1-4
MODELS 4081T SECTION 1.0
INSTALLATION
1.3 ELECTRICAL INSTALLATION
1.3.1 Conductivity Sensors
Rosemount Analytical Inc.’s inductive conductivity sensors
with PT100 are compatible with the Model 4081T transmit-
ter. Please refer to Figures 1-4 thru 1-6 for appropriate
sensor to transmitter wiring. The sensor cable should be
routed through the conduit opening closest to the Pin 2
connection.
1.3.2 Power Supply/Current Loop Wiring.
The Model 4081T operates within a range of 9-32 VDC
power. The power supply wiring routes through the conduit
opening closest to pin number 16. Connect as illustrated in
Figure 1-7. For shielded power supply cable, the shield
should be connected to the earth ground connection.
The Model 4081T sensor connection requires connecting
the white toroid wire (see Figure 1-5) to either TB-1 pin 11
(indicated on the inside of the terminal end cap) for high
range, or TB-1 pin 12 for low range. To access the terminal
block, unscrew the terminal end cap.
1.3.3 Hazardous Area Installation
In order to maintain the hazardous area rating for installed
transmitter, the following drawings must be used:
Figure 1-9. Wiring for FM Explosion-Proof Installation for
Model 4081T (Drawing Number 1400175)
Figure 1-10. Wiring for CSA Intrinsic Safety for Model 4081T
(Drawing Number 1400190). See also label (right).
Figure 1-11. Wiring for FMRC Intrinsic Safety for Model
4081T (Drawing Number 1400185).
1.4 INSTALLATION VERIFICATION
1.4.1 Overview. Verification of installation includes ensur-
ing that the proper precautions have been observed during
the installation process and recognizing whether the
instrument is operating properly upon power up.
1.4.2 Precautionary Checklist. Before applying power
verify the following:
1. Sensor wiring and power supply/loop wiring are not in
the same conduit.
2. Sensor or power supply/loop wiring are at least 12
inches from any high current lines.
3. Sensor chosen is compatible with the 4081T
Transmitter.
4. Terminal end cap has been replaced.
1.4.3 Power Up. Activate power supply. Upon powering
up, with the sensor in solution, the transmitter:
1. Should display a live conductivity reading in large, dark
numerals on a gray background.
2. Should display the present temperature in smaller numer-
als on the lower line of the display screen.
3. Should NOT have the word FAULT or HOLD appearing on
the left edge of the display. The display should not be flash-
ing.
TABLE 1-1. Hardware/Software Compatibility
(Measurement Range [µS/cm]*)
MANUAL RANGE 1 2 3
Low Range 80 to 800 to 7,500 to
(accuracy: ± 1.0%) 800 7,500 80,000
High Range 1,100 to 11,000 to 100,000 to
(accuracy: ± 1.0%) 11,000 100,000 1,100,000
Wire Terminal
11
or 12
*NOTE: Values shown are for uncompensated conductivity using
a cell constant of 1.0. The conductivity values auto
ranges from 0 to 2,000,000
µS/cm with an accuracy of
5 to 10%
±150 µS/cm depending on the process con-
ditions, installation, and the sensor used. For greater
accuracy and repeatability, manual range selection is
recommended.
LABEL, I.S. N.I. & EX CSA approved for Model 4081T