D+H SSM 45 Operating instructions

Type
Operating instructions
99.823.01 1.0/05/06
D+H Mechatronic AG • Georg-Sasse-Str. 28-32 • D-22949 Ammersbek • Tel. +4940-60565219 • Fax +4940-60565264
Instruction for use
342
IN
SKS
56
Mot.
7
18
Mot.
ab ab
OUT
SSM 45
Edge protection modul
Temp. -5°C..40°C
30.104.80-26.05 - 000001
Edge protection module SSM 45
Application
The main/ and lateral closing edges can be
protected with the edge protection module
SSM 45.
Maximally 2 contact hoses can be connected
to the SSM 45.
The module requires no power supply of its
own. It will be looped in jointly in the power
supply lines of the drive.
Safety Notes
Danger of squeezing and violent pressure
with electric motor driven windows and flaps!
The drive will be stopped via limit stop or
overload cutoff, if automatically operated.
Developing forces can become so strong,
that parts of the body get crushed.
Danger of injury and life is existing, if a
window is located in an accessible area.
In case of mounting heights of less than
2,5m (lower edge of window!), suitable
precautions must be taken for preventing any
endangering of persons.
The contact hoses must completely cover
the main/ and lateral edges!
See guideline BGR 232 for power operated
windows, doors and gates.
Technical Data
Power supply : 24VDC
(from driving line)
Rupturing
capacity : max. 5A
Interfering : DIN EN 55011,
emission DIN EN 50081-2
Resistance to : DIN EN 50082-2,
jamming DIN EN 61000-4-2,
DIN EN 61000-4-3,
DIN EN 61000-4-4,
DIN EN 61000-4-5,
DIN EN 61000-4-6
Dimensions
(WxHxD) : 48 x 50 x 23mm
2/4 SSM 45 Rev.:1.0
If a contact hose is activated with closing of
a window, the window will automatically open
again. The drive will be triggered in OPEN-
direction for 20 seconds. After that, the drive
will be automatically run CLOSED again.
If the contact hose will be activated once
more, the drive will run OPEN again.
This process can be repeated up to three
times. After that, the drive will remain in
opened position until it will receive a new
CLOSED-signal from the control panel.
In case of interruption of contact hoses or
connecting lines, SSM 45 will recognize a
malfunction and run open the drive.
The window will remain open so long until
the malfunction is eliminated.
Information:
If a window is closed for 3 minutes, the
contact hoses will be deactivated. This will
prevent an undesirable opening of closed
windows by operating of the contact hoses.
Function
Guarantee
You will get 2 years guarantee for all D+H products from date of verified handing over of the
system up to maximal 3 years after date of delivery, when mounting and starting has been
carried out by a D+H authorized distributor.
D+H guarantee is expired, with connection of D+H components with external systems or
with mixing of D+H products with parts of other manufacturers.
1. 2.
3. 4.
20
Sec.
3/4
SSM 45 Rev.:1.0
DIP Switch adjustment
S1
without
function
function
ON
12
1
factory
preset
2
3
4
S1
ON
12
5
6
4/4 SSM 45 Rev.:1.0 All sizes in millimetre • Rights to technical modifications reserved. • Reprinting and phototechnical
reproduction also in extracts has to be expressively authorized by D+H Mechatronic AG.
Connection
1 contact hose
* Monitoring resistors are factory-connected on module (1/2 and 3/4).
If there are no resistors at the ends of the contact hoses, these monitoring resistors
must be removed from the module and connected to the ends of the contact hoses.
** When using one contact hose, leave the monitoring resistor (5k6) on the input, which is
not used!
2 contact hoses
12 3546 7
8
SSM 45
Mot.a
Mot.b
drive 24V with
load cutoff
Mot.a (-) in running direction CLOSED
Mot.b (+) in running direction CLOSED
control
panel
5k6 *
IN
SKS Mot. Mot.
ab ab
OUT
S1
ON
12
***
Mot.a
Mot.b
Mot.a (-) in running direction CLOSED
Mot.b (+) in running direction CLOSED
12 3546
SSM 45
drive 24V with
load cutoff
Mot.a (-) in running direction CLOSED
Mot.b (+) in running direction CLOSED
control
panel
5k6 *
*
IN
SKS Mot.
ab
S1
ON
12
5k6 *
*
Mot.a
Mot.b
78
Mot.a
Mot.b
Mot.a (-) in running direction CLOSED
Mot.b (+) in running direction CLOSED
Mot.
ab
OUT
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

D+H SSM 45 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI