Daikin FVXS09NVJU Installation guide

Category
Split-system air conditioners
Type
Installation guide

This manual is also suitable for

EnglishFrançaisEspañol
DAIKIN ROOM AIR CONDITIONER
INSTALLATION MANUAL
R410A Split Series
Installation manual
Manuel dinstallation
Manual de instalación
MODELS
FVXS09NVJU
FVXS12NVJU
FVXS18NVJU
Manuel dinstallation
00_CV_3P379970-3.indd 1 10/31/2014 2:30:59 PM
1
English
Safety Considerations
• ReadtheseSafety Considerationscarefullytoensure
correctinstallation.
• ThismanualclassiestheprecautionsintoDANGER,
WARNINGandCAUTION.
Besuretofollowalltheprecautionsbelow:theyareall
importantforensuringsafety.
DANGER ����������� Indicatesanimminentlyhazardous
situationwhich,ifnotavoided,will
resultindeathorseriousinjury.
WARNING ��������� FailuretofollowanyofWARNING
islikelytoresultinsuchgrave
consequencesasdeathorserious
injury.
CAUTION ���������� FailuretofollowanyofCAUTION
mayinsomecasesresultingrave
consequences.
• Aftercompletinginstallation,testtheunittocheckfor
installationerrors.Givetheuseradequateinstructions
concerningtheuseandcleaningoftheunitaccordingtothe
OperationManual.
DANGER
• Refrigerantgasisheavierthanairandreplacesoxygen.
Amassiveleakcouldleadtooxygendepletion,especially
inbasements,andanasphyxiationhazardcouldoccur
leadingtoseriousinjuryordeath.
• Iftherefrigerantgasleaksduringinstallation,ventilatethe
areaimmediately.
Refrigerantgasmayproduceatoxicgasifitcomes
incontactwithresuchasfromafanheater,stoveor
cookingdevice.
Exposuretothisgascouldcausesevereinjuryordeath.
• Aftercompletingtheinstallationwork,checkthatthe
refrigerantgasdoesnotleak.
Refrigerantgasmayproduceatoxicgasifitcomes
incontactwithresuchasfromafanheater,stoveor
cookingdevice.
Exposuretothisgascouldcausesevereinjuryordeath.
• Donotgroundunitstowaterpipes,telephonewiresor
lightningrodsbecauseincompletegroundingcouldcause
asevereshockhazardresultinginsevereinjuryordeath,
andtogaspipesbecauseagasleakcouldresultinan
explosionwhichcouldleadtosevereinjuryordeath.
• Safelydisposeofthepackingmaterials.
Packingmaterials,suchasnailsandothermetalor
woodenparts,maycausestabsorotherinjuries.
Tearapartandthrowawayplasticpackagingbagssothat
childrenwillnotplaywiththem.
Childrenplayingwithplasticbagsfacethedangerofdeath
bysuffocation.
• Donotinstallunitinanareawhereammablematerials
arepresentduetoriskofexplosionresultinginserious
injuryordeath.
• Donotgroundunitstotelephonewiresorlightningrods
becauselightningstrikescouldcauseasevereshock
hazardresultinginsevereinjuryordeath,andtogas
pipesbecauseagasleakcouldresultinanexplosion
whichcouldleadtosevereinjuryordeath.
Contents
Safety Considerations ������������������������������������ 1
Accessories ����������������������������������������������������� 3
Choosing an Installation Site ������������������������ 3
1. Indoorunit.............................................................3
2. Wirelessremotecontroller....................................3
Indoor Unit Installation Drawings ����������������� 4
Indoor Unit Installation ����������������������������������� 5
1. Refrigerantpiping.................................................5
2. Drillingawallholeandinstallingwallembedded
pipe.......................................................................7
3. Drainpiping...........................................................7
4. Installingindoorunit..............................................8
4-1. Preparation...................................................8
4-2. Installation.....................................................9
5. Flaringthepipeend..............................................1 2
6. Connectingtherefrigerantpipe............................12
6-1. Cautiononpipinghandling...........................13
6-2. Selectionofcopperandheatinsulation
materials.......................................................13
7. Checkingforgasleakage.....................................1 4
8. Attachingtheconnectionpipe..............................1 4
9. Connectingthedrainhose....................................14
10. Wiring...................................................................1 5
11. WhenconnectingtoanHAsystem......................1 6
12. Howtosetthedifferentaddresses.......................1 7
Trial Operation and Testing ���������������������������� 18
1. Trialoperationandtesting.....................................1 8
2. Testitems..............................................................18
01_EN_3P379970-3.indd 1 10/29/2014 11:23:09 AM
2
English
WARNING
• Installationshallbelefttotheauthorizeddealeroranother
trainedprofessional.
Improperinstallationmaycausewaterleakage,electrical
shock,re,orequipmentdamage.
• Installtheairconditioneraccordingtotheinstructions
giveninthismanual.
Incompleteinstallationmaycausewaterleakage,
electricalshock,reorequipmentdamage.
• Besuretousethesuppliedorexactspeciedinstallation
parts.
Useofotherpartsmaycausetheunittocometofall,
waterleakage,electricalshock,reorequipmentdamage.
• Installtheairconditioneronasolidbasethatisleveland
cansupporttheweightoftheunit.
Aninadequatebaseorincompleteinstallationmaycause
injuryorequipmentdamageintheeventtheunitfallsoff
thebaseorcomesloose.
• Electricalworkshallbecarriedoutinaccordancewith
theinstallationmanualandthenational,stateandlocal
electricalwiringcodes.
Insufcientcapacityorincompleteelectricalworkmay
causeelectricalshock,reorequipmentdamage.
• Besuretouseadedicatedpowercircuit.Neverusea
powersupplysharedbyanotherappliance.
Followallappropriateelectricalcodes.
• Forwiring,useawireorcablelongenoughtocoverthe
entiredistancewithnosplicesifpossible.
Donotuseanextensioncord.Donotputotherloadson
thepowersupply.
Useonlyaseparatededicatedpowercircuit.
(Failuretodosomaycauseabnormalheat,electricshock,
reorequipmentdamage.)
• Usethespeciedtypesofwiresforelectricalconnections
betweentheindoorandoutdoorunits.
Followallstateandlocalelectricalcodes.
Firmlyclamptheinter-unitwiresotheirterminalsreceive
noexternalstresses.
Incompleteconnectionsorclampingmaycauseterminal
overheating,reorequipmentdamage.
• Afterconnectingallwiresbesuretoshapethecablesso
thattheydonotputunduestressontheelectricalcovers,
panelsorterminals.
Installcoversoverthewires.Incompletecoverinstallation
maycauseterminaloverheating,electricalshock,reor
equipmentdamage.
• Wheninstallingorrelocatingthesystem,besuretokeep
therefrigerantcircuitfreefromallsubstancesotherthan
thespeciedrefrigerant(R410A),suchasair.
(Anypresenceofairorotherforeignsubstanceinthe
refrigerantcircuitcausesanabnormalpressurerisewhich
mayresultinrupture,resultingininjury.)
• Duringpumpdown,stopthecompressorbeforeremoving
therefrigerantpiping.
Ifthecompressorisstillrunningandthestopvalveis
openduringpumpdown,airwillbesuckedinwhenthe
refrigerantpipingisremoved,causingabnormallyhigh
pressurewhichcouldleadtoequipmentdamageorand
personalinjury.
• Duringinstallation,attachtherefrigerantpipingsecurely
beforerunningthecompressor.
Iftherefrigerantpipesarenotattachedandthestopvalve
isopenduringinstallation,airwillbesuckedinwhenthe
compressorisrun,causingabnormallyhighpressure
whichcouldleadtoequipmentdamageandpersonal
injury.
• Besuretoinstallagroundfaultcircuitinterrupter.
Failuretoinstallagroundfaultcircuitinterruptermay
resultinelectricallyshocks,orrepersonalinjury.
CAUTION
• Donotinstalltheairconditionerwheregasleakagewould
beexposedtoopenames.
Ifthegasleaksandbuildsuparoundtheunit,itmaycatch
re.
• Establishdrainpipingaccordingtotheinstructionsofthis
manual.
Inadequatepipingmaycausewaterdamage.
• Tightenthearenutaccordingtothespeciedtorque.A
torquewrenchshouldbeused.
Ifthearenutistightenedtoomuch,thearenutmay
crackovertimeandcauserefrigerantleakage.
• Donottouchtheheatexchangerns.
Improperhandlingmayresultininjury.
• Beverycarefulaboutproducttransportation.
SomeproductsusePPbandsforpackaging.Donot
useanyPPbandsforameansoftransportation.Itis
dangerous.
• Electricalworkmustbeperformedinaccordancewiththe
NEC/CECbyauthorizedpersonnelonly.
English
01_EN_3P379970-3.indd 2 10/29/2014 11:23:09 AM
3
English
Accessories
A Mountingplate 1 B Titaniumapatitephotocatalytic
air-purifyinglter 2C Drainhose 1
DInsulationtape 2 E Wirelessremotecontroller 1 F Remotecontrollerholder 1
G
Fixingscrewforremote
controllerholder1/8”×13/16”
(M3×20mm)
2HDrybatteryAAA.LR03
(alkaline) 2 J Operationmanual 1
KInstallationmanual 1
Choosing an Installation Site
• Beforechoosingtheinstallationsite,obtainuserapproval.
1 Indoor unit
Theindoorunitshouldbepositionedinaplacewhere:
1)therestrictionsoninstallationrequirementsspeciedinIndoor Unit Installation Drawingsonpage4aremet,
2)boththeairinletandairoutletareunobstructed,
3)theunitisnotexposedtodirectsunlight,
4)theunitisawayfromthesourceofheatorsteam,
5)thereisnosourceofmachineoilvapour(thismayshortentheindoorunitservicelife),
6)cool/warmairiscirculatedthroughouttheroom,
7)theunitisawayfromelectronicignitiontypeuorescentlamps(inverterorrapidstarttype)astheymayaffecttheremote
controllerrange,
8)theunitisatleast3.3ft(1m)awayfromanytelevisionorradioset(theunitmaycauseinterferencewiththepictureor
sound),
9)nolaundryequipmentisnearby.
2 Wireless remote controller
Turnonalltheuorescentlampsintheroom,ifany,andndalocationwhereremotecontrollersignalsareproperly
receivedbytheindoorunit(within23ft(7m)).
01_EN_3P379970-3.indd 3 10/29/2014 11:23:09 AM
4
English
Indoor Unit Installation Drawings
• Theindoorunitmaybemountedinanyofthethreestylesshownhere.
Exposed Half concealed
Floor Installation Wall Installation
Concealed
Grid (field supply)
Mounting
plate
A
Molding
• Locationforsecuringtheinstallationpanel.
unit: inch (mm)
(27-9/16 (700))
2-1/2 (64)
5-1/4
(134)
1 (26)
(23-5/8 (600))
22-5/8 (574)
5-1/2 (140)
9-13/16 (250) 5-7/8 (150)
9-1/16 (230)
25-3/8 (644)
8-1/4
(210)
6-5/16
(160)
1-3/8 (35)
1-3/8 (35)
Titanium apatite photocatalytic
air-purifying filter (2)
B
Front grille
Air filter
Front panel
1-15/16” (50mm)
or more
from walls
2-3/4 (70mm) or more
1-15/16” (50mm)
or more
from walls
Caulk pipe
hole gap
with putty.
Wireless remote
controller
Fixing screw
for remote
controller holder
1/8” × 13/16”
(M3 × 20mm) Remote controller
holder
E
F
G
English
01_EN_3P379970-3.indd 4 10/29/2014 11:23:10 AM
5
English
Indoor Unit Installation
1 Refrigerant piping
1)Drillahole(φ2-9/16inch(65mm)indiameter)inthespotindicatedbythe symbolintheillustrationasbelow.
2)Thelocationoftheholeisdifferentdependingonwhichsideofthepipeistakenout.
3)Forpiping,see“6� Connecting the refrigerant pipe”onpage12.
4)Allowspacearoundthepipeforaeasierindoorunitpipeconnection.
<Bottom piping>
1-3/4 (45)
1-3/4
(45)
1-3/4
(45)
1-3/4
(45)
2-3/8 (60)
2-15/16 (75)2-15/16 (75)
2-15/16 (75)2-15/16 (75)
1-3/4 (45)
Left back piping
Left bottom piping Right bottom piping
Wall
Right back piping Left/right piping
Left bottom piping Right bottom piping
2-15/16 (75)
1-15/16
(50)
1-3/8 (35)
Wall
2-15/16 (75)
Exposed installation Half concealed installation
Left bottom piping Right bottom piping
1-3/4 (45)
2-3/8 (60)
2-15/16 (75)
Left/right piping
1-3/4
(45)
1-3/4 (45)
2-15/16 (75)
unit:inch(mm)
Concealed installation
<Left/Right -side piping>
1-3/4 (45)
1-3/4
(45)
1-3/4
(45)
1-3/4
(45)
2-3/8 (60)
2-15/16 (75)2-15/16 (75)
2-15/16 (75)2-15/16 (75)
1-3/4 (45)
Left back piping
Left bottom piping Right bottom piping
Wall
Right back piping Left/right piping
1-3/4(45)
1-15/16 (50)
Wall
Left/right piping
Exposed installation Half concealed installation
Left bottom piping Right bottom piping
1-3/4 (45)
2-3/8 (60)
2-15/16 (75)
Left/right piping
1-3/4
(45)
1-3/4 (45)
2-15/16 (75)
unit:inch(mm)
Concealed installation
01_EN_3P379970-3.indd 5 10/29/2014 11:23:12 AM
6
English
<Back piping>
1-3/4 (45)
1-3/4
(45)
1-3/4
(45)
1-3/4
(45)
2-3/8 (60)
2-15/16 (75)2-15/16 (75)
2-15/16 (75)2-15/16 (75)
1-3/4 (45)
Left back piping
Left bottom piping Right bottom piping
Wall
Right back piping
Left/right piping
unit:inch(mm)
CAUTION
Minimum allowable length
• Thesuggestedshortestpipelengthis8.2ft(2.5m),inordertoavoidnoisefromtheoutdoorunitandvibration.
(Mechanicalnoiseandvibrationmayoccurdependingonhowtheunitisinstalledandtheenvironmentinwhichitisused.)
• Seetheinstallationmanualfortheoutdoorunitforthemaximumpipelength.
• Formulti-connections,seetheinstallationmanualforthemulti-outdoorunit.
13-3/4 (350)
2-15/16 (75)
1-3/4 (45)
Wall
Refrigerant pipe
Floor
unit: inch (mm)
English
01_EN_3P379970-3.indd 6 10/29/2014 11:23:12 AM
7
English
Indoor Unit Installation
2 Drilling a wall hole and installing wall embedded pipe
• Formetalframeormetalboardwalls,besuretouseawallembedded
pipeandwallholecoverinthefeed-throughholetopreventpossibleheat,
electricalshock,orre.
• Besuretocaulkthegapsaroundthepipeswithcaulkingmaterialtoprevent
waterleakage.
1)Drillafeed-throughholewithaφ2-9/16inch(65mm)diameterthroughthe
wallatadownwardangletowardtheoutside.
2)Insertawallembeddedpipeintothehole.
3)Insertawallholecoverintowallpipe.
4)Aftercompletingrefrigerantpiping,wiring,anddrainpiping,caulkthepipe
holegapwithputty.
Inside Outside
Caulking
(field supply)
Wall embedded
pipe
(field supply)
Wall hole cover
(field supply)
φ2-9/16”
(65mm)
3 Drain piping
1)Usecommercialrigidpolyvinylchloridepipe(generalVP20pipe,outerdiameter1inch(26mm),innerdiameter13/16
inch(20mm))forthedrainpipe.
2)Thedrainhose(outerdiameterφ11/16inch(φ18mm)atconnectingend,8-11/16inch(220mm)long)issuppliedwiththe
indoorunit.Preparethedrainpipepicturebelowposition.
3)
Thedrainpipeshouldbeinclined downwardsothatwaterwillowsmoothlywithoutanyaccumulation.(Shouldnotbe
trap.)
4)Insertthedrainhosetothisdepthsoitwon’tbepulledoutofthedrainpipe.
5)Insulate the indoor drain pipe with 3/8 inch (10mm) or more of insulation material to prevent condensation�
6)Removetheairltersandpoursomewaterintothedrainpantocheckthewaterowssmoothly.
1-15/16
(50)
8-11/16 (220)
5-7/8
(150)
3-15/16
(100)
3-15/16 (100)
Reducer Vinyl chloride
drain pipe
(VP-30)
Vinyl chloride
drain pipe
(VP-20)
Drain hose
C
unit: inch (mm)
Insert drain hose
to this depth so
it won’t be pulled
out of drain pipe. No trap is permitted.
Do not put the end
of the hose in water.
CAUTION
Usepolyvinylchlorideadhesiveagentforgluing.Failuretodosomaycausewaterleakage.
01_EN_3P379970-3.indd 7 10/29/2014 11:23:13 AM
8
English
4 Installing indoor unit
4-1� Preparation
• Removethefrontpanel.
1)Slideuntilthe2stoppersclickinside.
2)Openthefrontpanelforwardandremovethestring.
3)Removethefrontpanel.
1)Slide the stoppers.
2)Remove the string.
String
• Removethefrontgrille.
1)Removethe4screws.
2)Pullthefrontgrilleandremovethe3tabs.
Casing
3 tabs
Front grille
4 screws
Remove
front grille
Open the front panel
• Removetheupperandthesidecasings.
1)Removethe7screws.
2)Slideandremovetheuppercasing(2tabs).
3)Slideandremovetheleftandrightcasings(2tabson
eachside).
Slit portions
Upper casing
7 screws
Side casing
Side
casing
• Duringinstallation,ifneeded,cuttheslitportionsusing
nippersasshowintheillustrationbelow.
<For moldings> <For side piping>
Side casing
Bottom frame
Slit portions
Side casing
Bottom frame
Slit portions
English
01_EN_3P379970-3.indd 8 10/29/2014 11:23:18 AM
9
English
Indoor Unit Installation
4-2� Installation
Exposed installation
1)Securetheindoorunit
<Floor Installation>
• Securetheindoorunitusing6screws.(2screwsforoorand4screwsforrearwall)
Casing
2 screws
3/16” × 1” (M4 × 25mm) (field supply)
5 screws
3/16” × 1” (M4 × 25mm)
(field supply)
Mounting plate
A
Molding
The mounting
plate should be
installed on a wall
which can support
the weight of the
indoor unit.
A
4 screws
3/16” × 1” (M4 × 25mm) (field supply)
<Wall Installation>
• Securethe Amountingplateusing5screws.
• Securetheindoorunitusing4screwsforrearwall.
3/16” × 1” (M4 × 25mm)
(field supply)
Mounting plate
A
Molding
The mounting
plate should be
installed on a wall
which can support
the weight of the
indoor unit.
A
4 screws
3/16” × 1” (M4 × 25mm) (field supply)
2)Oncerefrigerantpipinganddrainpipingconnectionsarecomplete,llinthegapofthethroughholewithputty.
A gap can lead to condensation on the refrigerant pipe, and drain pipe, and the entry of insects into the pipes�
3)Attachandscrewstheeachsidecasingsanduppercasingintheiroriginalpositionusing7screws.
4)Attachthefrontgrillintheiroriginalpositionusing4screws.
5)Attachthefrontpanelintheiroriginalposition.
• Attachthestringtotheright,inner-sideofthefrontgrille.
• Closethefrontpanelandslideuntilthestoppersclickoutside.
Slide the stoppers
01_EN_3P379970-3.indd 9 10/29/2014 11:23:26 AM
10
English
Half concealed installation
1)Thesizeofawallopeningspaceshownintheillustrationon
theright.
26-3/8 – 27-3/16
(670-690)
23-1/1623-7/16
(585595)
unit: inch (mm)
Open size
Opening space
Floor
2)Therearoftheunitcanbexedwithscrewsatthepointsshownintheillustrationasbelow.Besuretoinstallthesupplemental
plateinaccordancewiththedepthoftheinnerwall.
Fixing point
on the back
Supplemental plate
(field supply)
5-1/2 (140)
9-1/16 (230)
25-3/8 (644)
Screw hole
Screw hole
Opening hole
5-7/8 (150)
9-13/16 (250)
3-3/4 (95)
Supplemental plate
(field supply)
9-13/16 (250)
7-7/8 (200)
unit: inch (mm)
CAUTION
Thesupplementalplateforinstallingthemainunitmustbeused,ortherewillbeagapbetweentheunitandthewall.
3)Securetheindoorunitusing6screws.(2screwsforoorand4screwsforrearwall)
Side casing
Upper casing
Remove 7 screws.
2 screws
(3/16” × 1” (M4 × 25mm))(field supply)4 screws
3/16” × 1” (M4 × 25mm) (field supply)
4)Oncerefrigerantpipinganddrainpipingconnectionsarecomplete,llinthegapofthethroughholewithputty.
A gap can lead to condensation on the refrigerant pipe, and drain pipe, and the entry of insects into the pipes�
5)Attachthefrontgrillintheiroriginalpositionusing4screws.
6)Attachthefrontpanelintheiroriginalposition.
•Attachthestringtothehook.
•Closethefrontpanelandslideuntilthestoppersclickoutside.
Slide the stoppers
CAUTION
• Usedrainpanedgeforhorizontalprojectionoftheindoorunit.
• Installtheindoorunitushagainstwall.
English
01_EN_3P379970-3.indd 10 10/29/2014 11:23:33 AM
11
English
Indoor Unit Installation
Concealed installation
• Installtheunitaccordingtotheinstructionsbelow.Failuretodosomaycauseleadtobothcoolingandheatingfailureandthe
condensationinsidethehouse.
1)Allowenoughspacebetweenthemainunitandceilingnottoobstructtheowofcool/warmair.
2)Placeapartitionplatebetweenoutletandinletsections.
3)Placeapartitionplateontherightside.
4)Changetheupwardairowdipswitch(SW2-4)toONtolimittheupwardairow.(Factorydefault:OFF)
• Removethefrontgrille.
• Switchthedipswitch(SW2-4)onthePCBintheelectricalequipmentboxtoON.
Upward airflow dipswitch
CAUTION
Besuretoturnontheupwardairowswitch.Failuretodosomaycauseincompletecooling/heatingandformation
ofcondensationinsidethehouse.
5)Useamovablelatticeattheairoutlettoallowtheadjustmentofcool/warmairowdirection.
6)Latticesizeshouldbe70%ormoreofopenrate.
Right side partition plate
Partition plate
1-15/16 (50)
or more
1-15/16 (50)
or more
Partition plate
Movable lattice
9/16 – 13/16
(15 – 20)
16-1/8 (410)
4-3/4
(120)
70% or more
of open rate
1-9/16 (40)
or less
13/16
1-3/16 (20-30)
Upper lattice
must not
project
Right side partition plate
Partition plate
Movable lattice
2-3/4 (70)
or more
unit: inch (mm)
• FortheinstallationprocessrefertoExposed installationonpage9.
01_EN_3P379970-3.indd 11 10/29/2014 11:23:35 AM
12
English
5 Flaring the pipe end
1)Cutthepipeendwithapipecutter.
2)Removeburrswiththecutsurfacefacingdownwardsothatthechipsdonotenterthepipe.
3)Putthearenutonthepipe.
4)Flarethepipe.
5)Checkthatthearingisproperlymade.
WARNING
• Donotusemineraloilonaredpart.
• Preventmineraloilfromgettingintothesystemasthiswouldreducethelifetimeoftheunits.
• Neverusepipingwhichhasbeenusedforpreviousinstallations.Onlyusepartswhicharedeliveredwiththeunit.
• NeverinstalladriertothisR410Aunitinordertoguaranteeitslifetime.
• Thedryingmaterialmaydissolveanddamagethesystem.
• Incompletearingmaycauserefrigerantgasleakage.
Flare’s inner
surface must
be flaw-free.
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.
Set exactly at the position shown below.
A
Flaring
Die A0-0.020 inch (0-0.5mm)
Clutch-type
Flare tool for R410A
0.039-0.059 inch (1.0-1.5mm)
Clutch-type (Rigid-type)
0.059-0.079 inch (1.5-2.0mm)
Wing-nut type (Imperial-type)
Conventional flare tool
Cut exactly at right angles.
Remove burrs Check
6 Connecting the refrigerant pipe
CAUTION
• Usethearenutxedtothemainunit.(Thisistopreventcrackingofthearenutasaresultofdeteriorationovertime.)
• Topreventgasleakage,applyrefrigerationoilonlytotheinnersurfaceoftheare.(UserefrigerationoilforR410A.)
• Useatorquewrenchwhentighteningthearenutstopreventdamagetothearenutsandgasleakage.
• Alignthecenterofbotharesandtightenthearenuts3or4turnsbyhand.Thentightenthemfullywithaspanneranda
torquewrench.
Torque wrench
Piping union
Flare nut
Do not apply refrigeration
oil to the outer surface.
Flare nut
Apply refrigeration oil to
the inner surface of the
flare.
Do not apply refrigeration oil to
the flare nut to avoid tightening
with excessive torque.
Spanner
Apply oil Tighten
Pipingsize Flarenuttighteningtorque
Gasside 3/8inch(9.5mm) 24.1-29.4ft•Ibf(32.7-39.9N•m)
1/2inch(12.7mm) 36.5-44.5ft•lbf(49.5-60.3N•m)
Liquidside 1/4inch(6.4mm) 10.5-12.7ft•lbf(14.2-17.2N•m)
English
01_EN_3P379970-3.indd 12 10/29/2014 11:23:36 AM
13
English
Indoor Unit Installation
6-1� Caution on piping handling
1)Protecttheopenendofthepipeagainstdustandmoisture.
2)Allpipebendsshouldbeasgentleaspossible.Useapipe
benderforbending.
Wall
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
Be sure to
place a cap.
Rain
6-2� Selection of copper and heat insulation materials
Whenusingcommercialcopperpipesandttings,observethefollowing:
• Insulationmaterial:Polyethylenefoam
Heattransferrate:0.041to0.052W/mK(0.024to0.030Btu/fth°F
(0.035to0.045kcal/mh°C))
BesuretouseinsulationthatisdesignedforusewithHVACSystems.
• ACRCopperonly.
Liquid pipe
Gas pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Inter-unit
wiring
• Besuretoinsulateboththegasandliquidpipingandobservetheinsulationdimensionsasbelow.
Gas side
Piping size
O.D. 3/8 inch
(9.5mm)
O.D. 1/2 inch
(12.7mm)
O.D. 1/4 inch
(6.4mm)
1-3/16 inch (30mm)
or more
1-9/16 inch (40mm)
or more
1-3/16 inch (30mm)
or more
0.031 inch (0.8mm)
(C1220T-O)
I.D. 15/32-19/32 inch
(12-15mm)
I.D. 9/16-5/8 inch
(14-16mm)
I.D. 5/16-13/32 inch
(8-10mm)
13/32 inch
(10mm) Min.
Minimum bend radius Piping thickness Thermal insulation size Thermal insulation
thickness
Liquid side
• Useseparatethermalinsulationpipesforgasandliquidrefrigerantpipes.
01_EN_3P379970-3.indd 13 10/29/2014 11:23:37 AM
14
English
7 Checking for gas leakage
1)Checkforleakageofgasafterairpurging.
2)Seethesectionsonairpurgesandgasleak
checksintheinstallationmanualforthe
outdoorunit.
Check for leakage here.
Apply soapy water and
check carefully for leaking
gas.
Wipe soapy water off after
the check is complete.
8 Attaching the connection pipe
• Attachthepipeaftercheckingforgasleakage,
describedabove.
1)Cuttheinsulatedportionoftheon-sitepiping,
matchingitupwiththeconnectingportion.
2)Securetheslitontherefrigerantpipingside
withthebuttjointontheauxiliarypipingusing
thetape,makingsuretherearenogaps.
3)Wraptheslitandthebuttjointwiththe
Dinsulationtape,makingsurethereareno
gaps.
Refrigerant
pipe
Refrigerant
pipe
Refrigerant
pipe
2)1) 3)
Auxiliary pipe
Slit Slit
Tape
Insulation
tape
D
CAUTION
• Insulatethejointofthepipessecurely.
Incompleteinsulationmayleadtowaterleakage.
• Pushthepipeinsidesoitdoesnotplaceundueforceonthefrontgrille.
9 Connecting the drain hose
• Insertthe Cdrainhoseintothesocketofthe
drainpan.
Fullyinsertthedrainhoseuntilitadherestoa
sealofthesocket.
Drain pan
Drain pan
Seal
Seal
Drain hose
C
Drain hose
C
English
01_EN_3P379970-3.indd 14 10/29/2014 11:23:40 AM
15
English
Indoor Unit Installation
10� Wiring
With a Multi indoor unit , install as described in the installation manual supplied with the Multi outdoor unit�
• Livethesensorsecuringplate,removethefrontmetalplatecover,andconnectthebranchwiringtotheterminalblock.
1)Asshownintheillustration,insertthewiresincludingthegroundwireintotheconduitandsecurethemwithlocknut
ontotheconduitmountingplate.
2)Stripwireends(3/4inch(20mm)).
3)Matchwirecolourswithterminalnumbersonindoorandoutdoorunit’sterminalblocksandrmlysecurethewiresin
thecorrespondingterminalswiththescrews.
4)Connectthegroundwirestothecorrespondingterminals.
5)Pullthewireslightlytomakesuretheyaresecurelyconnected.
6)Makesurethatthewiresdonotcomeincontactwiththemetalconduitfortheheatexchanger.
7)Incaseofconnectingtoanadaptersystem.RuntheremotecontrollercableandattachtheS21.(Referto“11� When
connecting to an HA system”onpage16.)
Conduit
mounting
plate
Conduit
Lock nut
Back
1
2
3
1 2 3
L
2
123
L
1
Use AWG 14 wires.
Firmly fix the wires with
the terminal screws.
Outdoor unit
Indoor
unit
Firmly fix the wires with
the terminal screws.
Use AWG16 if the connection wire
length is less than 33ft (10m), or
AWG14 if it is 33ft (10m) or more.
Terminal block
Electrical
component
box
Wire retainer
Use the specified
wire type.
Make sure that the wires
do not come in contact
with the metal conduit
for the heat exchanger.
Shape wires so
that the front metal
plate cover will fit
securely.
Front metal
plate electrical
wiring box cover
Sensor securing plate
WARNING
• Donotusetappedwires,strandedwires,extensioncords,orstarburstconnections,astheymaycauseoverheating,
electricalshock,orre.
• Donotuselocallypurchasedelectricalpartsinsidetheproduct.(Donotbranchthepowerforthedrainpump,etc.,fromthe
terminalblock.)Doingsomaycauseelectricshockorre.
• Donotconnectthepowerwiretotheindoorunit.Doingsomaycauseelectricshockorre.
01_EN_3P379970-3.indd 15 10/29/2014 11:23:42 AM
16English
11� When connecting to an HA system
1)Removethefrontpanelandthefrontgrille.(Referto4-1� Preparationonpage8.)
2)Openupthesensorsecuringplate.(SeeFig� 1)
3)Removethefrontmetalplateelectricalwiringboxcover(4tabs).(SeeFig� 1)
4)Removeconnectors 123.(SeeFig� 2andFig� 3)
5)Afterremovingthegroundwires(2screws),removetheelectricalwiringbox(1screw).(SeeFig� 4)
6)Removethethermistor.(SeeFig� 5)
7)Removethesidemetalplateelectricalwiringboxcover(7tabs).(SeeFig� 1)
8)Cutoffthepinsusinganipper.(SeeFig� 1)
9)WireandconnecttheHAconnectioncordtotheS21connector.(SeeFig� 1)
10)
InstallthesidemetalplateelectricalwiringboxcoverwhilebeingcarefulnottopinchtheHAconnectioncordorgroundwires(7tabs).
11)Attachthethermistor.
12)Installthegroundwires(2screws)andtheelectricalwiringbox(1screw).
13)Installtheconnectors 12andguidethecordasshowninthegure.(SeeFig� 2)
14)Installconnector 3andguidethecordasshowninthegure.(SeeFig� 3)
15)Attachthefrontmetalplateelectricalwiringboxcover(4tabs),andclosethesensorsecuringplate.
16)Attachthefrontpanelandthefrontgrilleastheywere.
S21
Sensor securing plate
Front metal plate electrical
wiring box cover
Side metal plate electrical
wiring box cover Cut off the pins using a nipper.
Be careful not to pinch the HA connection cord or ground wire.
Fig� 1
Connector 1
Connector 2Connector 3
Fig� 2 Fig� 3
Screws
Ground wires
Thermistor
Fig� 4 Fig� 5
English
01_EN_3P379970-3.indd 16 10/29/2014 11:23:48 AM
17 English
Indoor Unit Installation
12� How to set the different addresses
• When2indoorunitsareinstalledinoneroom,the2wirelessremotecontrollerscanbesetfordifferentaddresses.
Changetheaddresssettingofoneofthetwounits.
Whencuttingthejumperbecarefulnottodamageanyofthesurroundingparts.
1)Removetheelectricalwiringbox.(Referto11� When connecting to an HA system”onpage16steps1)-7).)
2)Cuttheaddressjumper(JA)ontheprintedcircuitboard.
3)Cuttheaddressjumper(J4)intheremotecontroller.
4)
Attachtheelectricalwiringboxastheywere.(Referto11� When connecting to an HA system”onpage16steps10)-15).)
5)Attachthefrontpanelandthefrontgrilleastheywere.
Jumper
(J8) (J4)
J4
ADRESS
EXIST
1
CUT 2
JA
ADRESS
EXIST
1
CUT 2
JA
Front metal plate cover
Side metal plate cover
Sensor
securing plate
01_EN_3P379970-3.indd 17 10/29/2014 11:23:49 AM
18English
Trial Operation and Testing
1 Trial operation and testing
• TrialoperationshouldbecarriedoutineitherCOOLorHEAToperation.
1-1� Measure the supply voltage and make sure that it is within the specied range.
1-2� In COOL operation, select the lowest programmable temperature;
in HEAT operation, select the highest programmable temperature�
1-3� Carry out the trial operation in accordance with the operation manual to ensure
that all functions and parts, such as ap movement, are working properly.
• Forprotection,thesystemdisablesrestartoperationfor3minutesafteritisturnedoff.
1-4� After trial operation is complete, set the temperature to a normal level (78°F
to 82°F (26°C to 28°C) in COOL operation, 68°F to 75°F (20°C to 24°C) in HEAT
operation)�
• WhenoperatingtheairconditionerinCOOLoperationinwinter,orHEAToperationinsummer,setittothetrialoperation
modeusingthefollowingmethod.
1)Press toturnonthesystem.
2)Pressbothof and atthesametime.
3)Press ,thenselect“ ”,andpress forconrmation.
• Trialoperationwillstopautomaticallyafterabout30minutes.
Tostoptheoperation,press .
• Someofthefunctionscannotbeusedinthetrialoperationmode.
• Theairconditionerdrawsasmallamountofpowerinitsstandbymode.Ifthesystemisnottobeusedforsometimeafter
installation,shutoffthecircuitbreakertoeliminateunnecessarypowerconsumption.
• Ifthecircuitbreakertripstoshutoffthepowertotheairconditioner,thesystemwillrestoretheoriginaloperationmode
whenthecircuitbreakerisopenedagain.
2 Test items
TestItems Symptom Check
Indoorandoutdoorunitsareinstalledproperlyonsolidbases. Fall,vibration,noise
Norefrigerantgasleaks. Incompletecooling/heatingfunction
Refrigerantgasandliquidpipesandindoordrainhoseextensionare
thermallyinsulated. Waterleakage
Draininglineisproperlyinstalled. Waterleakage
Systemisproperlygrounded. Electricalleakage
Thespeciedwiresareusedforinter-unitwiringconnections. Nooperationorburndamage
Indoororoutdoorunit’sairinletorairoutletareunobstructed. Incompletecooling/heatingfunction
Stopvalvesareopened. Incompletecooling/heatingfunction
Indoorunitproperlyreceivesremotecontrolcommands. Nooperation
willbedisplayedwhentheMODEbuttonispressed.* Noheating
*Checkthatthejumper(J8)hasnotbeencut.Ifithasbeencut,contact
theserviceshop. Jumper (J8)
English
01_EN_3P379970-3.indd 18 10/29/2014 11:23:52 AM
1
Français
Considérations sur la sécurité
• LisezattentivementcesConsidérations sur la sécurité
pourassureruneinstallationcorrecte.
• Cemanuelclasselesprécautionsdelamanièresuivante,
DANGER,AVERTISSEMENTetATTENTION.
Assurez-vousdesuivretouteslesprécautionsci-dessous:
ellessonttoutesessentiellespourassurerlasécurité.
DANGER ����������� Indiqueunesituationextrêmement
dangereusequi,siellen'estpas
évitée,entraîneralamortoudes
blessuresgraves.
AVERTISSEMENT
��� Lenon-respectdel'unedes
précautionsAVERTISSEMENT
estsusceptibled'entraînerdes
conséquencesaussidramatiques
quelamortoudegravesblessures.
ATTENTION ������ Lenon-respectdel'unedes
précautionsATTENTIONpeut,dans
certainscas,entraînerdegraves
conséquences.
•
Aprèsavoirterminél'installation,testezl'unitépourvérier
qu'iln'yapasd'erreurdansl'installation.Donnezàl'utilisateur
lesinstructionsadéquatesconcernantl'utilisationetle
nettoyagedel'unitéconformémentaumanueld'utilisation.
DANGER
• Legazréfrigérantestpluslourdquel'airetremplace
l'oxygène.Unefuiteimportantepeutconduireàun
appauvrissementenoxygène,enparticulierensous-sol,
etunrisqued'asphyxiepeutsurveniretentraînerdes
blessuresgravesoulamort.
•
Sivousconstatezdesfuitesdegazréfrigérantpendant
l'installation,aérezimmédiatementlazone.
Legazréfrigérantpeutproduireungaztoxiques'ilentreen
contactavecuneammecommeàpartird'unventilateur
dechauffage,unecuisinièreouunappareildecuisson.
L'expositionàcegazpeutprovoquerdesblessuresgraves
oulamort.
•
Aprèsl'achèvementdestravauxd'installation,vériezque
legazréfrigérantnefuitpas.
Legazréfrigérantpeutproduireungaztoxiques'ilentreen
contactavecuneammecommeàpartird'unventilateur
dechauffage,unecuisinièreouunappareildecuisson.
L'expositionàcegazpeutprovoquerdesblessuresgraves
oulamort.
• Nereliezpaslesunitésàdesconduitesd'eau,àdes
câblestéléphoniquesouàdesparatonnerres,carune
miseàlaterreincomplètepeutprovoquerunrisque
d'électrocutionimportantpouvantentraînerdesblessures
gravesoulamort;nelesreliezpasnonplusàdestuyaux
degazcarunefuitedegazpeutprovoqueruneexplosion
etentraînerdesblessuresgravesoulamort.
• Mettezprudemmentaurebutlesmatériauxd'emballage.
Lesmatériauxd'emballage,telsquelesclousetautres
piècesenmétalouenbois,peuventcauserdescoupures
oud'autresblessures.
Déchirezetjetezlessacsd'emballageenplastiquepour
quelesenfantsnepuissentpasjoueravec.
Lesenfantsquijouentavecdessacsenplastiquerisquent
demourirparsuffocation.
• N'installezpasuneunitédansunendroitoùdes
matériauxinammablessontprésentsenraisondurisque
d'explosionpouvantentraînerdesblessuresgravesoula
mort.
•
Nereliezpaslesunitésàdescâblestéléphoniquesouà
desparatonnerrescardeséclairspeuventprovoquerun
risqued'électrocutionimportantpouvantentraînerdes
blessuresgravesoulamort;nelesreliezpasnonplusà
destuyauxdegazcarunefuitedegazpeutprovoquerune
explosionetentraînerdesblessuresgravesoulamort.
Sommaire
Considérations sur la sécurité ���������������������� 1
Accessoires ����������������������������������������������������� 3
Choix du site de l’installation ������������������������ 3
1. Unitéintérieure.....................................................3
2. Télécommandesansl.........................................3
Schémas d'installation de l’unité intérieure ���
4
Installation de l'unité intérieure ��������������������� 5
1. Tuyauteriederéfrigérant.......................................5
2. Perçaged'untroudanslemuretinstallationdu
tuyauencastrédanslemur..................................7
3. Tuyaud’évacuation...............................................7
4. Installationdel’unitéintérieure.............................8
4-1. Préparation...................................................8
4-2. Installation.....................................................9
5. Évasementdel'extrémitédutuyau.......................12
6. Connexiondutuyauderéfrigérant.......................12
6-1.
Attentionàlamanipulationdelatuyauterie
...13
6-2. Sélectiondesmatériauxd'isolationthermique
etencuivre...................................................13
7. Vériezqu'iln'yapasdefuitedegaz...................14
8. Fixationdutuyauderaccordement......................14
9. Connexiondutuyaud’évacuation.........................14
10. Câblage................................................................15
11. LorsdelaconnexionàunsystèmeHA................1 6
12. Commentdénirlesdifférentesadresses............17
Fonctionnement d’essai et test ��������������������� 18
1. Fonctionnementd’essaiettest.............................18
2. Élémentstestés....................................................18
02_FR_3P379970-3.indd 1 10/29/2014 11:52:26 AM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56

Daikin FVXS09NVJU Installation guide

Category
Split-system air conditioners
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI