AKO -555241 Gas Leak Detection Trapped Person Alarm User guide

Type
User guide

AKO -555241 Gas Leak Detection Trapped Person Alarm is a reliable device designed to protect you from gas leaks and ensure your safety in case of an emergency. With its advanced gas detection capabilities, it accurately monitors gas concentrations and triggers alarms when harmful levels are present, providing you with ample time to take necessary action. Additionally, the trapped person alarm feature enhances your safety by alerting others in case you become trapped or incapacitated due to gas exposure.

AKO -555241 Gas Leak Detection Trapped Person Alarm is a reliable device designed to protect you from gas leaks and ensure your safety in case of an emergency. With its advanced gas detection capabilities, it accurately monitors gas concentrations and triggers alarms when harmful levels are present, providing you with ample time to take necessary action. Additionally, the trapped person alarm feature enhances your safety by alerting others in case you become trapped or incapacitated due to gas exposure.

AKO-555241 AKO-558241
AKO-555242 AKO-558242
Wiring
Always disconnect the power supply to carry out wiring.
The wiring between the transmitter / detector / push-button
and the station should NEVER be installed in a conduit alongside
power, control or supply cables.
For disconnection, the power supply circuit must be equipped with
a switch of at least 2 A, 230 V, located near the device. The power
supply cable will be H05VV-F or NYM 1x16/3. The section to be
used will depend on current local regulations, but should never be
2
less than 1.5 mm .
Cables for wiring the relay contact should have the relevant
section for the device to be connected
The 120 / 230 V~ wiring must be kept clear of any other external
element.
Make sure you have connected the batteries before
starting up the device. (AKO-558xxx models are not equipped
with batteries.).
Certain international standards indicate that alarm power supply
should originate from a different circuit to that used for the
refrigeration and ventilation system. Be sure to comply with
current local regulations.
Technical specifications
Power supply ........................................................................................................100-240 V~ 50/60 Hz
Maximum input power ...................................................................................................................15 W
Accumulators (Only AKO-555xxx).......................................................................................Ni-MH 1.6 Ah
Lighting + alarm autonomy (Only AKO-555xxx).................................................................> 10 Hours (*)
No. of inputs AKO-555241/558241..............................................................................................2
AKO-555242/558242..............................................................................................4
Compatibility of inputs.............................................................AKO-52326, AKO-5761x, AKO-575xxx
Relays.......................................................................................................................SPDT 8(2)A 250 V~
Working ambient temperature ...........................................................................................-5 ºC to 50 ºC
Storage ambient temperature.......................................................................................-30 ºC to 60 ºC
Protection degree........................................................................................................................IP 65
Installation category...................................................................................................II s/ EN 61010-1
Pollution degree.........................................................................................................II s/ EN 61010-1
Double isolation between power supply, secondary circuit and relay output.
Sound power ........................................................................................................90 dB(A) at 1 metre
MODBUS address ........................................................................................................Shown on label
Maximum push-button cable distance........................................................................................300 m
Dimensions .........................................................................290 mm (W) x 141 mm (H) x 84.4 mm (D)
5552H412 Ed.03
355552412 Rev 02 2023
AKO ELECTROMECÁNICA , S.A.L.
Avda. Roquetes, 30-38
08812 Sant Pere de Ribes.
Barcelona Spain.
www.ako.com
en
Pre-alarm
jumper Pre-alarm disabled
Pre-alarm enabled
CC NCNC NONO
15V
15V
In
In
Gnd
Gnd
Gas
Pre-Alarm
CAM 1
Gas
Alarm
CAM 1
Input 1 RY3
RY2
Input 2
CC NCNC NONO
15V
15V
In
In
Gnd
Gnd
Gas
Pre-Alarm
CAM 2
Gas
Alarm
CAM 2
Input 3* RY5*
RY4*
Input 4* Vac
100 -
240 V~
50/60 Hz
Tr-
C C
Tr+
1NO
Gnd
2NC
Gnd
DI1
DI2
Gas
system
failure
Trapped
person
RS485 RY1 Gas Fail
Mute
Sethold
Remote
Set Hold
Remote
mute
SECURE
H.E. push-button
15V
In
Gnd
Input x
15V
Out
*Only AKO-555242 / 558242
Gas leak detection
+ trapped person alarm
Quick guide
Warnings
-The alarm and the transmitters / detectors should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in
the technical data. The station should be installed in a monitored area, where it is guaranteed that people able to alert to the presence of alarms will be present.
-Neither the alarm nor the gas transmitter / detector are suitable for areas classified as potentially explosive.
-Transmitters / detectors measure gas concentration at a given point. If the gas leak does not reach the transmitter / detector, the alarm will not be activated.
-Transmitters / detectors cannot supervise areas. If perimeter supervision is required, several transmitters / detectors should be installed surrounding the area to be supervised.
-Thoroughly studying transmitters’ / detectors’ location is recommended, bearing in mind the areas most vulnerable to suffering leaks, the type of gas used, the size and shape of the room, air flows,
maintenance work, etc.
-The EN-378 and F-GAS international standards require that correct transmitter / detector functioning be checked at least once per year. Review what current local regulations specify for these cases.
Consult the appropriate verification method in the transmitter / detector manual.
Work conditions:
-Avoid handling refrigerant gases near the transmitter / detector. Do not paint the transmitter / detector or place it near solvents or paints. Exposure to acetone vapours may cause false alarms.
-The transmitter / detector should be installed away from:
-Smoke outlets located in or originating from engines, generators or motorised machinery (fork-lift trucks, etc.).
-Particularly damp areas or with strong ventilation.
Gas transmitter / detector
AKO-575xxx / AKO-5761x
15V
S
GND
15V
In
Gnd
Input x
We reserve the right to supply materials that might vary slightly to those described in
our Technical Sheets. Updated information is available on our website.
ON
OFF
Configuration
Step 1:
Connect the station power supply. Input indicators illuminate sequentially.
Step 2:
Press the AUTOCONFIG” push-button for 5seconds; the alarm will emit 5short tones.
Configuration is complete.
For correct input detection, all devices must be correctly connected and in NO
ALARM mode, including devices connected via digital inputs.
Once the alarm has been configured, this function will not be activated again. To
activate it again, disconnect the power supply, connect it again and press the
AUTOCONFIG” pushbutton 5 times consecutively within 2 minutes and repeat
step 2 within another 2 minutes.
Once configured, the display shows in green the indicator corresponding to the device
detected at each input:
Luminous push-button Gas detector / transmitter
Pre-alarm jumper
Activates / deactivates pre-alarm detection. Before using this
option, ensure that regulations allow for two alarm levels.
When using the ammoniac or CO detector, the pre-alarm must be
2
enabled.
Operation
No alarms
The input indicators are green.
Alarm activated
The station emits an audible alarm sound, shows the affected
input(s) in red, the general alarm indicator illuminates and the visual
alarm flashes.
Gas alarm saved
An alarm has sounded in the past.
The affected input indicator flashes green.
Wiring error / malfunction
The station emits 3 short beeps every two minutes and the affected
input indicator flashes red.
Short-circuit in an input
The affected input indicator will flash red and the input will be
disabled. The general alarm indicator will also flash. Once the
problem has been resolved, to re-establish functioning of the
affected input, press the Mute button for more than 1 second.
Alarm tones:
ŸTrapped person alarm / gas alarm: Bi-tonal sound.
ŸGas pre-alarm: Intermittent sound.
ŸWiring error / malfunction: 3 short beeps every 2 minutes.
MUTE Function
Cancels alarm tone in the event of gas pre-alarm or alarm. To activate
it, press the Mute key.
Does not affect relay or indicator functioning.
Trapped person alarms cannot be silenced.
Indicator is shown on the displayMMM
Set Hold Mode
Avoid false alarms during the chamber charging or cleaning process.
When this mode is activated, pre-alarms will not sound and alarms will
sound like pre-alarms to all effects (sound, relay and signal activation).
To activate / deactivate it, press the Mute key for 3 seconds; the display
will show indicator .SSSS
Unless it is manually deactivated, this mode will remain activated for a
maximum of 5 hours, before automatically deactivating itself.
Maintenance Mode
Disables gas pre-alarms and alarms for 1 hour for maintenance tasks.
When it is activated, no gas pre-alarm or alarm will sound.
To activate / deactivate it, press the Mute key for 6 seconds; indicator
SSSS will flash.
In the event of a power failure, the gas detectors will
disconnect to extend battery duration and the corresponding
indicator will switch off on the display
Trapped person alarm inputs will continue to operate until their
batteries run flat.
Relays
See accompanying table
Pre-alarm disabled
Pre-alarm enabled
SECURE
AUTO-CONFIGURATION
push-button
PRE-ALARM
jumper
Input
1
Input
2
Input
1
Input
3
Input
2
Input
4
Constant green: Trapped person push-button connected.
Quick-flashing red: Malfunction / wiring fault in push-
button.
Slow-flashing red: Push-button not detected or
disconnected.
Constant red: Trapped person alarm activated.
Green constant: Gas transmitter / detector connected.
Flashing green: Gas pre-alarm / alarm saved
Quick-flashing red: Malfunction / wiring fault in gas
transmitter / detector.
Slow-flashing red: Gas transmitter / detector not detected
or disconnected.
Constant red: Gas pre-alarm / alarm activated.
Constant: Gas pre-alarm / alarm / trapped person
alarm activated.
Flashing: Malfunction / wiring fault in detector /
transmitter / push-button.
Description
Pressing for 3 seconds activates / deactivates the Set Hold mode.
Pressing for 6 seconds activates / deactivates the maintenance mode
Pressing briefly deletes saved alarms
For gas alarm, pressing briefly silences the alarm tone.
Trapped person alarms cannot be silenced.
Constant: Set Hold mode activated
Flashing: Maintenance mode activated
Power supply
present
Bluetooth activated (Only
with CAMM module)
Constant green: Battery connected
Switched off: Battery disconnected *
Gas alarm
silenced
Constant: CAMM module in operation
Flashing: CAMM module malfunction.
STATUS
Relays
Trapped person
System failure
Gas Pre-alarm 1 / 2
Gas Alarm 1 / 2
With power supply
Battery connected *
A
C
E
G
With power supply
Battery disconnected *
A
C
E
G
No power supply /
With battery *
A
C
E
G
No power supply/
No battery
B
D
E
G
Trapped person alarm
activated
B
C
E
G
Gas pre-alarm activated
A
C
F
G
Gas alarm activated
A
C
E
H
Wiring fault in gas
detector
A
D
E
G
C1 2C1 2
CNC NOCNC NO
CNO NCCNO NC
CNC NOCNC NO
Without alarms
A
C
E
G
B
D
F
H
Maintenance
Clean the device surface with a soft cloth, water and soap.
Do not use abrasive detergents, petrol, alcohol or solvents, as this
might damage the sensor.
1
2
Visual alarm
Alarm display
Audible alarm
Mute /
Set Hold key
AKO-555241 / AKO-558241AKO-555242 / AKO-558242
* AKO-558xxx models are not equipped with batteries.
  • Page 1 1
  • Page 2 2

AKO -555241 Gas Leak Detection Trapped Person Alarm User guide

Type
User guide

AKO -555241 Gas Leak Detection Trapped Person Alarm is a reliable device designed to protect you from gas leaks and ensure your safety in case of an emergency. With its advanced gas detection capabilities, it accurately monitors gas concentrations and triggers alarms when harmful levels are present, providing you with ample time to take necessary action. Additionally, the trapped person alarm feature enhances your safety by alerting others in case you become trapped or incapacitated due to gas exposure.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI