Elvaco CMe2100 Quick Manual

Type
Quick Manual
CMe2100 Quick Manual English v4.0 Page | 1
CM e2 100 Qu i ck M an u al
CM e2100
English
Version 4.0
Get the com plete m anual online at ww w.elvaco.com
Page | 2 Support: +46 300 434300 ? support@elvaco.com
Cont ent s
1 DOCUMENT NOTES............................................................................ 3
2 INTRODUCTION .................................................................................. 6
3 MOUNTING ....................................................................................... 10
4 CONFIGURE FOR E-MAIL REPORTS ................................................. 14
5 CONFIGURE FOR FTP REPORTS ....................................................... 17
6 CONFIGURE FOR HTTP REPORTS .................................................... 19
7 CONFIGURE FOR TRANSPARENT M-BUS ........................................ 21
8 RESET TO FACTORY DEFAULT......................................................... 23
9 CHANGING CONFIGURATION .......................................................... 24
10 LED INDICATIONS............................................................................. 33
11 TROUBLESHOOTING ........................................................................ 36
12 REPORT TEMPLATES ........................................................................ 43
13 COMM AND LISTING ......................................................................... 46
14 TECHNICAL SPECIFICATIONS .......................................................... 49
15 SAFETY AND ENVIRONMENT .......................................................... 56
16 ACCESSORIES AND SIMILAR PRODUCTS ....................................... 59
CMe2100 Quick Manual English v4.0 Page | 3
1 Do cum en t no t es
All information in this manual, including product data, diagrams, charts,
etc. represents information on products at the time of publication, and is
subject to change by Elvaco AB without notice. It is recommended that
customers contact Elvaco AB to find out the latest available documentation.
Elvaco AB assumes no responsibility for technical inaccuracies,
typographical errors or any damage, liability, or other losses by use of
this product.
© 2014, Elvaco AB. All rights reserved. No part of the contents of this m anual may be
transm itted or reproduced in any form by any m eans without the written perm ission
of Elvaco AB. Printed in Sweden.
Page | 4 Support: +46 300 434300 ? support@elvaco.com
This manual provides information needed to get started with the
CMe2100 product.
CMe2100 version appliance: >= 1.2.0
For a complete description of the CMe2100 product, download the full
manual from Elvaco AB web site, w w w .elv aco.c om .
CMe2100 Quick Manual English v4.0 Page | 5
1.1 Cont act i nf orm at i on
Elv aco A B Headquar t er
Teknikgatan 18
434 37 Kungsbacka
SWEDEN
Phone: +46 300 30250
Fax: +46 300 18440
E-Mail: info@elvaco.com
Elv aco A B Techni cal Support
Phone: +46 300 434300
E-Mail: support@elvaco.com
Online: www.elvaco.com
Page | 6 Support: +46 300 434300 ? support@elvaco.com
2 Int roduct ion
The CMe2100 is a stand-alone, DIN-mounted GSM/GPRS equipment
with M-Bus master, intended to read and store values from any m eter
supporting the M-Bus protocol.
The CMe2100 is available in the following variants:
CMe2100 GPRS M-Bus terminal with M-Bus 2-wire interface and
E-Mail support
CMe2100 Quick Manual English v4.0 Page | 7
2.1 K ey f eat ur es
ï‚· Read and store meter data from ABB electricity meters with
IR interface or any slaves supporting the M-Bus standard protocol
ï‚· Connect up to 8 M-Bus slaves, extendable using CMeX Series
ï‚· Send a variety of meter data reports using E-Mail, FTP, HTTP and SM S
ï‚· Transparent M-Bus using TCP and GSM data
ï‚· Configurable using SMS ,Telnet and HTTP
ï‚· Remotely upgradable application and firmware
ï‚· Manufacturer specific report templates
The CMe2100 fits into almost any kind of meter collecting system, i.e.
remote reading for M-Bus compatible electricity meters, water meters,
gas meters, temperature meters, heat meters etc.
Page | 8 Support: +46 300 434300 ? support@elvaco.com
2.2 Over vi ew
1. Serial number
2. Button
3. M-Bus connector
4. Antenna SM A connector
5.
M
-
Bus IR interface
CMe2100 Quick Manual English v4.0 Page | 9
6. GSM LED (Yellow)
7. Error LED (Red)
8. Status LED (Green)
9. SIM card holder
10. Service interface
11. Power supply N
12. Power supply L
Page | 10 Support: +46 300 434300 ? support@elvaco.com
3 M o u n t ing
The CMe2100 should be mounted on a DIN-rail. The metallic clip on the
bottom is used to mount and demount the unit from the DIN-rail. For
safety reasons, a DIN-rail enclosure must cover the terminals.
3.1 SIM car d
Install the GSM SIM card into the SIM card holder (9). Remember the
phone number for later use.
IMPORTANT
ï‚· The SIM card shall not have any PIN code activated
ï‚· The SIM card must have GPRS internet access activated for full
functionality
ï‚· If a prepaid SIM card is used, ensure that enough credits are available
CMe2100 Quick Manual English v4.0 Page | 11
3.2 A nt enna
The antenna should be connected to the SMA connector (4). Depending
on signal strength and environment, a different antenna with extension
cable can be used. Torque should be finger tight.
IMPORTANT
ï‚· Do not mount the antenna close to any metallic objects
ï‚· Do not mount the antenna close to the M-Bus 2-wire bus
ï‚· Do not mount the antenna inside a metallic cabinet
3.3 M -Bus 2-w ire bus
M-Bus is a multi-drop 2-wire bus with no polarity. A cable of either
shielded (typically 4 x 0.8 m m diam./0.5 mm
2
) telephone type or
standard mains type (1.5 mm
2
) should be used. Connect the wiring to
the connector (3). Do not exceed the maximum cable length of 1000 m.
Page | 12 Support: +46 300 434300 ? support@elvaco.com
IMPORTANT
ï‚· The internal M-Bus interface can handle up to 8 slaves. Overloading
the bus causes communication problems with the connected slaves.
ï‚· All connected slaves must have unique M-Bus secondary addresses.
3.4 IR i nt erf ace w i t h A BB elect ri cit y m et er s or
CM eX Seri es m odul es
When the IR interface will be used beside an ABB electricity meter or
CMeX module, the IR shield (5) should be removed. The CM e2100
should be mounted on the left side of the ABB electricity m eter or CMeX
module. There shall be no space between the CMe2100 and the ABB
electricity meter or CM eX module. (Do not remove the shield if not used
beside an ABB electricity meter or CM eX module.)
CMe2100 Quick Manual English v4.0 Page | 13
3.5 Pow er suppl y
The main supply should be connected to the power supply screw
terminals (11) and (12). Main supply voltage should be in the range of
100-240 VAC, 50/60 Hz. The CM e2100 will be running factory default
settings when first powered up.
An emergency circuit breaker should be used in order to ensure safe
separation of the CMe2100 product from the main power supply.
The next chapters cover the configuration of the CMe2100 product. If any
problem occurs during configuration, please refer to the
Troubleshooting section on page 33.
Page | 14 Support: +46 300 434300 ? support@elvaco.com
4 Co n f igure f o r E-M ail rep o rt s
This section describes how to enable the CMe2100 product to send
E-Mail reports of connected slaves to one or more E-Mail recipients. The
CMe2100 product will store hourly values of connected slaves, send
value reports every day at 00:00 and send an E-Mail installation report
on completion.
4.1 Set E-M ai l r eci pi ent s
SMS to CMe2100 product: qset email <recipients>
Example: qset email name@domain.com,name2@domain.com
The CMe2100 product will acknowledge with an SMS receipt.
CMe2100 Quick Manual English v4.0 Page | 15
4.2 Sear ch and i nst all M -Bus sl aves
The CMe2100 product will search and install M-Bus slaves using primary
and secondary addressing on 2400 baud and synchronize time with an
internet time server.
SMS to CMe2100 product: install <slaves> <profile> <mode>
Par am et er d escr ip t io n:
<slaves> - Number of slaves to find. Not m andatory
<profile> - Configuration profile name. Not mandatory
<mode>- Use word keep to keep existing slaves and clean to
remove all slaves before searching for new.
Page | 16 Support: +46 300 434300 ? support@elvaco.com
Exam pl es:
Install and search for 2 meters and use profile myprofile:
install 2 myprofile
Install and search for 2 meters:
install 2
Clean all existing meters and install and search for 2 meters:
install 2 clean
Keep all existing meters and install and search for 2 n ew meters:
install 2 keep
Install and search for unknown number of m eters:
install
The CMe2100 product is now configured and will by default send E-Mail
value reports of connected slaves every day at 00:00.
CMe2100 Quick Manual English v4.0 Page | 17
5 Co n f igure f o r FTP rep o rt s
This section describes how to enable the CMe2100 product to send FTP
reports of connected slaves to an FTP server. The CMe2100 product will
store hourly values of connected slaves, send value reports every day at
00:00 and send an E-Mail installation report on completion (if E-Mail is
configured, see page 14).
5.1 Set FTP server
SMS to CMe2100 product: qset ftp <server> <port> <user>
<password> <remotedir>
Example: qset ftp ftp.domain.com 21 user pass datafolder
The CMe2100 product will acknowledge with an SMS receipt.
Page | 18 Support: +46 300 434300 ? support@elvaco.com
5.2 Sear ch and i nst all M -Bus sl aves
First perform steps as described on page 15.
FTP reports must be manually activated.
Exam pl es:
Activate to send FTP reports every day using report template 2104:
sch report2 1day 2104
Activate to send FTP reports every hour using report template 2104:
sch report2 1hour 2104
Activate to send FTP reports every month using report template 2105:
sch report2 1month 2105
CMe2100 Quick Manual English v4.0 Page | 19
6 Co n f igure f o r HTTP rep o rt s
This section describes how to enable the CMe2100 product to send
HTTP POST reports of connected slaves to a web server. The CMe2100
product will store hourly values of connected slaves, send value reports
every day at 00:00 and send an E-Mail installation report on completion
(if E-Mail is configured, see page 14).
6.1 Set HTTP server
SMS to CMe2100 product: qset http <url> <user> <password>
<authentication mode>
Example: qset http http://www.domain.com user pass basic
The CMe2100 product will acknowledge with an SMS receipt.
Page | 20 Support: +46 300 434300 ? support@elvaco.com
6.2 Sear ch and i nst all M -Bus sl aves
First perform steps as described on page 15.
HTTP reports must be manually activated.
Exam pl es:
Activate to send HTTP reports every day using report template 3104:
sch report3 1day 3104
Activate to send HTTP reports every hour using report template 3104:
sch report3 1hour 3104
Activate to send HTTP reports every month using report template 3105:
sch report3 1month 3105
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Elvaco CMe2100 Quick Manual

Type
Quick Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI