1592002510 XT11S GB-IT r1 0 05 05 2015 XT11S 1/1
XT11S
Electronic Digital Thermometer with
maximum / minimum temperature log
1. GENERAL WARNING
PLEASE READ BEFORE USING THIS MANUAL
• This manual is part of the product and shall be kept near the
device for easy and quick reference.
• Check the application limits before proceeding.
• Dixell Srl reserves the right to change the composition of its
products, even without notice, ensuring the same and unchanged
functionality.
SAFETY PRECAUTIONS
• WARNING: this equipment should be installed, adjusted and
serviced by qualified electrical maintenance personnel familiar
with the construction and operation of the equipment and the
hazards involved. Failure to observe this precaution could result
in bodily injuries.
• Dixell is not responsible for any impairment or damage
caused by the product if used in a not specified manner.
• Always ensure that the probe is connected to the instrument
before the power supply is connected and turned ON.
• Check the supply voltage is correct before connecting the
instrument.
• The probe is under NO extra low safety voltage for models
with 230V or 110V power supply.
• For the model at 230V or 110V a double insulation probe has to
be used, NOT SUPPLIED.
• Use insulated quick connector terminals for voltage and probe.
• The instrument is designed for panel mounting and electrical
connections must be positioned inside a properly protected
board/panel.
• Do not expose to water or moisture: use the instrument only within
the operating limits avoiding sudden temperature changes with
high atmospheric humidity to prevent condense formation.
• Warning: disconnect all electrical connections before any kind of
maintenance.
• The instrument shall never be opened.
• In case of failure or faulty operation send the instrument back to
the retailer or to “Dixell S.r.l.” (see address) with a detailed
description of the fault.
• Assure that the wires for probes and for power supply are
separated and far enough from each other, without crossings and
spirals.
• To see the max and minimum recorded temperatures, use a S1
Class II approved push button, normally open, connected as
indicated in par. 5.
2. GENERAL DESCRIPTION
The XT11S is a new electronic digital thermometer which displays
the current temperature and also logs the maximum and minimum
temperatures experienced.
These max. / min. temperatures can be displayed at the touch of a
button and reset if required.
3. INSTALLATION - 230V OR 115V VERSION (FIG.1)
The instrument is equipped with fast-on type spade terminals with
probe connections separated from the power supply connections. To
install the instrument proceed as follow:
Use insulated quick connector terminals for voltage and
probe.
Probe
input
Power Supply
Line
(N)
(L)
(N) (L)
P1
NTC
Fig.1
1. Make a 59x25,5 mm (1.01x2.32 inch) hole in a panel with a
thickness between 0.8mm and 2.7mm.
2. Take the instrument from the box and place it in the hole until
the side flaps click, which means they are locked.
3.
Disconnect the power supply from the board by
means of a panel switch, not supplied, (P1 in Fig.1).
4.
A Class II and certified according to IEC 60947-1 and
60947-3 approved panel switch has to be used.
5.
Fit the panel switch near the XT11S, in a place easy to
reach, to make the power supply disconnection easy.
6. Place the probe where it has to measure the temperature.
7. Connect the probe terminals to the 2.8mm. fast-on as
indicated.
8. For supply use double insulation cables, with at least 0.75 mm²
as diameter.( AWG minus or equal to 20.)
9. To protect the instrument against over current a 63mA
external fuse has to be used.
10. Connect the power supply cables to the 6.3mm. fast-on.
11. If possible, the manufacturer suggests connecting the phase
(L) to the fast-on on the right and neutral (N) to the fast-on on
the left as indicated.
12. At this stage the board can be connected to the power supply
once more.
4. DISPLAY OFFSET ADJUSTMENT
1. It’s possible to adjust the display visualisation in the range –
10÷10°C, in case of wrong read-out of the probe.
2. To do it, use a 3mm screwdriver to rotate the potentiometer
till the thermometer display the right temperature.
5. DISCONNECTION AND PROBE SUBSTITUTION
(FIG.1)
1. Disconnect the power supply on the board where the
instrument is positioned, by means of the panel switch (P1
in Fig.1)
2. Remove the power supply fast-ons.
3. Disconnect the instrument and the probe.
6. EXTERNAL PUSH-BUTTON CONNECTION (FIG.2)
In order to display the maximum and minimum values on the
instrument, use the S1 Class II approved type push button, normally
open. Button has to be rated for the maximum main supply voltage.
(NOT SUPPLIED).
1.
Disconnect the power supply on the board where the
instrument is positioned, by means of the panel switch (P1
in Fig.1)
2. Connect the push button in parallel with the probe as shown in
Fig.2.
Probe
input
Power Supply
NTC
S1
0
-
+10°C
+17°F
-10°C
-17°F
S1: external
push button
Probe
Fig.2
3. Place the probe where it has to measure the temperature.
4. Connect the probe terminals to the 2.8mm. fast-ons as
indicated.
5. For supply use double insulation cables, with at least 0.75
mm² as diameter (AWG minus or equal to 20).
6. Connect the power supply cables to the 6.3mm. fast-ons.
7. If possible, the manufacturer suggests connecting the phase
(L) to the fast-on on the right and neutral (N) to the fast-on on
the left as indicated.
8. At this stage the board can be connected to the power supply
once more.
7. DISPLAY OF MIN. AND MAX. TEMPERATURES
LOGGED
Once the button for min & max temperatures has been
connected, proceed as follows:
Maximum temperature display:
1. Press and hold the push button (S1) till the display reads “HI”.
2. Release S1 and the highest temperature recorded since the
last reset will be displayed for 3 seconds.
Minimum temperature display:
1. Press and hold the push button (S1) till the display reads “LO”.
2. Release S1 and the lowest temperature recorded since the last
reset will be displayed for 3 seconds.
Probe offset value display:
1. Press and hold the push button (S1) till the display reads “PO”.
2. Release S1 and the probe offset value will be displayed for 3
seconds.
Maximum /minimum temperature reset
:
1. Press and hold the push button (S1) till the display reads “rE”.
2. Release S1 and the display will flash “rE” for 5 seconds.
3. While the display is flashing press the push button and the
max&min temperature will be erased.
Power on and power failure warning:
When the power supply is turned on and after any power failure,
when the max. and min. set values are visualised, the display
flashes. This is to warn the user that there has been an interruption
to the power supply.
To restore normal operation, follow the same procedure that is used
for re-setting the maximum/minimum memory. (see Maximum
/minimum temperature reset).
8. MAINTENANCE AND CLEANING
Instruments do not require particular maintenance. To clean frontal,
just use a soft moist cloth and avoid using any strong detergent or
solvent.
9. TECHNICAL DATA
Case: 64x31mm, depth: 19.5mm; self extinguishing polycarbonate.
Mounting: only for panel mounting; 25,5x59mm panel cut out
(1.01x2.32inc.).
Frontal protection: IP20.
Electrical connections: fast-on type spade terminals with probe
connections (2.8mm) separated from power supply
connections (6.3mm).
Power supply: 230Vac ±10% 50/60Hz VDE approved
or 110Vac ±10% 50/60Hz, or 12Vac/dc, or 24Vac/dc.
Absorbed current: 40mA.
Probe: NTC with double isolation for 230Vac or 110Vac version.
Display and measurement units:
- 50.0÷99.9 °C => 100 to110°C; -40÷230 °F
NTC standard probe: -30÷105°C (-22÷220°F).
Display update delay times (optional) when the temperature
increases: fixed at 1 or 3 minutes depending on model
specified at time of order.
Operating temperature: T60°C/32÷140°F.
Storage temperature: -30÷75°C/-22÷167°F.
Relative humidity: 20÷85% (no condensing).
Maximum working height: 2000m a. s. l.
Installation category III; Transitory over-voltage: 4000V.
Pollution degree: 2 according to IEC 664.
Offset: ±10°C (±17°F).
Accuracy: from -30 to -10°C (-22÷14°F): 1°C (2 °F) ±1 digit.
from -10 to 110°C (14÷230°F): 0,5°C (1 °F) ±1 digit.
Only for 230V