Appalachian Stove & Fabricators UV-EF-MIL 24-P is an unvented gas-fired heater that uses air (oxygen) from the room in which it is installed. It has been design certified for installations in a solid fuel burning masonry or UL 127 factory built fireplace or in a listed ventless firebox enclosure. This unit is tested to the Unvented Room Heater Standard ANS Z21.11.2a-2008 and operates as an unvented domestic room heater when fitted to a masonry or factory built fireplace with the flue damper closed or as a decorative appliance when the flue damper is fully open.

Appalachian Stove & Fabricators UV-EF-MIL 24-P is an unvented gas-fired heater that uses air (oxygen) from the room in which it is installed. It has been design certified for installations in a solid fuel burning masonry or UL 127 factory built fireplace or in a listed ventless firebox enclosure. This unit is tested to the Unvented Room Heater Standard ANS Z21.11.2a-2008 and operates as an unvented domestic room heater when fitted to a masonry or factory built fireplace with the flue damper closed or as a decorative appliance when the flue damper is fully open.

InstallationandOperatingInstructionsforUnventedZeroClearanceFireplaceHeaters
UV36RFP &UV-42RFP
INSTALLER:Leavethismanualwiththeappliance.
CONSUMER:Retainthismanualforfuturereference.
InstallationandOperatingInstructionsforGasLogHeaters
ModelsUV-EF-MIL (24/30)-N ANDUV-EF-MIL (24/30)-P
MODEL UV-EF-MIL 24P
UV-EF-MIL 30P
ForusewithPropane/LP gas
WARNING:Iftheinformationinthismanualis
notfollowedexactly,afireorexplosionmay
resultcausingpropertydamage,personalinjury,
orlossoflife.
WHATTODOIF YOUSMELL GAS
*Donottryandlightanyappliance.
*Donottouchanyelectricalswitch.
*Donotuseanyphoneinyourbuilding.
*Immediatelycallyourgassupplierfroma
neighborsphone.Followyourgassuppliers
instructions.
*Ifyoucannotreachyourgassupplier,callthe
firedepartment.
*Installationandservicemustbeperformedbya
qualifiedinstaller,serviceagency,orthegas
supplier.
Donotstoreorusegasolineorotherflammable
vaporsandliquidsinthevicinityofthisoranyother
appliance.
Thisisanunventedgas-firedheater.It
usesair(oxygen)fromtheroomin
whichitisinstalled.Provisionsfor
adequatecombustionandventilation
airmustbeprovided.(Seepage3for
additionalinformation).
The AppalachianStoveandFabricators
329EmmaRd.
Asheville,NC28806
Phone:(828)-253-0164
158-L-09-5Fax:(828)-254-7803
The AppalachianStove
MODEL UV-EF-MIL 24N/
UV-EF-MIL 30N
ForusewithNaturalGas
UNVENTEDGAS APPLIANCE
WARNING: Thisapplianceisfor
installationonlyinasolidfuel
burningmasonryorUL 127
factorybuiltfireplaceorina
listedventlessfireboxenclosure.
Ithasbeendesigncertifiedfor
theseinstallations.Exception:
DONOT installthisappliancein
afactorybuiltfireplacethat
includesinstructionsstatingit
hasnotbeentestedorshould
notbeusedwithunventedgas
logs.
Stateorlocalcodesmayonly
allowoperationofthisappliance
inaventedconfiguration.Check
yourstateorlocalcodes.
THIS APPLIANCEMAY BE
INSTALLEDIN AN
AFTERMARKET,
PERMANENTLY LOCATED,
MANUFACTURED(MOBILE)
HOME,WHERENOT
PROHIBITEDBY LOCAL
CODES.
THIS APPLIANCEISONLY FOR
USEWITHTHETYPEOFGAS
INDICATEDONTHERATING
PLATE.THIS APPLIANCEIS
NOTCONVERTIBLEFORUSE
WITHOTHERGASES.
USPatent#5,397,233,#5,591,024and
otherPatentsPending
ThisunittestedtotheUnventedRoomHeater
Standard ANSZ21.11.2a-2008
Thisapplianceoperatesasanunventeddomesticroom
heaterwhenfittedtoamasonryorfactorybuiltfireplacewith
thefluedamperclosedorasadecorativeappliancewhenthe
fluedamperisfullyopen.Itmustnotbeusedforanyother
purposeandmustbefittedinamasonryorfactorybuilt
fireplace.Ifcertainrequirementsaremet,thenthisproduct
alsoqualifiesunder ANSZ21.60b-2004 CGA2.26b-2004
DecorativeapplianceforinstallationinSolid-FuelBurning
Fireplaces.
Contents
ImportantInformation.......................................................Page3
Installation.........................................................................Page4
Unpacking........................................................................Page5
FireplacePreparation.......................................................Page5
LogPositioning.................................................................Page5
GasConnection................................................................Page4
GasPressureCheck.........................................................Page4
InstallationandClearances...............................................Page4-5
InstructionsforVented Applications..................................Page8
LightingInstructions..........................................................Page6
To TurnOffGas Appliance................................................Page6
............................................................................Page7
ExplodedView...................................................................Page7
ImportantSafeguards.......................................................Page10
Cleaning............................................................................Page10
Servicing...........................................................................Page10
RepairParts......................................................................Page10
LimitedWarrantyPolicy....................................................Page11
FlameCheck.....................................................................Page7
PartsList
3
Important Information
WARNING: ANY CHANGE TO THIS HEATER OR ITS
CONTROLS CAN BE DANGEROUS.
IMPORTANT: READ THESE INSTRUCTIONS CAREFULLY
BEFORE INSTALLING.
WARNING:
Due to high temperatures, the appliance should be located
out of traffic and away from furniture and draperies.
Young children should be carefully supervised when they
are in the same room as the appliance. Children and adults
should be alerted to the hazard of high surface temperatures,
and should stay away to avoid burns or clothing ignition.
The appliance should be inspected before use and at least
annually by a professional service person. More frequent
cleaning may be required due to excessive lint from
carpeting, bedding material, et cetera. It is imperative that
control compartment, burners, and circulating air
passageways of the appliance should be kept clear. See
cleaning instructions.
DO NOT place clothing or other flammable materials on or
near the appliance.
Installation and repair should be done by a qualified
service person.
Any safety screen or guard removed for servicing an
appliance must be replaced prior to operating the heater.
This appliance is intended for supplemental heating”
This appliance must be installed only in a solid fuel
burning fireplace with a working flue and constructed of non-
combustible materials, or UL 127 factory built fireplace or in a
listed ventless firebox enclosure. Exception: DO NOT install this
appliance in a factory built fireplace that includes instructions
stating it has not been tested or should not be used with unvented
gas logs.
The appliance area must be kept free and clear of combustible
materials, gasoline, and other flammable vapors and liquids. Solid
fuels shall not be burned in a masonry or UL 127 Factory-Built
Fireplace in which an unvented room heater is installed.
This appliance must only be used with pressures at the inlet
shown in Table 1.
The installation must conform with local codes, or in the
absence of local codes, with the NATIONAL FUEL GAS CODE
ANSIZ23.1/NFPA 54.
The appliance and its appliance main gas valve must be
disconnected from the gas supply piping system during any
pressure of that system at test pressures in excess of 1/2PSIG
(3.5 kPa).
The appliance must be isolated from the gas supply piping
system by closing its equipment shut off valve during any testing
of the gas supply piping system at test pressures equal to or less
than 1/2PSIG (3.5 kPa).
DO NOT use this heater in a bedroom, bathroom, or in a
recreation vehicle.
An unvented room heater having input rating of more than
10,000 Btu per hour shall not be installed in a bedroom or
bathroom.
DO NOT use this heater if any part has been under water.
Immediately call a qualified technician to inspect the appliance
and replace any part of the control system and any gas control
that has been under water.
ALWAYS OPERATE THE APPLIANCE AT THE MARKED
POSITIONS. NEVER OPERATE THE HEATER AT A SETTING
BETWEEN THESE POSITIONS, AS THIS COULD RESULT IN
IMPROPER COMBUSTION AND EXCESSIVE CARBON
MONOXIDE EMISSIONS.
WARNING: Glass doors must be in a fully open position when the
appliance is in operation.
Keep burner and control compartment clean. See installation and
operation instructions elsewhere in this manual.
WARNING: During manufacturing, fabricating, and shipping,
various components of this appliance are treated with certain oils,
films, or bonding agents. These chemicals are not harmful, but may
produce annoying smoke and smells as they are burned off during the
initial operation of this appliance, possibly causing headaches or eye
and lung irritation. This is a normal and temporary occurrence. The
initial break -in operation should last 2-3 hours with the burner at its
highest setting. Provide maximum ventilation by opening windows,
doors, and the chimney flue to allow odors to dissipate. Any odors
remaining after this initial break-in will be slight and disappear with
initial use.
The installation of appliances designed for manufactured homes
(U.S. Only) or mobile home installation must conform with the
standard in Canada, or with the
in the United States, or when such a standard is not
applicable,
Provide a 1/8 NPT plugged tapping accessible for test gauge
connection, immediately upstream of the gas supply connection to the
appliance.
This appliance can not be converted for use with other types of
gasses.
When used as an unvented heater, always ensure that there is
adequate ventilation for the room where the appliance is
operating. “This heater shall not be installed in a room or space
unless the required volume of indoor combustion air is provided by
the method described in the
.” “The
defines a confined space as a space whose volume is less than
50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the
aggregate input rating of all appliances installed in that space.
Rooms communicating directly with the space in which the
appliances are installed through openings not furnished by doors
are considered part of the unconfined space.
WARNING: If the area in which the heater may be operated does
not meet the required volume for indoor combustion air, combustion
and ventilation air shall be provided by one of the methods described
in the
or applicable local codes.
Unusually tight construction is defined as construction where:
(A) Walls and ceilings exposed to the outside atmosphere have a
continuous water vapor retarder with a rating of 1 perm (6x10-11 kg
per pa-sec-m 2) or less with openings gasketed sealed.
(B) Weather stripping has been added on openable windows and
doors.
(C) Caulking or other sealants are applied to areas such as joints
around windows and door frames, between sole plates and doors,
between wall and ceiling joints, between wall panels, at penetrations
for plumbing, electrical and gas lines and at other openings.
Example of room dimension limitations: If this appliance is listed at
40,000 Btu’s, then the room cannot be less than 50 cubic feet for each
1,000 Btu’s or 2000 Cubic Feet. As an example, if the room is 11 ft. Tall,
12 ft. Wide, and 14 ft. Deep (11x12x14 = 1848), then it must be
provided with adequate combustion and ventilation air.
This appliance is equipped with an ODS (oxygen depletion
sensor) pilot light safety system designed to shut itself off if not enough
fresh air is available. Additional ventilation may be obtained by
opening a door to another room or opening a ventilating window.
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International Fuel Gas Code, or applicable
local codes National Fuel Gas Code, ANSI Z223.1/NFPA
54
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the
International Fuel Gas Code,
CAN/CSA Z240 MH, Mobile Housing,
Manufactured Home Construction and Safety Standard, Title 24 CFR,
Part 3820,
ANSI/ NCBS A225.1/ NFPA 501A, Manufactured Home
Installations Standard.
GASCONNECTION
GASPRESSURECHECK
CHECKGAS TYPE.Useonlythegastype
indicatedontheheater’sratingplate.Ifthe
gaslistedontheplateisnotthetypeofgas
supplyDONOT INSTALL.Contactyourdealer
forpropermodel.
AlwaysuseanexternalregulatorforallLP
appliancestoreducethesupplytankpressure
toamaximum13”WC. Thisisinadditionto
theregulatorfittedtotheheater.
WARNING:Connectiondirectlytoan
unregulatedLP tankcancauseanexplosion.
Thenormalgasconnectionis3/8”madeat
theleftsidefacingtheunit.Ifarightside
connectionisrequired,theconnectingpipe
maybeleadbehindtherearoftheappliance
toterminateattherighthandsidefor
connectiontotheinletoftheappliance.
Testforleaksusingasoapandwater
solutionaftercompletion.DONOT USE
OPENFLAME.
Checktheinletpressuretotheappliance
toensurethatitisasshowninthetable
below. Theminimuminputcanbeobtainedby
turningtheadjustablecontrolknobtoits
lowestsetting.
TABLE1
Thepressureiscontrolledbytheregulator
andshouldbecheckedatthepressuretest
pointlocatedinthecontrolvalvebody. Access
tothepressuretestpointisobtainedby
removingalllogs.
Thepressureshouldbecheckedwiththe
applianceburningandthecontrolsetonhigh.
Thepressureregulatorispresetand
lockedtoavoidtampering.Ifthepressureis
notspecified,replacethewhitereplacement
partUV-001BfornaturalgasandUV-026Bfor
propaneonly.
Aftermeasuringthepressure,replacethe
testpointplug,ensuringnoleaks,replacing
theheatshieldwhereappropriate,andthe
logsintheirspecifiedpositions.
MODEL UVEF-MIL24,30NUVEF-MIL 24,30P
GASNATURAL (N)PROPANE(LP)
Max.HeatInput39,000BTUH35,000BTUH
Min.HeatInput23,000BTUH23,000BTUH
GasInletPressure
Max.10.5ins.WC13.0ins.WC
Ideal7.0ins.WC11.0ins.WC
Min.4.5insWC10.0ins.WC
(Minimumforpurposeofinputadjustmentonly)
RegulatorPressure3.5insWC10ins.WC
INSTALLATION ANDCLEARANCES
WARNING:Beforeinstallinginasolidfuelburningfireplace,
thechimneyfluemustbecleanedofsoot,creosote,ashes,and
loosepaintbyaqualifiedchimneycleaner.
WARNING:Donotallowfanstoblowdirectlyintothe
fireplace. Avoidanydraftsthatalterburnerflamepatterns.
WARNING:Thisapplianceisforinstallationinasolidfuel
burningfireplaceonly.
WARNING:Failuretokeeptheprimaryairopening(s)ofthe
burner(s)cleanmayresultinsootingandpropertydamage.
Toensuresafeinstallationintoamasonryorfactorybuilt
fireplace,thefollowinginstructionsmustbecarefullyobserved.
1.SidewallClearances: Theclearancefromthesidepfthis
appliancetoanycombustiblewallshouldnotbelessthan15”.
2.CeilingClearances: Theceilingheightshouldnotbelessthan
42”fromthetopofthefireplaceopening.
3.MantelClearances:Inordertoreduceclearances,acanopy
(model#1510-0140)maybeused.Refertofigure4B&4Conpage5
foracleardefinitionofclearances.
Important: Airopeningsshallnotbeobstructedinanywaywhen
installingthisgasappliance.
Thefireplacescreenmustbeinplacewhentheapplianceis
operating,andunlessotherprovisionsaremadeforcombustionair,
thescreenshallhaveanopeningfortheintroductionofcombustion
air.
Theleftandrightsidesaredeterminedwhenfacingthefrontof
theappliance.
Withnocanopyused(Figure4B)theclearancefromthetop
edgeofthefireplaceopeningtoa2½”mantelis28,”6”mantelis
38,”anda10”mantelis44.”
Withoutlouversandthecanopyinposition(Figure4C)the
clearancefromthetopedgeofthefireplaceopeningtoa2½”mantel
is16,”6”mantelis20,”anda10”mantelis26.”
Withlouversandcanopyinposition(Figure4D)theclearance
fromthetopedgeofthefireplaceopeningtoa2½”mantelis18,”6”
mantelis24,”anda10”mantelis30.”
Themantelpieceprofilemustfallwithinthecrosssectionas
showninthefiguresonthenextpage.
(Sectioncontinuedonfollowingpage)
4
Pressure TestPoint
Left Right
FRONT OFBURNER
(Continuedfrompreviouspage)
Thecanopymustbeinstalledinaccordancewiththeinstructions
providedwithit.
Noncombustiblematerialsusedinthisinstallationsuchasslate,
marble,tile,etcetera,mustbeatleast½”thick. Thereshouldbeno
combustiblematerialinstalledbehindsheetmetal.
Failuretoinstallnoncombustiblematerialabovetheopeningas
specifiedwiththeseinstructionsmaycausedamagetothematerialsused
orcauseafirehazard.
Installation
WARNING:Before
installinginasolidfuel
burningfirebox,the
chimneyflueandfirebox
mustbecleanedofsoot,
creosote,ashesandloose
paintbyaqualified
chimneycleaner.
WARNING:Outsideair
ducts,and/orashdumps
inthefireplacemustbe
permanentlyclosedatthe
timeofappliance
installation.
WARNING:Donot
allowfanstoblowdirectly
intothefireplace. Avoid
anydraftsthatalterburner
flamepatterns.
WARNING:Donotuse
ablowerinsert,heat
exchangerinsert,orother
accessorynotapproved
withthisheater.
PositioningLogs
Unpacking
FireplacePreparation
Opencartonandremove
chassisfromitslocation.
Removeeachofthelogsby
grippingateitherendofthe
logwhileavoidingany
unduepressure.
Thefirstcartoncontains
thefollowingitem:
Burner
Thesecondcarton
containsthefollowingitems:
1.Rearlog
2.CenterRightLog
3.Frontleftlog
4. Topleftlog
5. Topcenterlog
6. Toprightlog
Beforeinstallation,the
dampermustbesecured
opentothepropersize.
Refertothechartonpage5
foradditionalinformation.
Thefireplacemustbe
preparedbeforeinstallation:
A. Turnoffthegassupply
tothefireplace.
B.Cleanthefireplace
floorandchimney(ifused)
ofanyashes,soot,
creosote,orobstruction.
Thiswillminimizeanysmell
fromthefireplace.We
recommendcleaningbya
chimneysweep.
Carefullypositionlogsas
shown:PositionLog#2
betweenfrontgrateand
mainburners. Thenposition
Log#1onrearsupporters,
pushingbackasfaras
possibleandintonotches.
ThenplaceLog#3around
theleftgratebar.PlaceLog
#4onLog#2andframeas
shown. ThenplaceLogs#5
and#6ontothepinsofLogs
#1and#2,settingtheminto
theirnotches.Makesure
thatnologcanbemoved
easilyfromsidetoside.
ENSURE THAT ALL LOGS
ARECENTRAL AND
VERTICAL ASSEENFROM
THESIDE. THERE
SHOULDBESOME
IMPINGEMENT OF
FLAMESFROM THE
BURNER.IF THELOGS
BECOMEBLACKENED
DURINGUSE, TURNUNIT
OFF ANDCLEANWITH A
DAMP CLOTHOR A SOFT
BRUSH.RECHECKFOR
POSITIONING.FOLLOW
CLEANING
INSTRUCTIONSBEFORE
RELIGHTING.
Figure1
5
DecorativeGlowingEmberPlacement
TheGlowEmberPadispre-assembledandneedsnoadjustingor
addedmaterialstoglow.Padshouldbesecureandinplacebefore
operating.
Warning:Thisapplianceisequippedfor
(naturalorpropane)gas.Fieldconversionis
notpermitted.
FOR YOURSAFETY READBEFORELIGHTING
6
A. Thisappliancehasapilotwhichmustbe
lightedbyhand. Whenlightingthepilot,followthese
instructionsexactly.
B.BEFORELIGHTINGsmellallaroundthe
applianceareaforgas.Besuretosmellnexttothe
floorbecausesomegasisheavierthanairandwill
settleonthefloor.
WHAT TODOIF YOUSMELL GAS:
DONOT TRY TOLIGHT ANY APPLIANCE.
DONOT TOUCH ANY ELECTRICAL
SWITCH;DONOT USE ANY PHONEIN YOUR
BUILDING.
IMMEDIATELY CALL YOURGASSUPPLIER
WARNING:Ifyoudonotfollowtheseinstructionsexactly,afireor explosionmay
Resultcausingpropertydamage,personalinjuryor lossoflife.
LIGHTING INSTRUCTIONS
FROM A NEIGHBOR’SPHONE.FOLLOW
YOURGASSUPPLIER’SINSTRUCTIONS.
IF YOUCANNOT REACH YOURGAS
SUPPLIER,CALL THEFIREDEPARTMENT.
C.Useonlyyourhandtopushinorturnthegas
controlknob.Neverusetools.Iftheknobwillnotpush
inorturnbyhand,don’ttrytorepairit,callaqualified
servicetechnician.Forceorattemptedrepairmay
resultinafireorexplosion.
D.Donotusethisapplianceifanyparthas
beenunderwater.Immediatelycallaqualifiedservice
techniciantoinspecttheapplianceandtoreplaceany
partofthecontrolsystemandanygascontrolwhich
hasbeenunderwater.
1.STOP!Readthesafetyinformationabove.
2.Pushingascontrolknobslightlyandturnclockwiseto
“OFF.”NOTE:Knobcannotbeturnedfrom“PILOT”to
“OFF”unlesstheknobispushedinslightly.Donotforce.
3. Waitfive(5)minutestoclearoutanygas.Ifyousmellgas,
STOP!Follow“B”inthesafetyinformationabove.Ifyoudon’t
smellgas,gotothenextstep.
4.Findpilotlocatedbetweenthefrontlogandthesecondlog.
5. Turnthecontrolknobcounterclockwisetopilot.
6.Pushthecontrolknoballthewayinandholdin. Whilestill
holdingthecontrolknobin,pushthePiezoIgnitorbutton
severaltimes. Thiswillcauseasparkatthepilotwhichshould
ignitethepilotgas.Continuetoholdthecontrolknobinfor
severalsecondstopreventflamefailure.
7.Releasethecontrolknob.
*Ifthecontrolknobdoesnotpopbackupwhen
released,stopandimmediatelycallyourservice
technicianorgassupplier.
*Ifthepilotdoesnotstaylitafterseveraltries,turnthe
gascontroltoOFFandcallyourservicetechnicianor
gassupplier.
8.Oncethepilotremainslit,depressthegascontrolknobslightly
andturnthegascontrolknobcounterclockwiseto“ON.”
NOTE: The“ON/OFF”SWITCHisusedtoturntheflameonor
offwhenthecontrolvalveisinthe“ON”position.
Thisapplianceisfittedwithatransientpilotburnerforthesole
purposeofsafe,momentaryignitionofthemainburnerin
conjunctionwiththepiezoignitor. Wheninoperationwiththe
mainburner,itcontributestothebaseheatreleaseandisturned
offbyturningthecontrolknobtotheoffposition.
9.Periodicallycheckthepilotflameforproperflamepattern.
Ifthepilotcannotbeignitedwiththepiezo,itcanbemanuallylit
withtheuseofapapermatchandalighterrod.Placethematch
intheholderandlight. Withtherighthand,depressandturnthe
controlknobcounterclockwisetothepilotpositionandhold
in.
Taketherodandlitmatchandlightthepilot. Thepilotislocated
behindthefrontandthesecondlog.
Continuetoholdthecontrolknobforanadditional10secondsto
ensurethatthepilotismaintained.
IMPORTANT:DONOT OPERATEBETWEENSETTINGS
MATCHLIGHTING
Toturnoffthegasappliance
1.Fromthe“ON”position,turnthecontrolknobclockwisetothe“PILOT”position. Thelogsetwillextinguish,andthe
pilotwillremainlit.
2.Ifcompleteshutdownisdesiredfromthe“PILOT”position,pushinthecontrolknobslightlyandturnclockwisetothe
“off”position.Donotforcetheknob.
TO TURNOFF GAS TO APPLIANCE
Piezo
PiezoIgnitor
HI/LOKNOB
OFF
ON
PILOT
OFF
ControlKnob
FlameCheck
A periodicvisualcheckoftheflamesshouldbemade. Thepilot
flameshouldalwaysbepresentwhentheapplianceisinoperation.
SeefiguresDandE.
Innormaloperation(atafullrateforapproximately15minutes),
thefollowingflameappearancesshouldbeobserved:
Rearflames: Theflamesattherearorateithersideofthetoplog
shouldbeverysimilar,yellowincolor,andshouldextendaboutthree
tofourinchesabovethelargecenterlogfornaturalgas,twotothree
inchesforPropane.
IMPORTANT:IF THESEFLAMESBECOMELARGERSEE
“CLEANINGINSTRUCTIONS”
MainBurner: Theflamesattheburnerfrontfacewillbeblue
becomingyellowishastheyhitthebottomofthefrontlogs. Typical
mainburnerflameshapesaregiveninFigureE.
NOTE:Foryoursafety,theapplianceisequippedwithanoxygen
depletionsystem. Thesystemsensedtheamountofoxygeninthe
atmosphereandswitchesoffthegassupplyincasethelevelof
oxygenfallsbelowasafelevel.
WHENUSED AS A HEATING APPLIANCE/HEAT OUTPUT
Theheatoutputiscontrolledbythespanknob,oroptional
thermostat,notbythemaincontrolknob. Thespanknobwilladjust
flameintensity.
Thisappliancemaybeusedasaheatingapplianceonlyif
unventedheatingappliancesarepermittedbylocalstateandcity
codes.
7
FigureE
WARNING:Failuretokeeptheprimaryair
opening(s)oftheburner(s)cleanmay
resultinsootingandpropertydamage.
PART NAMEPART ##REQ
1.RearLog24EF-0211
2.FrontRightLog24EF-0221
3.FrontLeftLog24EF-0231
4. TopLeftLog24EF-0241
5. TopMidLog24EF-0251
6. TopRightLog24EF-0261
7.EmberflameGloPad24EF-027
8.ControlValve(N)
(RobertShaw)24UV1201
(Genesis)24UV120E1
(S.I.T.)24UV1401
ControlValve(LP)
(RobertShaw)24UV1211
(Genesis)24UV121E1
(S.I.T.)24UV1411
PART NAMEPART ##REQ
9.PiezoUV0871
10.Pilot Assembly(N)UV070N1
Pilot Assembly(P)UV071P 1
11.RearBurnerOrifice24UV010C(N)1
12.MainBurnerOrifice24UV052(N)1
13.MainBurner(N)24UV4518-0241
MainBurner(LP)24UV4518-1681
14.MainBurner Tube13971-0161
15.LavaRock Tray13971-0031
SourceonPage10
InstructionsforVented Applications
Thisunitmaybeinstalledinareaswherebuildingcodesrequireallgasappliancestobevented,if
andonlyifthefollowingguidelinesaremet. ThoseguidelinesfallintotheNationalFuelGasCode
ANSIZ223.1standard.
Thisappliancemustbeinstalledinasolidfuelburningfireplacewithaworkingflueand
constructedwithnoncombustiblematerial.
Theminimumpermanentfreeopeningthatmustbeprovidedbyeitherthefireplacechimneyor
chimneydampertoventthefluegasmustbeinaccordancewiththetableinFigure10.
Solidfuelsshallnotbeburnedinafireplacewhereadecorativefireplaceisinstalled. The
installationandprovisionsforcombustionandventilationairmustconformwiththe
Ensureperiodicexaminationandcleaningoftheventingsystemofthesolidfuelburningfireplace
atleastonceayearbyaqualifiedagency.
Decorativeappliancesforinstallationinsolidfuelburningfireplacesshallnotbethermostatically
controlled. Additionssuchasthermostatsorotherautomaticallycyclingdevicesarenotpermitted.
Additionssuchasthermostatsorotherautomaticallycyclingdevicesarenotpermitted.
PermanentFreeOpening
SecureChimneyDamper
Thechimneydampermustbefixedinamannerwhichwillmaintaintheminimumpermanentvent
openingatalltimes(Byscrew,boltatdamper’sedgetopreventitsclosing,orbyaholeorholesinthe
damper).
NationalFuelGas
Code, ANSIZ223.1/NFPA54.
MINFLUEDIAMETER:7”
OtherImportantItems:
1.Operatorshouldnotadjusttheflamebythecontrolknob.(SeeImportantInformationandLightingInstructions.)
2.Extendedusemaycauseairholeonleftrearburnertubetoclogup. Thiswillmaketheflamesappeartallerwhich
couldcauseacarbonorsootingproblem.
3.Logsnotplacedcorrectlywillcausesooting.
Ifsootingoccurs,thisunitshouldnotbeoperateduntiltheproblemisdiagnosed!
Othernotsocommonproblemsmaycausesooting.
1.Incorrectlinetounit.Checkwithlocalbuildingcodesforproperlinesizes,andnokinksinanylineareacceptable.
2.Lowfuelpressureintank.
3.Draftfromfanssuchasceilingfansorproximitytodoorwaythatcausesflamestodanceerratically.
4. Anythingsittingtooclose,orinfrontoftheunit,maycauseanobstructionofairflowtothegaslogs.
8
ChimneyHeightEF-N,39,000Btu’s
(Min.PermanentEF-P,35,000Btu’s
freeopening)
6ft.34squareinches
8ft.32squareinches
10ft.29squareinches
15ft.27squareinches
20ft.24squareinches
25ft.23squareinches
30ft.22squareinches
Diameterof Area
Std.RoundFlue
5in20sq.in.
6in.29sq.in.
7in39sq.in.
8in51sq.in.
Figure10
IMPORTANT:Ensurethatthechimneydraftisadequatebyholdingalitmatchorcandleatthetop
edgeofthefireplaceopening. Thiswillindicateifairmovementistowardthefireplace.Ifdraftis
inadequate,donotoperatelogsuntildraftisadequate.Ifthedraftisinsufficient,haveitinspectedbya
qualifiedchimneysweep.
(Minimumpermanentfreeopeninginsquareinchesbasedon6’ height)
9
ImportantSafeguards
Althoughyourgaslogsareveryrealisticinappearance,itisnotarealwoodburningfireplaceandmustnotbeusedfor
burningrejectedmaterial.
Toavoidirreparabledamagetotheapplianceorpersonalinjury,matches,paper,garbage,oranyothersolidfuelsmust
notbeplacedorthrownontopofthelogsorintotheflames.
Toavoidpersonalinjury,donottouchanyhotsurfaceoftheappliancewhenitisinoperation.
Touchonlythecontrolknob. Avoidcontactwiththegratefeetorprongsoranyotherpartwhichmaybeveryhot.
Alwaysensurethatthefireplacescreenisclosedwhentheapplianceisoperatingandprovisionsaremadefor
combustionair. Thisapplianceisnotcertifiedforusewithglassdoorsinaclosedposition.
Closesupervisionisnecessarywhentheapplianceisoperatednearchildren.
Cleaning
CAUTION:Beforecleaningormovinglogsorotherpartsoftheunit,besuretoreadtheabovesectionsonimportant
safeguards.
Allcleaningshouldbedonewhentheapplianceiscold.
Onlylimitedcleaningwillberequiredundernormaluse.Dustingthefrontgrate,thetopofthecover,orthecontrolknob
panelmayberequiredoccasionally.Donotuseanycleaningfluidtocleanthelogsoranyotherpartoftheappliance.
Iftheflamesshowanyunusualshapesorbehavior,oriftheburnersfailtoigniteproperly,thentheburnerholesmay
requirecleaning.Ifthisoccurs,donotoperatetheappliance.
Contactyournearestdealertogetyourapplianceserviced. Theairholesontheleftbottomrearburnertubemay
causetheflamestobecome4½”ortallerwhenclogged,requiringthetubetobecleanedwithawireorpipecleaner.
Alternatively,theappliancecanbecleanedbyremovingthetop,front,andrearlogs.Handlethelogsgentlyastonot
damagethefiberpieces. Alwayslifteachlogbyholdingitcarefullyatbothends.
Carefullyuseavacuumcleanertoremovedustandlooseparticlesfromthebase,logs,andfromaroundtheburners.
Glovesarerecommendedtopreventthefibersfrombreakingyourskin.Iftheskinisbroken,washgentlywithsoapand
water.
Servicing
Repairandreplacementworkshouldonlybedonebyaqualifiedserviceperson. Theapplianceshouldbeinspected
beforeuseandatleastannuallybyaprofessionalserviceperson.Morefrequentcleaningmayberequireddueto
excessivelintfromcarpeting,beddingmaterials,etc.
Itisimperativethatthecontrolcompartmentismaintainedcleanandfreeofobstructions.
Alwaysshutoffthegassupplyandmakesuretheapplianceiscoolbeforebeginninganyserviceoperation.
Anysafetyscreenorguardremovedforservicingagasappliancemustbereplacedbeforeoperatingtheheater.
Alwayscheckforgasleaksafterservicing.
RepairParts
A partslistwithexplodedviewsisonpage7. Alwaysincludecorrectname,partnumber,andmodelnumberofthe
appliancewhenorderingserviceparts.
Ifyoudesiretocommunicatewiththefactory,writeto:
AppalachianStove
&Fabricators
329EmmaRoad
Asheville,NC28801
Phone:(828)235-0154
Fax:(828)254-7803
10
Location
Fireplacescreen
Centrallylocatetheunitinthefireplaceanddeepenoughintothefirepittoaccomplishadequatedraft.
Ensurethatthegratefrontfeetsitinsidethefrontedgeofthefireplace.
Thefireplacescreenmustbeinplacewhentheapplianceisoperating,andunlessotherprovisions
forcombustionairaremade,thescreenmusthaveanopening(s)fortheintroductionofcombustion
air.
Thiswarrantyislimitedtofireplacesmanufacturedandassembledby AppalachianStoveand
Fabricators,henceforth“Appalachian.”
Ifanycomponentofafireplacecoveredunderthiswarrantyisreturnedto Appalachianand
foundtobedefectivewithintwoyearsfromthedateofpurchase, Appalachianwill,atitsoption,
repairorreplacethedefectivecomponentatnocharge.Valves,ODS’s,regulators,andmotors
carrya1yearwarranty.Dateofpurchaseandpurchasepricemustbeverifiedbyan
acceptableproofofpurchase.
Thiswarrantycoversonlypartsasprovidedabove.Innocaseshall Appalachianbe
responsibleformaterials,components,orconstructionwhicharenotmanufacturedorsupplied
by Appalachian,orthelabornecessarytoinstall,repair,orremovesuchmaterials,components,
orconstruction.
Thefireplacemustbeinstalledinaccordancewith Appalachianinstallationinstructions
andlocalcodes.
Thefireplacemustbeinstalledbyaqualifiedinstallerandmustbeoperatedaccordingtothe
operationinstructionsfurnished.
Thislimitedwarrantyappliesonlytotheoriginalownerofthegaslogsortheoriginalowner
ofthedwellinginwhichthegaslogsareinstalled.
Appalachianisnotresponsibleforanyincidentalorconsequentialdamagecausedby
possibledefectsinthisproduct.
Thedurationofanyimpliedwarrantywithrespecttothefireplaceislimitedtotheduration
oftheforegoingwarranty.
Somestatesdonotallowtheexclusionofincidentalorconsequentialdamagesorlimitsonthe
durationofimpliedwarranties,sotheselimitationsmaynotapplytoyou.
Appalachianreservestherighttoinvestigateanyandallclaimsagainstthiswarrantyandto
decideonthemethodofsettlement.
Appalachianisnotresponsibleforwarrantyworkcompletedwithoutobtaining Appalachian’s
consent. Appalachianemployeesanddealershavenorighttoalterthiswrittenwarranty.
Thislimitedwarrantyisgiveninlieuofanyotherexpressedorimpliedwarranty.
The AppalachianStove
329EmmaRoad
AshevilleNC28806
Phone:(828)253-0164
Fax:(828)254-7803
WarrantyCoverage
Qualification
Limitations
WarrantyFulfillment
Two YearLimitedWarranty
11
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11

Appalachian Stove & Fabricators UV-EF-MIL 24-P Installation And Operating Instructions Manual

Category
Fireplaces
Type
Installation And Operating Instructions Manual
This manual is also suitable for

Appalachian Stove & Fabricators UV-EF-MIL 24-P is an unvented gas-fired heater that uses air (oxygen) from the room in which it is installed. It has been design certified for installations in a solid fuel burning masonry or UL 127 factory built fireplace or in a listed ventless firebox enclosure. This unit is tested to the Unvented Room Heater Standard ANS Z21.11.2a-2008 and operates as an unvented domestic room heater when fitted to a masonry or factory built fireplace with the flue damper closed or as a decorative appliance when the flue damper is fully open.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI