16
offî135îsecondsîafterîtheîgasîvalveîisîclosed.î(Theîheatingî
blowerîoffîdelayîisîfactoryîsetîatî90îseconds.îThereîisîanî
additionalî45îsecondîoffîdelayîprogrammedîintoîtheîX-13î
blowerîmotorîforîaîtotalîofî135îseconds)
Verifying Burner Operation â To verify operation of
the burners remove the louvered control access panel to
ensureîthereîisîpowerîtoîtheîunit.îSetîtheîthermostatîtoî
a temperature above room temperature and observe the
ignitionîsequence.îTheî burnerî îameî shouldî carryî overî
immediatelyîbetweenîallîburners.îTheîîamesîshouldîbeî
blue,îwithoutîyellowîtips.îFlamesîshouldîextendîfromîeachî
burnerîwithoutîliftingîoff,îcurling,îorîîoating.îîAfterîverifyingî
satisfactoryîîameîcharacteristics,îsetîtheîthermostatîtoîaî
temperatureîbelowîroomîtemperatureîandîverifyîthatîtheî
burnerîîameîextinguishesîcompletely.
WARNING:
Uninsulatedîliveîcomponentsîareîexposedîwhenî
louvered control access panel is removed.
Verify Operation of Over-Temperature Limit Control
âîîToîverifyîoperationîofîtheîover-temperatureîlimitîcontrol,î
makeî sureî thatî theî louveredî controlî accessî panelî isî
inîplaceîandîthatî thereîisîpowerîtoîtheîunit.îîBlockîtheî
returnîairîowîtoîtheîunitîbyîinstallingîaîclose-offîplateîinî
place of or upstream of the ïŹlter. Set the thermostat to a
temperature above room temperature and verify the unit
operatesîwithîtheîcorrectîîsequenceîofîoperationî(seeîpageî
25). The over-temperature limit control should function to
turnîoffîtheîgasîvalveîwithinîapproximatelyîfourîminutesî
(theîexactîtimeîdependingîonîtheîefîŹciencyîofîtheîclose-
offîinîblockingîtheîreturnîairîtoîtheîunit).îTheîcirculatingî
airîandîcombustionîblowersîshouldîcontinueîtoîrunîwhenî
theîover-temperatureîlimitîcontrolîswitchîopens.îRemoveî
the close-off immediately after the over-temperature limit
control opens. If the unit operates for more than four minutes
withînoîreturnî air,îsetî theî thermostatî toîaîtemperatureî
belowîroomîtemperature,îshutîoffîtheîpowerîtoîtheîunit,î
and replace the over-temperature limit control.
COMPONENT FUNCTIONS
Flame Sensor âîTheî îameî sensorîactsîtoîproveîthatî
îameîhasîcarriedîoverîfromîtheîignitorîtoîtheîright-mostî
burner.îîIfînoîîameîisîsensed,îtheîunitîwillîbeîshutîdownî
automatically.
Flame Roll-Out Control âîTheîîameîroll-outîcontrolîactsî
toîverifyîthatîtheîburnerîîameîisîbeingîdrawnîintoîtheîheatî
exchangerîtubes.îîIfîtheîburnerîîameîisînotîbeingîdrawnî
intoî theî heatî exchangerî tubes,î theî roll-outî controlî willî
openîwithinîseveralîsecondsîandîtheîintegratedîcontrolî
diagnosticî lightî willî îashî oneî time.î Theî circulatingî airî
blowerîandîcombustionîblowerîwillîcontinueîtoîoperateîifî
theîîameîroll-outîcontrolîopens.
5.î Multiplyîtheîgasîîowîrateîinîcubicîfeetîperîhourîbyî
the heating value of the gas in Btu per cubic foot
toîobtainîtheîîŹringîrateîinîBtuîperîhour.îExample:
a.î Timeîforîoneîrevolutionîofîaîgasîmeterîwithîaîîîîîîî
one cubic foot dial = 40 seconds.
b. From Table 8 read 90 cubic feet per hour of
gas.
c.î Heatingî valueî ofî theî gasî (obtainedî fromî gasîîî
supplier) = 1040 Btu per cubic foot.
d.î Firingîrateî=î1040îxî90î=î93,600îBtuh.
6.î Adjustmentsî toî theî îŹringî rateî canî beî madeî byî
adjustingîtheîgasîmanifoldîpressure.îSeeîtheîHighî
Altitude Application section for additional information
of ïŹring rate at elevations above 2000 ft.
The manifold pressure must be set to the appropriate value
for your installation. Refer to either Table 5 for natural
gas or Table 6 for LP/propane gas to verify the manifold
pressure setting required for your particular installation.
Toîadjustîtheîmanifoldîpressure,îremoveîtheîregulatorîcapî
andîturnîtheîadjustingîscrewîclockwiseîtoîincreaseîpres-
sureîorîcounterclockwiseîtoîreduceîpressure.îReplaceîtheî
regulatorîcapîafterîadjustmentsîareîcomplete.î
Verifying and Adjusting Temperature Rise âîVerifyî
thatîtheîtemperatureîriseî throughîtheîunitîisî withinî theî
range speciïŹed on the unit data label. Temperature rises
outside the speciïŹed range could result in premature heat
exchanger failure.
Place thermometers in the return and supply air stream
as close to the duct connections as possible. The
thermometer on the supply air side must be shielded
from direct radiation from the heat exchanger to avoid
falseîreadings.îAdjustîallîregistersîandîductîdampersîtoî
the desired position and run the unit for ten to ïŹfteen
minutesî beforeî takingî anyî temperatureî readings.î îTheî
temperatureî riseî isî theî differenceî betweenî theî supplyî
and return air temperatures.
Forîtypicalîductîsystems,îtheîtemperatureîriseîwillîfallîwithinî
theîrangeîspeciîŹedîonîtheîdataîlabelîwithîtheîblowerîspeedî
at the factory recommended setting (see Table 3). If the
temperatureîriseîmeasuredîisîoutsideîtheîrangeîspeciîŹed,î
itîmayîbeînecessaryîtoîchangeîtheîblowerîspeed.îLowerî
blowerîspeedsîwillîincreaseîtheîtemperatureîriseîandîhigherî
blowerîspeedsîwillîdecreaseîtheîtemperatureîrise.
Theîunitîisîequippedîwithîaîmulti-speedîmotor.îAîheatingî
and cooling speed selection is made by moving the leads
onîtheîblowerîmotorîterminalîblock.îîTheîwiringîdiagramî
on the unit and in Figure 10î showî theî speedî tapsî forî
adjustingîmotorîspeed.îReferîtoîtheîBlowerîSpeedîSectionî
of this installation instruction for more details.
The integrated control is designed to start the circulating
airîblowerî30îsecondsîafterîtheîgasîvalveîisîopened.îTheî
integratedîcontrolîisîfactoryîwiredîtoîturnîtheîblowerîmotorî