1. Introduction
The tM-P3R3 provides 3 channels for digital input and 3 channels for relay output, each
of which features photocouple isolation. All output channels are form A type relays,
while input is based on sink- or souce-type using a wire connecion. All input channels
can be used an 16-bit counters. There are options for configuring power-on and safe
digital output values. 4 kV ESD protection and 3750 VDC intra-module isolation are also
provided.
2. Terminal Assignment
tM-P3R3 3-channel DI and 3-channel Relay Output Module- QuickStart (Nov/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
2
3. Block/ Wiring Diagram
Use 26-12 AWG wire for signal
connections.
Strip the wire to a length of
7±0.5mm.
Use a crimp terminal for wiring.
Avoid high-voltage cables and
power equipment as much as
possible.
For RS-485 communication, use
insulated and twisted pair 24 AWG
wire, e.g. Belden 9841.
4. Default Settings
Default settings for the tM-P3R3 module are as follows:
Protocol: Modbus RTU
Module Address: 01
DIO Type: Type 40
Baud Rate: 9600 bps
tM-P3R3 3-channel DI and 3-channel Relay Output Module- QuickStart (Nov/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
3
5. Configuration
To install the module, follow the steps below:
1. Connect the thermistor analog input.
2. Connect the module to the RS-485 network using the DATA+ and DATA- terminals.
3. Connect the module to the power supply using the +Vs and GND terminals. Note that
the voltage supplied should be in the range of +10 to +30V DC.
tM-P3R3 3-channel DI and 3-channel Relay Output Module- QuickStart (Nov/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
4
4. Open DCON utility pro
click on COM port(first icon).
It can select multi-options such as Baud Rate, Protocol, Checksum, and Format to
search module. The default settings for the module can be found in Section 3. Click OK
after selecting the COM port setting.
tM-P3R3 3-channel DI and 3-channel Relay Output Module- QuickStart (Nov/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
5
5. DCON utility pro will search for the selected COM port according the setting
previously set. DCON Utility Pro supports DCON and Modbus protocol for all ICPDAS
and the others modules.
6. Configuration I/O module setting on PC
tM-P3R3 3-channel DI and 3-channel Relay Output Module- QuickStart (Nov/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
6
7. The Modbus RTU communication protocol is the default protocol of the tM series.
The communication Baud Rates for the Modbus RTU protocol can be in the range of
1200 bps to 115200 bps
8. If user doesn’t know command, user can select Address and ID, it will show some
refer commands as below. User can select necessary command to test or debug
modules.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6