ABB C1900 Series Installation guide

Type
Installation guide
ABB MEASUREMENT & ANALYTICS | OPERATING INSTRUCTIONS | IM/C1900-MOD REV. G
C1900
Circular chart recorder and recorder/controller
MODBUS (RTU)
communications option
Measurement made easy
For more information
Further publications are available for free download
from:
www.abb.com/recorders
or by scanning this code:
Search for or click on
Data Sheet
C1900
Circular chart recorder
DS/C1900R-EN
Data Sheet
C1900
Circular chart recorder/controller
DS/C1900RC-EN
Quick Reference Guide
C1900 recorders
IM/C1900-QR
Quick Reference Guide
C1900 recorder and recorder/controller
IM/C1900-QC
Search for or click on
Installation Guide
C1900
Circular chart recorder and recorder/
controller
IM/C1900-INS
Operating Guide
C1900
Circular chart recorder
IM/C1900-OGR
Operating Guide
C1900
Circular chart recorder/controller
IM/C1900-OGC
Programming Guide
C1900
Circular chart recorder
IM/C1900-PGR
Programming Guide
C1900
Circular chart recorder/controller
IM/C1900-PGC
C1900
circular chart recorder
and recorder/controller
Electrical safety
This equipment complies with the requirements of CEI/IEC
61010-1:2001-2 ‘Safety Requirements for Electrical Equipment
for Measurement, Control and Laboratory Use. If the
equipment is used in a manner NOT specified by the Company,
the protection provided by the equipment may be impaired.
Symbols
One or more of the following symbols may appear on the
equipment labelling:
Warning – refer to the manual for instructions
Caution – risk of electric shock
Protective earth (ground) terminal
Earth (ground) terminal
Direct current supply only
Alternating current supply only
Both direct and alternating current supply
The equipment is protected through double insulation
Information in this manual is intended only to assist our
customers in the efficient operation of our equipment. Use of
this manual for any other purpose is specifically prohibited and
its contents are not to be reproduced in full or part without
prior approval of the Technical Publications Department.
Health and safety
To ensure that our products are safe and without risk to health,
the following points must be noted:
The relevant sections of these instructions must be read
carefully before proceeding.
Warning labels on containers and packages must be
observed.
Installation, operation, maintenance and servicing must
only be carried out by suitably trained personnel and in
accordance with the information given.
Normal safety precautions must be taken to avoid the
possibility of an accident occurring when operating in
conditions of high pressure and/or temperature.
Chemicals must be stored away from heat, protected from
temperature extremes and powders kept dry. Normal safe
handling procedures must be used.
When disposing of chemicals ensure that no two chemicals
are mixed.
Safety advice concerning the use of the equipment described in
this manual or any relevant hazard data sheets (where
applicable) may be obtained from the Company address on the
back cover, together with servicing and spares information.
1
CONTENTS 1 INTRODUCTION
Information.
The COMMANDER 1900 Series is extended by the
addition of a serial data communication option
designed for use with SCADA systems.
RS422/485 Communication standard.
Modbus RTU protocol – for master (host computer)
to slave (COMMANDER 1900) system.
Isolated (500V) from rest of instrument.
3 and 5 Wire communication supported.
Baud rate – from 1200 to 9600.
Parity-checking – of message available.
Section Page
1 INTRODUCTION ......................................................... 1
2 ELECTRICAL INSTALLATION .................................. 2
2.1 Selection of Serial Communication
Adaptors for Personal Computers ................... 2
2.2 Recommended OPTO22 Boards ..................... 2
2.3 Pull-up and Pull-down Resistors ...................... 2
2.4 Termination Resistors....................................... 4
2.5 RS485/422 Standard ........................................ 4
2.6 Serial Connections ........................................... 5
3 ADVANCED CONFIGURATION LEVEL .................... 6
3.1 Serial Data Communication Page .................... 7
4 MODBUS PROTOCOL ............................................... 8
4.1 Introduction to Modbus Protocol ...................... 8
4.1.1 Non-volatile Memory
Limitations ........................................... 8
4.2 Modbus Function Codes .................................. 8
5 MODBUS FUNCTIONS ............................................... 9
5.1 Read Coil Status – Function Code 01 ............. 9
5.1.1 Read Coil Status Query ...................... 9
5.1.2 Read Coil Status Response ............... 9
5.2 Read Holding Register – Function Code 03 .... 9
5.2.1 Read Holding Register Query ............ 9
5.2.2 Read Holding Register Response .... 10
5.3 Force Single Coil – Function Code 05 ........... 10
5.3.1 Force Single Coil Query ................... 10
5.3.2 Force Single Coil Response ............. 10
5.4 Preset Single Register – Function Code 06 .. 11
5.4.1 Preset Single Register Query ........... 11
5.4.2 Preset Single Register Response .... 11
5.5 Loopback Test – Function Code 08 ............... 11
5.5.1 Loopback Test Query ........................ 11
5.5.2 Loopback Test Response ................. 11
5.6 Write Multiple Registers – Function Code 16 12
5.6.1 Write Multiple Registers Query......... 12
5.6.2 Write Multiple Registers Response .. 12
6 EXCEPTION RESPONSES ...................................... 13
6.1 Examples ....................................................... 13
7 MODBUS REGISTERS ............................................. 14
7.1 Coils .......................................................... 14
7.2 Holding Registers ........................................... 16
7.3 Controller Settings/Outputs ............................ 17
7.4 Set Points ....................................................... 18
7.5 Alarm Settings ................................................ 18
7.6 Chart Settings................................................. 19
7.7 Ramp/Soak Settings ...................................... 19
7.8 Totalizer Settings ............................................ 20
7.9 Holding Registers –
Pasteurizer Versions Only .............................. 21
2
2.1 Selection of Serial Communication Adaptors for Personal Computers
Information.
A RS422/485 communication board is required in the host PC.
Observe the limitations outlined in the Installation Guide – the maximum serial data transmission line length for both
RS422 and RS485 systems is 1200m.
An RS422/485 communications adaptor is required for serial links. It is strongly recommended that the card used has galvanic
isolation to protect the computer from lightning damage and increase immunity from noise pick-up.
2.2 Recommended OPTO22 Boards
The following OPTO22 boards are recommended for use with the COMMANDER 1900 Series of instruments:
Part No. Computer Type
AC24 AT AT Bus IBM PC compatible
AC34 Microchannel IBM PC
2.3 Pull-up and Pull-down Resistors – Figs. 2.1 and 2.2
To prevent false triggering of the slave (COMMANDER 1900) by the presence of noise when the master (host computer) is
inactive, 1.8K pull-up and pull-down resistors must be fitted to the RS422/485 adaptor card – see Figs. 2.1 and 2.2.
2 ELECTRICAL INSTALLATION
Fig. 2.1 Pull-up and Pull-down Resistors (3-wire Operation)
Tx+
Tx–
GND
+5V
0V
Computer Terminal or Host Computer
Rx–
Rx+
Tx–
Tx+
'A'
'B'
1
2
7
8
9
3
4
5
6
Serial Module
Terminal Board
COMMANDER 1900
Pull-up and Pull-down Resistors
+5V
1.8kΩ Pull-up Resistor
1.8kΩ Pull-down Resistor
'A'
'B'
58
6
7
310
4
9
Linked In
Linked Out
+5V
0V
1.8kΩ Pull-up
Resistor
1.8kΩ Pull-down
Resistor
'A'
'B'
'A'
'B'
Links on Serial Module
Tx+/Rx+
Tx–/Rx–
PL2
PL2
GND
Note. If an RS422/485 adaptor card without pull-up and pull-down
resistors is used, the COMMANDER 1900's internal resistors can be
linked in.
3
2 ELECTRICAL INSTALLATION…
1
2
7
8
9
3
4
5
6
Rx+
Rx–
Tx+
Tx–
Computer Terminal or Host Computer
Serial Module
Terminal Board
0V
'A'
'B'
'B'
'A'
GND
GND
3
4
9
Links on Serial Module
PL2
COMMANDER 1900
Linked Out
+5V
0V
1.8k
Ω
Pull-down
Resistor
1.8K Pull-up
Resistor
+5V
1.8k
Ω
Pull-up
Resistor
0V
1.8kΩ Pull-down
Resistor
Note. If an RS422/485 adaptor card without pull-up and pull-down resistors is used, the COMMANDER 1900's
internal resistors must be linked out.
Fig. 2.2 Pull-up and Pull-down Resistors (5-wire Operation)
4
…2 ELECTRICAL INSTALLATION
2.4 Termination Resistors – Fig. 2.3
For long transmission lines, termination resistors are required on the last slave in the chain and the host computer/computer
terminal – see Fig. 2.3. Under normal operating conditions the resistors are required at the receive inputs only. For 3-wire
operation the slave termination resistor is fitted to the serial module terminal board – see Fig. 2.3A. For 5-wire operation the slave
termination resistor is selected using plug-in links on the serial module – see Fig. 2.3B.
2.5 RS485/422 Standard
The RS485 standard quotes connection of thirty two slaves maximum, to any single driver (computer terminal or host computer);
the RS422 standard quotes connection of up to ten slaves. However, these numbers can be increased if the driver’s serial port
permits.
76
12 1
2
5
4
3
6
A – 3-wire Operation
120Ω
External Termination Resistor – see Note
Tx+/Rx+
Tx–/Rx–
B – 5-wire Operation
Termination
Resistor
Linked In –
see Note
112
310
211
Termination
Resistor
Linked Out
310
211
112
PL2
PL2
PL2
Fig. 2.3 Slave Termination Resistors
Note.
For
3-wire operation an external 120Ω resistor must be on the last slave in the chain. The resistor is fitted across
terminals 4 and 5 on the serial module terminal board.
For
5-wire operation the internal termination resistor on the last slave in the chain must be linked in.
5
2 ELECTRICAL INSTALLATION
2.6 Serial Connections – Fig. 2.4
Information.
Up to
10 slaves can be connected to a single RS422 adaptor card on a PC.
Up to 32 slaves can be connected to a single RS485 adaptor card on a PC.
The maximum serial data transmission line length for both
RS422 and RS485 systems is 1200m.
All connections, apart from those for serial data communication, are made as shown in
Section 4 of the Installation Guide
.
Make serial data connections as shown in Fig. 2.4. The type of cable used is dependent on the cable length:
Up to 6m standard screened or twisted pair cable
Up to 300m twin twisted pair with overall foil screen and an integral drain wire, e.g. Belden 9502 or equivalent
Up to 1200m twin twisted pair with separate foil screens and integral drain wires for each pair, e.g. Belden 9729
or equivalent
Fig. 2.4 Serial Module Connections
A – Connections for 3-wire Operation
B – Connections for 5-wire Operation
8
4
5
Connections
GND
TX+
TX–
RX+
RX–
OPTO22 Board Pin Identification
Part Number AC24 AT & AC34
3
4
5
8
9
TX+
TX–
GND
COMMANDER 1900 Serial Module Terminal Board
Terminal Number Connections
Table 2.2 Terminal and Pin Identification for 5-wire Operation
Table 2.1 Terminal and Pin Identification for 3-wire Operation
COMMANDER 1900 Serial Module Terminal Board
8
4
5
6
7
Connections
GND
TX+
TX–
RX+
RX–
OPTO22 Board Pin Identification
Part Number AC24 AT & AC34
3
4
5
8
9
GND
TX+
TX–
RX+
RX–
ConnectionsTerminal Number
4
7
6
OPTO22 Adaptor
Board Connections
Serial Module
Connections
5
8
Tx+
Tx–
Rx+
Rx–
GND
Tx+
Tx–
Rx+
Rx–
GND
4
7
6
Serial Module
Connections
5
8
OPTO22 Adaptor
Board Connections
Tx+
Tx–
GND
Tx+
Tx–
Rx+
Rx–
GND
8
5
4
9
3
8
5
4
9
3
Screen
Screen
6
3 ADVANCED CONFIGURATION LEVEL
Set Up Functions Keys
Set Up Logic
Set up Function Keys
SEtUP
F–KEY1
Set Up Logic
SEtUP
LOGIC
Set Up RS485
Section 3.1, opposite
SEtUP
rS 485
3/5 Wire Select
Controller Ident
Parity
tYPE
_LINE
Baud Rate
Set Up RS485
bAUd
____
IdENt
____
PArItY
____
OPrtOr
LEVEL
bASIC
CONFIG
AdVNCd
CONFIG
Basic Config
Advanced Config
Operator Level
CONtrL
CONFIG
Control Config
Set Up Logic
PEN
FUNCt
Set Up Pen Function
Input Assignment
INPUt
ASSIGN
Input Assignment
Refer to Programming Guide
Fig. 3.1 Location of the Serial Data (RS485) Communication Page
7
3 ADVANCED CONFIGURATION LEVEL
3.1 Serial Data Communication Page
Information.
Programmable for 3 or 5 wire connections.
Programmable baud rate (1200 to 9600 baud).
Odd or even parity.
The general programming procedure is as detailed in the
Operating Guide. In this Section, parameters in the lower display denoted
are Company Standard Settings. The instrument is dispatched programmed with these settings.
tYPE
3 LINE
bAUd
1200
SEt UP
rS 485
5 LINE
2400
4800
9600
IdENt
1
PArItY
NONE
Odd
EVEN
Page Header – Set Up RS485.
Connection Type
Select the required number of transmission wires (3 line, 5 line).
Transmission Rate
Select the transmission rate required (1200 slowest, 9600 fastest).
Controller Identification
Assign the controller an identification number between 1 and 99.
Parity
Select the appropriate parity to match the computer terminal or host computer.
Return to Set Up RS485 frame.
8
4 MODBUS PROTOCOL
Table 4.1 Modbus Function Codes
*NAK = Negative Acknowledgement
Information.
The COMMANDER 1900 operates as a Modbus, Remote Terminal Unit (RTU) slave.
Parity checking – used to detect transmission errors in individual characters.
Cyclic redundancy checking – used to detect errors in the master messages and slave responses.
Non-volatile memory save command.
4.1 Introduction to Modbus Protocol
Modbus communication is based on a master and a slave arrangement. The master sends a message to one slave at a time and
waits for a reply.
The slave cannot accept a new message until the existing message is processed and a reply sent to the master (maximum
response time 250 milliseconds). The slave monitors the elapsed time between receipt of characters. If the elapsed time without
a new character is 3
1/
2 character times, the slave assumes the next character received is the start of a new message.
To allow the master to differentiate between more than one slave in a system, each slave is given a unique identity address
(between 1 and 99).
A broadcast address (address zero) can be used to access all slave devices with one command. This is limited to write messages
only and there is no slave acknowledgment.
Note. Modbus RTU requires 1 start bit, 8 data bits, 1 parity bit (optional) and 1 or 2 stop bits.
4.1.1 Non-volatile Memory Limitations
Note. A non-volatile memory is used to store any parameter changes made via the serial link to ensure that the information
is retained during mains interruption or power-down. The memory used is rated at 10
4
write cycles per register and each
register is assigned a particular parameter, e.g. Alarm trip value, Channel 1. If the number of write cycles to any particular
register exceeds this value, the register's contents may not be retained.
To restrict unnecessary use of the non-volatile memory registers the memory enable/disable command is provided (Coil number
181, Section 7.1). The command can be used before parameters which do not need to be stored in the non-volatile memory, e.g.
frequently changed parameters or parameters which do not have to be retained on power-down.
4.2 Modbus Function Codes
The function code field instructs the addressed slaves what function to perform. Table 4.1 shows the function codes, their
meaning, and the action they initiate.
Modbus
Function Code
Modbus Message Name COMMANDER 1900 Definition
01 Read Coil Status
Read up to 16 consecutive discrete (boolean) points from a specific starting point. The
COMMANDER 1900 returns zeros for points which do not contain defined data and NAKs*
any request for point numbers greater than 200.
03 Read Holding Register
Read up to 8 consecutive registers from a specific starting register. The COMMANDER
1900 returns zeros from registers which do not contain defined data and NAKs any request
for register numbers greater than 250.
05 Force Single Coil
Write one discrete (boolean) point. The COMMANDER 1900 NAKs this if the point is not
currently writeable.
06 Preset Single Register
Write one register. The COMMANDER 1900 NAKs if the register is not currently writeable.
This function code also applies to any currently applicable limits to the value before storage
in the database.
08 Loopback Diagnostic Test Echo the message, only ‘Return of Query’ is supported.
16 Preset Multiple Registers
Write up to 8 consecutive registers from a specified starting register. The COMMANDER
1900 NAKs if any of the registers are not currently writeable, but still carries out all the
writes which are valid, applying any currently applicable limits to the value before storage in
the database. This function code is only available if ‘write to non-volatile memory’ is
disabled – see coil number 181.
9
5 MODBUS FUNCTIONS
This section shows typical examples of Modbus function codes 01, 03, 05, 06, 08 and 16.
5.1 Read Coil Status – Function Code 01
5.1.1 Read Coil Status Query
This function allows the user to obtain the ON/OFF status of logic coils used to control discrete outputs from the addressed slave
only. Broadcast mode is not supported with this function code. In addition to the slave address and function fields, the message
requires that the information field contain the initial coil offset address to be read (starting address) and the number of locations
to be interrogated must obtain status data.
Note. The coil offset address is the coil number minus one, e.g. to start at coil 31 the data start value must be set to 30 (1EH).
Example – a read coil status request to read 16 coils from slave (01) starting at coil 31 (alarm A status channel 1) is shown below.
5.1.2 Read Coil Status Response
The data is packed one bit for each coil (1 = ON, 0 = OFF). The response includes the slave address, function code, quantity of
data characters, the data characters and error checking. The low order bit of the first character contains the first addressed coil
and the remainder follow. For coil quantities that are not even multiples of eight, the last characters are filled in with zeros at high
order end.
Example – the response to the read coil status query shows the following:
Alarm A status channel 1 ON
Alarm B status channel 1 OFF
Alarm C status channel 1 ON
Alarm D status channel 1 OFF
Alarm A,B,C,D status channel 2 all OFF
Alarm A,B,C,D status channel 3 all OFF
Alarm A,B,C,D status channel 4 all OFF
Address Function
Coil Start
Offset High
Coil Start
Offset Low
Number of
Coils High
Number of
Coils Low
Error Check Field (CRC-16)
01 01 00 1E 00 10 5D C0
5.2 Read Holding Register – Function Code 03
5.2.1 Read Holding Register Query
The Read holding registers allow the user to obtain the binary contents of holding registers in the addressed slave.
Note. The data start register must contain the offset address of the first register to be accessed, e.g. to start at register 121the
data start register must contain 120 (78H).
Broadcast mode is not allowed.
Example – a read holding register request to read 6 holding registers from slave (01) starting at holding address 121 (alarm trip
A1) is shown below.
Address Function Byte Count
Data Coil Status
31 to 38
Data Coil Status
39 to 46
Error Check Field (CRC-16)
01 01 02 05 00 BA AC
Address Function
Register Start
Offset High
Register Start
Offset Low
Data Number of
Registers High
Data Number of
Registers Low
Error Check Field (CRC-16)
01 03 00 78 00 06 45 D1
10
…5 MODBUS FUNCTIONS
5.2.2 Read Holding Register Response
The addressed slave responds with its address and function code, followed by the information field. The information field contains
1 byte describing the quantity of data bytes to be returned. The contents of each register requested (DATA) is two bytes, the first
byte includes the high order bits and the second the low order bits.
Example – the response to the read holding register query shows the following:
Alarm trip A1 150
Alarm trip B1 50
Alarm trip C1 100
Alarm trip D1 400
Alarm trip A2 0
Alarm trip B2 0
5.3 Force Single Coil – Function Code 05
5.3.1 Force Single Coil Query
This message forces a single coil either ON or OFF. The data value 65,280 (FF00 HEX) sets the coil ON and the value zero turns
it OFF. All other values are illegal and do not affect the coil.
Note. To write to a coil the coil offset address must be used, e.g. to write to coil 149, the coil address 148(94H) is transmitted.
The use of slave address zero (broadcast mode) forces all attached slaves to modify the desired coil.
Example – a force single coil request to switch ON coil address 149 (auto/manual state, channel 1) in slave 01 is shown below.
5.3.2 Force Single Coil Response
The response is confirmation of the query after the coil state has been altered.
Example:
Address Function
Byte
Count
Holding
Register 121
High Low
Holding
Register 122
High Low
Holding
Register 123
High Low
Holding
Register 124
High Low
Holding
Register 125
High Low
Holding
Register 126
High Low
Error Check Field
(CRC-16)
01 03 0C 00 96 00 32 00 64 01 90 00 00 00 00 D9 91
Address Function
Coil Offset
High
Coil Offset
Low
Data Value High Data Value Low Error Check Field (CRC-16)
01 05 00 94 FF 00 CD D6
Address Function
Coil Offset
High
Coil Offset
Low
Data Value High Data Value Low Error Check Field (CRC-16)
01 05 00 94 FF 00 CD D6
11
5.4 Preset Single Register – Function Code 06
5.4.1 Preset Single Register Query
The preset single register allows the user to modify the contents of a holding register.
Note. Function codes 5, 6 and 16 are the only messages that are recognized as valid for broadcast.
Example – a preset single register request to write the value 500 to holding register address 121 (alarm trip A1) in slave 01 is
shown below.
Note. To write to a register, the registers offset address must be used, e.g. to write to register 121, the offset address
120(78H) is transmitted.
5 MODBUS FUNCTIONS…
5.4.2 Preset Single Register Response
The normal response to a preset single register request is to retransmit the query message after the register has been altered.
Example:
5.5 Loopback Test – Function Code 08
5.5.1 Loopback Test Query
The purpose of the loopback test is to test the Modbus system, it does not affect the content of the controller. Variations in the
response may indicate faults in the Modbus system. The information field contains 2 bytes for the designation of the diagnostic
code followed by 2 bytes to designate the action to be taken.
Example:
*These are considered to be the information fields for diagnostic mode.
5.5.2 Loopback Test Response
The response always echoes the query, only diagnostic code 0 (bytes 3 and 4) can be used.
Example:
Address Function
Register
Offset High
Register
Offset Low
Data Value High Data Value Low Error Check Field (CRC-16)
01 06 00 78 01 F4 09 C4
Address Function
Register
Offset High
Register
Offset Low
Data Value High Data Value Low Error Check Field (CRC-16)
01 06 00 78 01 F4 09 C4
Address Function
Data Diagnostic
Code High
Data Diagnostic
Code Low
Data* Data * Error Check Field (CRC-16)
01 08 00 00 A5 37 DA 8D
Address Function
Data Diagnostic
Code High
Data Diagnostic
Code Low
Data Data Error Check Field (CRC-16)
01 08 00 00 A5 37 DA 8D
12
…5 MODBUS FUNCTIONS
5.6 Write Multiple Registers – Function Code 16
5.6.1 Write Multiple Registers Query
Holding registers existing within the controller can have their contents changed by this message (a maximum of 8 registers).
When used with slave address zero (broadcast mode) all slave controllers load the selected registers with the contents specified.
Example – a write multiple register request to write the value 10 to the register address 121 and the value 100 to the register
address 122 in slave 01 is shown below.
5.6.2 Write Multiple Registers Response
The response confirms slave identification, function code, starting register address and quantity only.
Example:
Address Function
Register
Start
Offset
High
Register
Start
Offset
Low
Number
of
Registers
Byte
Count
Holding
Register
121 High
Holding
Register
121 Low
Holding
Register
122 High
Holding
Register
122 Low
Error Check Field
(CRC-16)
01 10 00 78 00 02 04 00 0A 00 64 D4 C4
Address Function
Register Start
Offset High
Register Start
Offset Low
Number of Registers Error Check Field (CRC-16)
01 10 00 78 00 02 00 10 90
13
6 EXCEPTION RESPONSES
The exception response codes sent by the slave are shown in Table 6.1. When a slave detects one of these errors, it sends a
response message to the master consisting of slave address, function code, error code and error check fields.
Exception
Response
Code
Exception Response Name Exception Response Definition
01 Illegal Function The message function received is not an allowable action for the C1900.
02 Illegal Data Address The address reference in the data field is not an allowable address for the C1900.
03 Illegal Data Value The value referenced in the data field is not allowable in the addressed slave location.
07 Negative Acknowledgment The function just requested cannot be performed.
08 Memory Parity Error Parity check indicates an error in one or more of the characters received.
Table 6.1 Exception Response Codes
6.1 Examples
A read register request to read holding register address 251 of slave 01 (undefined address for slave, beyond address limit) is
shown below.
The response is an exception response sighting ‘illegal data address’. To indicate that the response is a notification of an error, the
most significant bit of the function code is set to 1.
Slave
Address
Function
Register Start
Offset High
Register Start
Offset Low
Number of
Registers High
Number of
Registers Low
Error Check Field (CRC-16)
01 03 00 FA 00 06 E5 F9
Slave Address Function Exception Code Error Check Field (CRC-16)
01 83 02 CO F1
14
7 MODBUS REGISTERS
7.1 Coils
Coil Number Read/Write Description Response/Entry
Input Failure States
011 R Main Input
012 R Module 2
013 R Module 3 0 = Active
014 R Module 4 1 = Failed
015 R Module 5
A to D Converter
Failure States
021 R Main Converter
022 R Module 2
023 R Module 3 0 = Active
024 R Module 4 1 = Failed
025 R Module 5
Alarm Status
031 R Alarm A Channel 1
032 R Alarm B Channel 1
033 R Alarm C Channel 1
034 R Alarm D Channel 1
035 R Alarm A Channel 2
036 R Alarm B Channel 2
037 R Alarm C Channel 2
038 R Alarm D Channel 2 0 = Inactive
039 R Alarm A Channel 3 1 = Active
040 R Alarm B Channel 3
041 R Alarm C Channel 3
042 R Alarm D Channel 3
043 R Alarm A Channel 4
044 R Alarm B Channel 4
045 R Alarm C Channel 4
046 R Alarm D Channel 4
Digital Input States
051 R Main Module Digital Input 1
052 R Main Module Digital Input 2
061 R Module 2 Digital Input 1
062 R Module 2 Digital Input 2
071 R Module 3 Digital Input 1
072 R Module 3 Digital Input 2
081 R Module 4 Digital Input 1
082 R Module 4 Digital Input 2
083 R Module 4 Digital Input 3
084 R Module 4 Digital Input 4
085 R Module 4 Digital Input 5 0 = Inactive
086 R Module 4 Digital Input 6 1 = Active
087 R Module 4 Digital Input 7
088 R Module 4 Digital Input 8
091 R Module 5 Digital Input 1
092 R Module 5 Digital Input 2
093 R Module 5 Digital Input 3
094 R Module 5 Digital Input 4
095 R Module 5 Digital Input 5
096 R Module 5 Digital Input 6
097 R Module 5 Digital Input 7
098 R Module 5 Digital Input 8
15
7 MODBUS REGISTERS…
…7.1 Coils
Coil Number Read/Write Description Response/Entry
Logic Equation Results
121 R Logic Equation 1
122 R Logic Equation 2
123 R Logic Equation 3
124 R Logic Equation 4 0 = Inactive
125 R Logic Equation 5 1 = Active
126 R Logic Equation 6
127 R Logic Equation 7
128 R Logic Equation 8
Real Time States
131 R Channel 1 0 = Inactive
132 R Channel 2 1 = Active
Auto/Manual States
141 R Manual State Channel 1 0 = Auto, 1 = Manual
142 R Auto State Channel 1 0 = Manual, 1 = Auto
143 R Manual State Channel 2 0 = Auto, 1 = Manual
144 R Auto State Channel 2 0 = Manual, 1 = Auto
149 R/W A/M State Channel 1 0 = Auto, 1 = Manual
150 R/W A/M State Channel 2 0 = Auto, 1 = Manual
On/Off Count States
151 R Channel 1 0 = Off
152 R Channel 2 1 = On
Valve Open/Close Relay States
161 R Open Relay State Ch. 1
162 R Close Relay State Ch. 1 0 = De-energized
163 R Open Relay State Ch. 2 1 = Energized
164 R Close Relay State Ch. 2
171* R Event Status 0 = Divert, 1 = Forward
(C1951, C1952, C1953
Pasteurizer versions only)
MODBUS
181 R/W Save MODBUS writes to
Non-Volatile Memory 0 = Not Saved, 1 = Saved
16
…7 MODBUS REGISTERS
7.2 Holding Registers
Register Number Read/Write Description Response/Entry
Analog Inputs
011 R Process Variable 1 In Engineering Units in
012 R Process Variable 2 Range –9999 to +9999
013 R Process Variable 3
014 R Process Variable 4
015 R Process Variable 1 Failure State 0 = Input Active
016 R Process Variable 2 Failure State 1 = Input Failed
017 R Process Variable 3 Failure State 2 = A to D Failed
018 R Process Variable 4 Failure State 3 = Input and A to D Failed
Number of Decimal Points
019 R Process Variable 1 Value
020 R Process Variable 2 Value 0 to 3 Decimal Places
021 R Process Variable 3 Value
022 R Process Variable 4 Value
Input Values
031 R Main Input
032 R Module 2
033 R Module 3 In Engineering Units in
034 R Module 4 Range –9999 to +9999
035 R Module 5
Engineering Ranges
041 R Input 1 Decimal Point Position
042 R Input 2 Decimal Point Position
043 R Input 3 Decimal Point Position 0 to 3 Decimal Places
044 R Input 4 Decimal Point Position
045 R Input 5 Decimal Point Position
17
7 MODBUS REGISTERS…
7.3 Controller Settings/Outputs
Register Number Read/Write Description Response/Entry
Controller Settings/Outputs
Channel 1
051 R Process Variable 1 –9999 to +9999
052 R/W Control Set Point –9999 to +9999
053 R/W Control Output (write in manual mode) 0 to 1000 Representing (0.0.to 100.0%)
054 R Position Feedback 1 0 to 1000 Representing (0.0.to 100.0%)
0 = Input Active
055 R Position Feedback 1 Failure State 1 = Input Failed
2 = A to D Failed
3 = Input and A to D Failed
056 R/W On/Off Hysteresis Value 0 to 1000 Representing (0.0.to 100.0%)
057 R/W Cycle-Time Heat Control 10 to 3000 (1.0 to 300.0 Seconds)
058 R/W Proportional Band (Heat) Control 1 to 9999 (0.1 to 999.9%)
059 R/W Integral Value (Heat) Control 0 = OFF, 1 to 7200 Seconds
060 R/W Manual Reset (Heat) Control 0 to 1000 (0.0 to 100.0%)
061 R/W Derivative Action 1 to 9999 (0.1 to 999.9 Seconds)
062 R/W Approach Band 1 to 30 (0.1 to 3.0)
063 R/W Heat Output (write manual mode only) 0 to 1000 (0.0 to 100.0%)
064 R/W Cool Output (write manual mode only) 0 to 1000 (0.0 to 100.0%)
065 R/W Proportional Band Cool Control 1 to 9999 (0.1 to 999.9%)
066 R/W Integral Value Cool Control 0 = OFF, 1 to 7200 Seconds
067 R/W Manual Reset Cool Control 0 to 1000 (0.0 to 100.0%)
068 R/W Cycle-Time Cool Control 10 to 3000 (1.0 to 300.0 Seconds)
069 R/W Crossover Band 0 to 1000 (0.0 to 100.0%)
070 R/W Transition Band 0 to 1000 (0.0 to 100.0%)
Controller Settings/Outputs
Channel 2
071 R Process Variable 2 –9999 to +9999
072 R/W Control Set Point –9999 to +9999
073 R/W Control Output (write in manual mode) 0 to 1000 Representing (0.0.to 100.0%)
074 R Position Feedback 2 0 to 1000 Representing (0.0.to 100.0%)
0 = Input Active
075 R Position Feedback 2 Failure State 1 = Input Failed
2 = A to D Failed
3 = Input and A to D Failed
076 R/W On/Off Hysteresis Value 0 to 1000 Representing (0.0.to 100.0%)
077 R/W Cycle-Time Heat Control 10 to 3000 (1.0 to 300.0 Seconds)
078 R/W Proportional Band (Heat) Control 1 to 9999 (0.1 to 999.9%)
079 R/W Integral Value (Heat) Control 0 = OFF, 1 to 7200 Seconds
080 R/W Manual Reset (Heat) Control 0 to 1000 (0.0 to 100.0%)
081 R/W Derivative Action 1 to 9999 (0.1 to 999.9 Seconds)
082 R/W Approach Band 1 to 30 (0.1 to 3.0)
083 RW Heat Output (write manual mode only) 0 to 1000 (0.0 to 100.0%)
084 RW Cool Output (write manual mode only) 0 to 1000 (0.0 to 100.0%)
085 R/W Proportional Band Cool Control 1 to 9999 (0.1 to 999.9%)
086 R/W Integral Value Cool Control 0 = OFF, 1 to 7200 Seconds
087 R/W Manual Reset Cool Control 0 to 1000 (0.0 to 100.0%)
088 R/W Cycle-Time Cool Control 10 to 3000 (1.0 to 300.0 Seconds)
089 R/W Crossover Band 0 to 1000 (0.0 to 100.0%)
090 R/W Transition Band 0 to 1000 (0.0 to 100.0%)
18
…7 MODBUS REGISTERS
7.4 Set Points
Register Number Read/Write Description Response/Entry
Set Points Channel 1
101 R/W Local Set Point –9999 to +9999
102 R/W Dual Set Point –9999 to +9999
103 R Remote Set Point (without Ratio/Bias) –9999 to +9999
104 R Remote Set Point (with Ratio/Bias) –9999 to +9999
105 R Remote Set Point Failure State Refer to Process Variable Failure States
107 R/W Set Point Selection 0 = Local, 1 = 2nd Set Point
Set Points Channel 2
111 R/W Local Set Point –9999 to +9999
112 R/W Dual Set Point –9999 to +9999
113 R Remote Set Point (without Ratio/Bias) –9999 to +9999
114 R Remote Set Point (with Ratio/Bias) –9999 to +9999
115 R Cascade Set Point –9999 to +9999
116 R Remote Set Point Failure State Refer to Process Variable Failure States
117 R/W Set Point Selection 0 = Local, 1 = 2nd Set Point
7.5 Alarm Settings
Register Number Read/Write Description Response/Entry
Alarm Settings
121 R/W Alarm A Trip Value Channel 1
122 R/W Alarm B Trip Value Channel 1
123 R/W Alarm C Trip Value Channel 1
124 R/W Alarm D Trip Value Channel 1
125 R/W Alarm A Trip Value Channel 2
126 R/W Alarm B Trip Value Channel 2
127 R/W Alarm C Trip Value Channel 2
128 R/W Alarm D Trip Value Channel 2 –9999 to +9999 High/Low Process Limit
129 R/W Alarm A Trip Value Channel 3 5 to 5000 (0.5 to 500.0%) Fast/Slow Rate
130 R/W Alarm B Trip Value Channel 3 Alarm Limit
131 R/W Alarm C Trip Value Channel 3
132 R/W Alarm D Trip Value Channel 3
133 R/W Alarm A Trip Value Channel 4
134 R/W Alarm B Trip Value Channel 4
135 R/W Alarm C Trip Value Channel 4
136 R/W Alarm D Trip Value Channel 4
141 R Alarm A Type Channel 1
142 R Alarm B Type Channel 1
143 R Alarm C Type Channel 1
144 R Alarm D Type Channel 1
145 R Alarm A Type Channel 2 0 = Alarm Off
146 R Alarm B Type Channel 2 1 = High Process
147 R Alarm C Type Channel 2 2 = Low Process
148 R Alarm D Type Channel 2 3 = High Output
149 R Alarm A Type Channel 3 4 = Low Output
150 R Alarm B Type Channel 3 5 = High Deviation
151 R Alarm C Type Channel 3 6 = Low Deviation
152 R Alarm D Type Channel 3 7 = Fast Rate
153 R Alarm A Type Channel 4 8 = Slow Rate
154 R Alarm B Type Channel 4
155 R Alarm C Type Channel 4
156 R Alarm D Type Channel 4
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28