintosmallspace.Takecautionnottodamagethe
wires.
• Besuretoattacheachscrewtoitscorrespondentterminalwhensecuringthecordand/
orthewiretotheterminalblock.
INDOOR UNIT
Terminalblock
208/230VAC
1phase,60Hz
Grounding
terminal**
Disconnect
switch*
OUTDOOR UNIT
Groundingterminal**
Ground
Powersupply
208/230VAC,
1phase2wires.
60Hz
Terminal
block1
Remark:
* Adisconnectswitch(15A
MAX)shouldberequired.
Checkthelocalcode.
** Usearingtongueterminal
inordertoconnectaground
wiretoterminal.
Terminalblock2
2-6. CONNECTING WIRES FOR INDOOR UNIT
Note: Whentheindoorunitispoweredfromtheoutdoorunit,dependingonlocalcode,adisconnectswitchneedstobeinstalledtoapowersupplycircuit.
1)Removetheelectricalcover.
2)Removetheconduitplate.
3)Attachtheconduitpipetotheconduitplatewiththelocknut.Theindoor/outdoorunitconnectingwire(A)appearingfromtheinsideofconduitpipeshouldbe
lessthan7/8in.(23mm).(Fig.1)
4)Processtheendofgroundwire(Fig.2).Connectittothegroundterminaloftheelectricalpartsbox.
5)Processtheendofindoor/outdoorunitconnectingwire(A)(Fig.2).Attachittotheterminalblock.Becarefulnottomakemis-wiring.Attachthewiretotheterminal
blocksecurelysothatitscorecannotbeseen,andnoexternalforceaffectstheconnectingsectionoftheterminalblock.
6)Firmlytightentheterminalscrews.Aftertightening,verifythatthewiresaretightlyfastened.
7)Reinstalltheconduitplate.
8)Reinstalltheelectricalcover.
Fig.1
Lead
wire
19/32in.
(15mm)
Fig.2
Terminalblock
Locknut
Electricalcover
Electricalbox
Conduitpipe
Grounding
terminal
Screw
Lessthan7/8in.
(23mm)
Conduitplate
Conduitpipe
Locknut
Conduitplate
Donotmakedrainpipingasshownbelow.
Accumulated
drainwater
Air
Waving
Water
leakage
Donotraise
Water
leakage
Water
leakage
Tipofdrain
hosedipped
inwater
Ditch
Atleast
1-31/32in.
(50mm)gap
Downward
slope
Drain
hose
SofthoseI.D.
19/32in.
(15mm)
Drainhose
Hardvinylchloride
pipeI.D.1-3/16in.
(30mm)
Insert
securely
Differentdiameterjoint
27-9/16in.
(70cm)or
more
Fig.1 Fig.2 Fig.3
2-7. DRAIN PIPING
• Iftheextensiondrainhosehastopassthrougharoom,besuretowrapitwithcommerciallysoldinsulation.
• Thedrainhoseshouldpointdownwardforeasydrainow.(Fig.1)
• Ifthedrainhoseprovidedwiththeindoorunitistooshort,connectitwithdrainhose(J)thatshouldbeprovidedatyoursite.(Fig.2)
• Whenconnectingthedrainhosetothehardvinylchloridepipe,besuretoinsertitsecurelyintothepipe.(Fig.3)
Fig.5
Projection
Makesureto
hookthecatch.
Drainhose
Pullthehoseto
conrmitiscon-
nectedsecurely.
Fig.4
The Drain hose is removed at installation.
• Whenroutingthedrainpiping,makesurethatthedrainhose
(1)isroutedasshown.(Fig.4)
• Insertthedrainhoseallthewaytothebaseofthedrain
pan(endconnection).(Fig.5)
Makesurethatthecatchofthedrainhoseissecurely
hookedontotheprojectiononthehosettingofthedrain
pan.
• Afterconnectingthedrainhose,besuretopullthehoseto
conrmthatitisconnectedsecurely.
Conduitpipe
Pipe
cover
JG79Y071H02_en.indd 6 2016/01/21 13:20:05
En-7
1)Removethepanel.
2)OpenthecoveroftheindoorcontrolP.C.board.
3)JointheconnectingcabletoCN105and/orCN24ontheindoorcontrolP.C.
board.
4)Routetheconnectingcablethroughthispointinthegure.
5)Attachthecableclampprovidedwithinterface/connectorcabletothethick
partoftheconnectingcablewithascrew4×16asshowninthegure.
6)ClosethecoveroftheindoorcontrolP.C.board.Becarefulnottocatchthe
thinpartoftheconnectingcableinthecover.Reinstallthepanel.
5)
4)
3)CN105
WARNING
Fix the connecting cable at the prescribed position securely.
Incorrectinstallationmaycauseelectricshock,re,and/ormalfunction.
Whenmountingtheinterface
andtheconnectorcable,use
thisscrewtoxtheconnect-
ingcable.
3)CN24
2-9.CONNECTING AN INTERFACE (option)/CONNECTOR CABLE (option) TO THE AIR CONDITIONER
Thinpartoftheconnectingcable.
Placethispartwherecustomers
cannottouchit.
Roomair
conditioner
Mainbodyofaninterface
Thickpartoftheconnecting
cable
Indoorcontrol
P.C.board
CN105forinterface
CN24forconnectorcable
• Connectaninterface/connectorcabletotheindoorcontrolP.C.boardof
anairconditionerwithaconnectingcable.
• Cuttingorextendingtheconnectingcableoftheinterface/connectorca-
bleresultsindefectsinconnecting.Donotbundletheconnectingcable
togetherwithpowersupplycord,indoor/outdoorconnectingwire,and/or
earthwire.Keepasmuchdistanceaspossiblebetweentheconnecting
cableandthosewires.
• Thethinpartoftheconnectingcableshouldbestoredandplaced
wherecustomerscannottouchit.
2-8. FRONT PANEL INSTALLATION
1)Opentherearhorizontalvane.
2)Attachthepanel.Makesurethatthecatchesareengaged.
3)Fixthepanelwithscrews.
4)Insertthebottompartofthefrontpanel.
5)Push3placesontheupperpartofthefrontpaneltocloseit.
Frontpanel
Indoorunit
Indoorunit
Panel
Panel
Rearhorizontal
vane
JG79Y071H02_en.indd 7 2016/01/21 13:20:06
En-8
3-1. CONNECTING WIRES FOR OUTDOOR UNIT
1)Removetheservicepanel.
2)Removetheconduitcover.
3)Attachtheconduitconnectorstotheconduitplatewithlocknutsthensecure
itagainstunitwithscrews.
4)Connectthegroundwiresofindoor/outdoorunitconnectingwire(A)andpower
supplycord(L)totheTBsupport.
5)Loosentheterminalscrews,thenattachindoor/outdoorunitconnectingwire
(A)andpowersupplycord(L)fromtheindoorunitcorrectlytotheterminal
block.Attachthewirestotheterminalblocksecurelysothatthecorescannot
beseen,andnoexternalforceaffectstheconnectingsectionoftheterminal
block.
6)Firmlytightentheterminalscrews.Aftertightening,verifythatthewiresare
tightlyfastened.
7)Installtheconduitcover.
8)Installtheservicepanelsecurely.
3. OUTDOOR UNIT INSTALLATION
Power supply cord (L)
L1
L2
Lead
wire
19/32in.
(15mm)
Terminalblock
Power supply cord (L)
Indoor/outdoorunit
connectingwire(A)
• Makeearthwirealittlelongerthanothers.(Morethan4in.[100mm])
• Forfutureservicing,leavesomeslackintheconnectingwires.
• Besuretoattacheachscrewtoitscorrespondentterminalwhensecuring
thecordand/orthewiretotheterminalblock.
Servicepanel
Locknut
Conduitcover
Conduitplate
Conduitpipe
Grounding
terminal
Grounding
terminal
TBsupport
<KJ09/12>
<KJ15/18>
Terminalblock
toconduitcover
Power supply cord (L)
Indoor/outdoorunit
connectingwire(A)
TBsupport
Servicepanel
Locknut
Conduitcover
Conduit
plate
Conduitpipe
toconduitcover
3-2. PIPE FORMING AND INSTALLATION
Note: Referto4.FLARECONNECTION,PIPECONNECTION.
3-3. INSULATION AND TAPING
1)Coverpipingjointswithpipecover.
2)Foroutdoorunitside,insulatethepiping,includingvalves.
3)Applypipingtape(G)startingfromtheconnectionontheoutdoorunit.
• Whenpipinghastobeinstalledthroughaceiling,closetorwherethetem-
peratureandhumidityarehigh,useadditionaleld-suppliedinsulationto
preventcondensation.
JG79Y071H02_en.indd 8 2016/01/21 13:20:07
En-9
4-1.FLARECONNECTION
1)Cutthecopperpipeasstraightaspossiblewithapipecutter.(Fig.1,2)
2)Removeallburrsfromthecutsectionofthepipe,ensuringthatprecautions
aretakentoavoidgettingmetalshavingsintothepiping.(Fig.3)
3)Removearenutsattachedtoindoorandoutdoorunits,thenputthemon
pipe.
4)Flaringwork(Fig.4,5).Firmlyholdcopperpipeinthedimensionshowninthe
table.SelectAinch(mm)fromthetableaccordingtothetoolyouuse.
5)Check
• ComparethearedworkwithFig.6.
• Ifareisdefective,cutoffthesectionandrepeatprocedure.
Pipe
diameter
inch(mm)
Binch
(mm)
Ainch(mm) Tighteningtorque
Clutch
typetool
forR410A
Clutch
typetool
forR22
Wingnut
typetool
forR22
ft-lb
(kgf•cm)
N•m
ø1/4
(6.35)
21/32
(17)
0to0.02
(0to0.5)
0.04to
0.06
(1.0to1.5)
0.06to
0.08
(1.5to2.0)
10to13
(140to180)
13.7to
17.7
ø3/8
(9.52)
7/8(22)
25to30
(350to420)
34.3to
41.2
ø1/2
(12.7)
1-1/32
(26)
0.08to
0.10
(2.0to2.5)
36to42
(500to575)
49.0to
56.4
ø5/8
(15.88)
1-5/32
(29)
54to58
(750to800)
73.5to
78.4
4. FLARECONNECTION,PIPECONNECTION
Copper
pipe
Good
90°
Tilted
Nogood
Fig.1
Burr
Copperpipe
Sparereamer
Pipecutter
Fig.4
Smoothallaround
Evenlength
allaround
Insideis
shining
withoutany
scratches.
Fig.6
Clutchtype
Flaringtool
Wingnuttype
Uneven Burred
B
Flarenut
Die
Copperpipe
Fig.2
Fig.3
Fig.5
4-2.PIPECONNECTION
• Fastenarenutwithatorquewrenchasspeciedinthetable(referto3-2.).
• Whenfastenedtootight,arenutmayeventuallybreakandcauserefrigerant
leakage.
• Besuretowrapinsulationaroundthepiping.Directcontactwiththebare
pipingmayresultinburnsorfrostbite.
Indoor unit connection
Connectbothliquidandgaspipingstoindoorunit.
• Applyathincoatofrefrigerationoil(K)onthearedendsofthepipes.Do
notapplyrefrigerationoilonscrewthreads.Excessivetighteningtorquewill
resultindamageonthescrew.
• Toconnect,rstalignthecenter,thentightentherst3to4turnsofarenut.
• Usetighteningtorquetableaboveasaguidelineforindoorunitsidejoints,and
tightenusingtwowrenches.Excessivetighteningdamagesthearesection.
Outdoor unit connection
Connectpipestostopvalvepipejointoftheoutdoorunitfollowingthesame
proceduredetailedinindoorunitconnection.
• Fortightening,useatorquewrenchorspanner.
WARNING
When installing the unit, securely connect the refrigerant pipes before
starting the compressor.
JG79Y071H02_en.indd 9 2016/01/21 13:20:07
En-10
5-1. PURGING PROCEDURES AND LEAK TEST
1)
Removeserviceportcapsfromstopvalvesonbothsidesofrefrigerantlines.
(Thestopvalvesarefullyclosedwhenshipped.)Leaveclosed.
2)Connectgaugemanifoldtoportsofstopvalves.
5-4.EXPLANATIONTOTHEUSER
• UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowtousethe
airconditioner(theremotecontroller,removingtheairlters,placingorremov-
ingtheremotecontrollerfromtheremotecontrollerholder,cleaningmethods,
precautionsforoperation,etc.)
• RecommendthattheuserreadtheOPERATINGINSTRUCTIONScarefully.
Stopvalve
forGAS
Stopvalvecap
(Torque15to
22ft-lb,19.6to
29.4N•m,200
to300kgf▪cm)
Vacuumpump(orthe
vacuumpumpwiththe
functiontopreventthe
backow)
Gaugemanifold
valve(forR410A)
Compoundpressure
gauge(forR410A)
–14.7psi[Gauge]
(–0.101Mpa)
Handle
Low
HandleHigh
Adapterfor
preventingthe
backow
Chargehose
(forR410A)
*Close
*Open
Hexagonal
wrench
Precautionswhenusingthe
controlvalve
Whenattachingthecontrolvalve
totheserviceport,valvecoremay
deformorloosenifexcesspressure
isapplied.Thismaycausegasleak.
Serviceport
Chargehose
Body
Close
Open
Controlvalve
A
Whenattachingthecontrolvalvetothe
serviceport,makesurethatthevalve
coreisinclosedposition,andthen
tightenpartA.DonottightenpartA
orturnthebodywhenvalvecoreisin
openposition.
Serviceportcap
(Torque10to13
ft-Ib,13.7to17.7
N•m,140to180
kgf•cm)
*4to5turns
3)Evacuate the system to 4000 microns from both service valves. System
manifoldgaugesmustnotbeusedtomeasurevacuum.Amicrongaugemust
beusedatalltimes.BreakthevacuumwithNitrogen(N2)intothedischarge
servicevalveto0PSIG.
4)Evacuatethesystemto1500microns.BreakthevacuumwithNitrogen(N2)
intothedischargeservicevalveto0PSIG.
5)Evacuatethesystemto500microns.
6)Closegaugemanifoldvalves,stopthepump,andconducta30minuterise
test.
7)Systemshouldhold500micronsforaminimumof1hour.
8)Fullyopenallstopvalvesonbothsidesofgaspipeandliquidpipe.Operating
withoutfullyopeninglowerstheperformanceandthiscausestrouble.
9)Referto 1-3 and charge the prescribed amount of additional refrigerant if
needed.Besuretochargeslowlywithliquidrefrigerant.Otherwisecomposi-
tionoftherefrigerantinthesystemmaybechangedandaffectperformance
oftheairconditioner.
10)Removegaugemanifoldsandreplaceserviceportcapsandtighten.
11)Leaktest
Stopvalve
forLIQUID
5. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
Pressuregauge
(forR410A)
Caution:
• Aftertestrunorremotesignalreceptioncheck,turnofftheunitwiththe
E.O.SWortheremotecontrollerbeforeturningoffthepowersupply.Ifthis
procedureisnotperformed,theunitwillautomaticallybeginoperationwhen
powersupplyisresumed.
To the user
• Afterinstallingtheunit,explaintotheuseraboutautorestartfunction.
• Ifautorestartfunctionisunnecessary,itcanbedeactivated.Consultthe
servicerepresentativetodeactivatethefunction.Refertotheservicemanual
fordetails.
5-2. TEST RUN
1)Insertpowersupplyplugintothepoweroutletand/or
turnonthebreaker.
2)PresstheE.O.SWonceforCOOL,andtwiceforHEAT
operation.Testrunwillbeperformedfor30minutes.If
theleftlampoftheoperationindicatorblinksevery0.5
seconds,inspecttheindoor/outdoorunitconnecting
wire(A)formis-wiring.Afterthetestrun,emergency
mode(settemperature75°F[24°C])willstart.
3)Tostopoperation,presstheE.O.SWseveraltimes
untilallLEDlampsturnoff.Refertooperatinginstruc-
tionsfordetails.
Checking the remote (infrared) signal reception
PresstheOFF/ONbuttonontheremotecontroller(12)andlistenforan
audibleindicatorfromtheindoorunit.PresstheOFF/ONbuttonagaintoturn
theairconditioneroff.
• Oncethecompressor stops,therestartpreventivedevice operatessothe
compressorwillnotoperatefor3minutestoprotecttheairconditioner.
5-3. AUTO RESTART FUNCTION
Thisproductisequippedwithanautorestartfunction.Whenthepowersupply
iscutoffduringoperation,suchasduringblackouts,thefunctionautomatically
startsoperationintheprevioussettingoncethepowersupplyisresumed.
(Refertotheoperatinginstructionsfordetails.)
Emergencyoperation
switch(E.O.SW)
6. PUMPING DOWN
Whenrelocatingordisposingoftheairconditioner,pumpdownthesystemfollowingtheprocedurebelowsothatrefrigerantisnotreleasedintotheatmosphere.
1)Connectthegaugemanifoldvalvetotheserviceportofthestopvalveonthegaspipesideoftheoutdoorunit.
2)Fullyclosethestopvalveontheliquidpipesideoftheoutdoorunit.
3)Closethestopvalveonthegaspipesideoftheoutdoorunitalmostcompletelysothatitcanbeeasilyclosedfullywhenthepressuregaugeshows0psi[Gauge]
(0Mpa).
4)StarttheemergencyCOOLoperation.
TostarttheemergencyoperationinCOOLmode,disconnectthepowersupplyplugand/orturnoffthebreaker.After15seconds,connectthepowersupplyplug
and/orturnonthebreaker,andthenpresstheE.O.SWonce.(TheemergencyCOOLoperationcanbeperformedcontinuouslyforupto30minutes.)
5)
Fullyclosethestopvalveonthegaspipesideoftheoutdoorunitwhenthepressuregaugeshows(
0.1to0psi[Gauge](0.05to0Mpa))
.
6)StoptheemergencyCOOLoperation.
Tostopoperation,presstheE.O.SWseveraltimesuntilallLEDlampsturnoff.Refertooperatinginstructionsfordetails.
WARNING
When pumping down the refrigerant, stop the compressor before dis-
connecting the refrigerant pipes. The compressor may burst if air etc.
get into it.
JG79Y071H02_en.indd 10 2016/01/21 13:20:07
JG79Y071H02
HEADOFFICE:TOKYOBLDG.,2-7-3,MARUNOUCHI,CHIYODA-KU,TOKYO100-8310,JAPAN
JG79Y071H02_cover.indd 2 2016/01/21 13:10:40
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32