1.7 FITTING TO FIREPLACES WITH EXISTING CHAIRBRICKS AND
CONVENTIONAL BRICKBUILT CHIMNEYS
This appliance is suitable for use in fireplaces fitted with an existing chairbrick
without the need for removal of the chairbrick, providing the minimum depth of the
fireplace exceeds 190mm. If the depth is less than 190mm then the spacer
(optional) must be used to give a minimum clearance from the rear of the fire to
the rear of the chairbrick of at least 90mm to allow sufficient space for the collec-
tion of debris which may fall down the chimney. The fireplace must be checked to
ensure that no part of the chairbrick is within 50mm of the flue outlet of the fire
when installed.
1.8 FITTING TO PRE-CAST FLUE INSTALLATIONS
When installing this appliance into pre-cast flues, always ensure that the spigot
restrictor baffle has been removed. (2 screws). To install the fire box in to pre-cast
flue starter blocks, there must be at least 120mm from the mounting face of the
fire to the rear of the pre-cast flue starter block. It is important to consider this
depth when choosing a fire surround as the thickness of the fire surround must be
sufficient to give a total depth of at least 120mm to the rear of the starter block,
otherwise there will be insufficient depth. To increase this depth the fire surround
may be packed away from the wall and sealed using suitable material when used
in conjunction with a rebated fire surround. It is important to ensure that the pre-
cast flue is in good condition and is free from extruded mortar or sealant from
between the flue blocks. This appliance has been tested for use in a pre-cast flue
block system complying with BS EN 1858 / BS 1289, that has a minimum cross
sectional of 13,328mm
2
and no minor dimension of less than 63mm. Pre-cast
flues built with directly plastered faces (front or rear) are not correctly installed as
to ensure proper operation with any type of inset gas fire. In some instances of
this flue construction, temperature cracking of surface plaster may occur through
no fault of the appliance. An air gap or some form of insulation material should be
installed to prevent normal flue temperatures from damaging wall surfaces. BFM
Europe will not be liable for subsequent costs incurred due to installation of
products into pre-cast flue systems with directly plastered faces. It is important to
ensure that the pre-cast flue is in good condition and is free from extruded mortar
or sealant from between the flue blocks. A spillage test must always be carried out
to check satisfactory clearance of combustion products is achieved on all pre-cast
flue types.
1.9 FITTING TO PRE-FABRICATED TWIN WALL METAL FLUE BOXES
The appliance may be fitted to twin wall metal flue boxes conforming to the con-
structional requirements of BS 715, (for example the Selkirk LFE 125 box). The
box must have a minimum flue diameter of 125mm internal and minimum internal
dimensions of 160mm deep by 580mm high by 350mm wide. There are no maxi-
mum dimensional requirements for the box. The top face of the box must be
insulated with a minimum thickness of 50mm of non-combustible mineral wool
8