AD71S2SM1FA

Haier AD71S2SM1FA User manual

  • Hello! I am an AI chatbot trained to assist you with the Haier AD71S2SM1FA User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
SYJS-07-2018 REV.A Edition: 2018-07
R32 Super Match
II
Multi Split
CONTENTS
Part 1 General Information .......................................................................................................................................1
1. Lineup ...................................................................................................................................................................... 1
2. Feature ....................................................................................................................................................................3
Part 2 Indoor Units-4-Way Cassette Type................................................................................................................5
1. Feature ....................................................................................................................................................................6
2. Specication ............................................................................................................................................................8
3. Dimension..............................................................................................................................................................12
4. Wiring Diagram ...................................................................................................................................................... 14
5. Air Velocity and Temperature Distribution ..............................................................................................................17
6. Sound Pressure level ............................................................................................................................................19
7. Installation .............................................................................................................................................................21
Part 3 Indoor Units -Low Pressure Slim Duct Type .............................................................................................. 33
1. Feature ..................................................................................................................................................................34
2. Specication ..........................................................................................................................................................36
3. Dimension..............................................................................................................................................................44
4. Wiring Diagram ...................................................................................................................................................... 45
5. Airow and Static Pressure Chart .......................................................................................................................... 46
6. Installation .............................................................................................................................................................48
Part 4 Indoor Units -Medium Pressure Slim Duct Type .......................................................................................59
1. Specication ..........................................................................................................................................................60
2. Dimension..............................................................................................................................................................71
3. Wiring Diagram ...................................................................................................................................................... 76
4. Airow and Static Pressure Chart .......................................................................................................................... 80
5. Instalaltion .............................................................................................................................................................85
Part 5 Outdoor Units .............................................................................................................................................105
1. Feature ................................................................................................................................................................106
2. Dimension............................................................................................................................................................117
3. Wiring Diagram .................................................................................................................................................... 121
4. Wiring Connection ...............................................................................................................................................124
5. Piping Diagram ....................................................................................................................................................127
6. Limitation Values on Pipe lnstallation ..................................................................................................................131
7. Combination and the Data ................................................................................................................................... 134
8. Performance Curve .............................................................................................................................................160
9. Sound Pressure level ..........................................................................................................................................163
10. Installation Instructions ......................................................................................................................................167
Part 6 Electric Control and Troubleshooting ......................................................................................................195
1. Indoor PCB Photo................................................................................................................................................196
2. Outdoor unit PCB Photo, Dip Switch Setting and Function .................................................................................206
3. Diagnostic Code ..................................................................................................................................................223
4. Trouble Shooting .................................................................................................................................................233
1
Part 1 General Information
1. Lineup ...................................................................................................................................................................... 1
2. Feature ....................................................................................................................................................................2
1
Model Apperance
Indoor Unit
4-Way Cassette
AB25S2SC1FA
AB35S2SC1FA
AB50S2SC1FA
AB71S2SG1FA
Low ESP Duct
AD25S2SS1FA
AD35S2SS1FA
AD25S2SS2FA
AD35S2SS2FA
AD50S1SS2FA
AD50S2SS2FA
AD71S2SS1FA
AD71S2SS2FA
Model Apperance
Outdoor Unit
1U71S2SG1FA
3U55S2SR2FA
3U70S2SR2FA
4U75S2SR2FA
4U85S2SR2FA
5U105S2SS2FA
1. Lineup
2
Model Apperance
Indoor Unit Medium Pressure Duct
AD35S2SM3FA
AD50S2SM1FA
AD71S2SM1FA
AD71S2SM3FA
AD90S2SM3FA
AD105S2SM3FA
AD125S2SM3FA
AD140S2SM3FA
3
2. Feature
Clean Design
High Comfort
High Efciency
The outdoor unit takes no screw clean design in the top cover, this design makes people comfort when they are
watching the outdoor unit;
New outdoor unit and indoor unit design to get a ultra high SEER/SCOP A+++/A++ which is reaching the world
class energy efciency (3U55)
The new outdoor unit takes 550mm diameter large fan design, multi split II outdoor unit can provide same air ow
but with lower fan rotation speed, then the sound level reduce 3-4 dB(A) comapred with rst generation multi split
outdoor unit;
550mm
4
Installation Friendly
External General Stop Valve
Easy Start Up & Maintenance
The outdoor unit takes external general stop valve in all outdoor unit design, installer can vaccum/charge just one
time with no extra dismantlement, save lots of time;
In start up & maintenance, PC monitor can connect with outdoor unit by TD-02, read all indoor unit & outdoor
unit running parameter, also with the function to show parameter & curve.
When malfunction happens, show failure code.
General
stop valve
5
Part 2 Indoor Units-4-Way Cassette Type
1. Feature ....................................................................................................................................................................6
2. Specication ............................................................................................................................................................8
3. Dimension..............................................................................................................................................................12
4. Wiring Diagram ...................................................................................................................................................... 14
5. Air Velocity and Temperature Distribution ..............................................................................................................17
6. Sound Pressure level ............................................................................................................................................19
7. Installation .............................................................................................................................................................21
6
1. Feature
Appearance
Energy Efciency
DC Fan Motor
"Spiral" panel
The new 620mm*620mm panel is very t for thestandard decoration panel, won't cover otherthings like light, looks
more beautiful;
Compared to conventional AC fan motor, DC fan motor is more efciency.
AC Motor Effciency DC Motor Effciency
“Spiral” concept, “Haier” image;
The new 620mm*620mm panel
20
0
2004 00 6008 00 1000
40
60
80
100
45%
35%
25%
20
0
2004 00 6008 00 1000
40
60
80
100
90%
87.5%
85%
Torque(kgfcm)
Rev(r/min) Rev(r/min)
Torque(kgfcm)
7
Four aps can be controlled individually, airow can be controlled according to end user needs. Increase comfort;
Individual Flap Control
Comfort
Installation Friendly
Easy Access Electrical Box Design
The electrical box is located in the unit, you can just make maintenance by openning the panel .
Horizontal
Adjustable
Downward
corner installation solution
Fixed
8
2. Specication
Item Model AB25S2SC1FA
Function —— Cooling Heating
Capacity W 2600 3200
Sensible heat ratio W 0.71 /
Dehumidifying capacity 10-³xm³/h 1.0
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*1
Speed(H-M-L) r/min 690/620/560/500
Fan motor output/input power W 10/15
Air-ows (H-M-L) m³/h 620/520/450/350
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 1
Total area 0.272
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 570*570*260
Package mmxmmxmm 718*680*380
Drainage pipe (Material,I.D/O.D) mm PVC 26/32
Control type(Remote/Wired) Remote YR-HBS01(O) or Wired YR-E17(O)
Fresh air hole dimension mm 95
Electricity Heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 52
Sound pressure level dB(A) 36/33/30/27
Weight(Net/Shipping) kg/kg 17/20
Panel
Panel model(Color) PB-700IB(White)
Dimension
External(L*W*H) mmxmmxmm 700*700*60
Package(L*W*H) mmxmmxmm 740*750*115
Weight(Net/Shipping) kg/kg 2.8/4.8
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.
9
Item Model AB35S2SC1FA
Function —— Cooling Heating
Capacity W 3500 4000
Sensible heat ratio W 0.71 /
Dehumidifying capacity 10-³xm³/h 1.5
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*1
Speed(H-M-L) r/min 690/620/560/500
Fan motor output/input power W 10/15
Air-ows (H-M-L) m³/h 620/520/450/350
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 2
Total area 0.544
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 570*570*260
Package mmxmmxmm 718*680*380
Drainage pipe (Material,I.D/O.D) mm PVC 26/32
Control type(Remote/Wired) Remote YR-HBS01(O) or Wired YR-E17(O)
Fresh air hole dimension mm 95
Electricity Heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 52
Sound pressure level dB(A) 36/33/30/27
Weight(Net/Shipping) kg/kg 18.5/22
Panel
Panel model(Color) PB-700IB(White)
Dimension
External(L*W*H) mmxmmxmm 700*700*60
Package(L*W*H) mmxmmxmm 740*750*115
Weight(Net/Shipping) kg/kg 2.8/4.8
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.
10
Item Model AB50S2SC1FA
Function —— Cooling Heating
Capacity W 5000 5500
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 2.2
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Axial Fiow*1
Speed (H-M-L) r/min 800/700/600
Fan Motor Output/Input
Power
W 33/50
Air-Flows (H-M-L) m³/h 700/620/500
External Static Pressure pa 0
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/
7.0
Row —— 2
Total Area 1.25
Dimension
(LxWxH)
External mmxmmxmm 570x570x260
Package mmxmmxmm 718x680x380
Drainage Pipe (Material, I.D/O.D) mm PVC 27/31
Control Type (Remote/Wired) Remote YR-HBS01
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise Level
(H-M-L)
Sound Power Level dB (A) 55
Sound Pressure Level dB (A) 42/37/35
Weight (Net/Shipping) kg/kg 18.5/22
Panel
(Optional)
Panel Model (Color) PB-700KB
Dimension
External (L*W*H) mmxmmxmm 700/700/60
Package (L*W*H) mmxmmxmm 740/750/115
Weight (Net/Shipping) kg/kg 2.8/4.8
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35 (1/4)
Gas mm Φ12.7 (1/2)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27
DB/19
WB, indoor temperature (Heating): 20
DB
Outdoor temperature (Cooling): 35
DB/24
WB, outdoor temperature (Heating): 7
DB/6
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter.
11
Item Model AB71S2SG1FA
Function —— Cooling Heating
Capacity W 7100 8000
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.0
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed (H-M-L) r/min 650/600/550/500
Fan Motor Output/Input
Power
W 45/50
Air-Flows (H-M-L) m³/h 1260/1070/820/680
External Static Pressure pa 0
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/
7.0
Row —— 2
Total Area /
Temp.Scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 840*840*204
Package mmxmmxmm 990*990*310
Drainage Pipe (Material, I.D/O.D) mm PVC 26/32
Control Type (Remote/Wired) Remote YR-HBS01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise Level
(H-M-L)
Sound Power Level dB (A) 55
Sound Pressure Level dB (A) 36/33/29/26
Weight (Net/Shipping) kg/kg 27/32
Panel
(Optional)
Panel Model (Color) PB-950KB
Dimension
External (L*W*H) mmxmmxmm 950/950/50
Package (L*W*H) mmxmmxmm 1000/1000/110
Weight (Net/Shipping) kg/kg 6.5/9
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ9.52 (3/8)
Gas mm Φ15.88 (5/8)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27
DB/19
WB, indoor temperature (Heating): 20
DB
Outdoor temperature (Cooling): 35
DB/24
WB, outdoor temperature (Heating): 7
DB/6
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter.
12
3. Dimension
AB25S2SC1FA AB35S2SC1FA AB50S2SC1FA
13
840
840
840
80
5454
80 90
950
950
90 80
168
275
105
288
80
90
90
105
80
80
90
90
80
90
54 54
71
71
191
191
75
128
90 90
105
105
80
128
80
80 80
54 54
90
90
90
105
90
80
183
143
178
152
93
138
AB71S2SG1FA
14
4. Wiring Diagram
AB25S2SC1FA AB35S2SC1FA
TO OUT DOOR
0150523323
BM1-1
BM1-7
BM1-8
TYPE DEFINE
OFFOFF
BM1-2 BM1-3
BTU
B:BLACK
R:RED
W:WHITE
Y/G:YELLOW/GREEN
TEMP.
SENSOR
ROOM
SENSOR
FLOAT
SWITCH
HEATER
PUMP
UP/DOWN
CN9
CN1
CN6
PANNEL
CN4
CN11
CN19
CN13
CN3
ON
CN7
CN21
T5A/250VAC
FUSE
BM3
2
1
3
B
W
R
Y/G
OFF OFF OFF
ON OFF OFF
OFF ON OFF
ON ON OFF
OFF OFF ON
ON OFF ON
OFF ON ON
ON ON ON
9000
12000
18000
24000
28000
36000
48000
60000
NOTE1.DASHED PART ARE OPTIONAL.
2. USER SHOULD NOT TO SET BM1 AND BM3
CH1
OFF OFF
BM1-4
BM1-5
BM1-6
OFF
OFF
CN16
G
CN8
G
TEMP.
PIPING
DC FAN
ROOMCARD
U-HOME
WIRED
CONTROLLER
B
A
C
BA
C
REMOTE
CENTRAL
87654321
ON
BM1
OFF
87654321
N
OFF
Room card
available
unavailable
ON
AB25S2SC1FA
AB35S2SC1FA
Default
15
TO OUT DOOR UNIT
SW1-1
TYPE DEFINE
Cassette
Y/G:YELLOW/GREEN
RD:RED WHT:WHITE
BLK:BLACK
******************
.
SENSOR
CN1
CN11
CN19
SW3(BM3)
2
1
3
BLK
WHT
RD
OFF OFF ON
9.0
10.5
NOTE:
1.DASHED PARTS ARE OPTIONAL.
2.USER SHOULD NOT CHANGE THE
DIP SWITCH SW1 SW3 WITHOUT GUIDENCE
3.SW3-5->SW3-8 ARE USED FOR WIRED CONTROLLER
ADRESS SELECT. SW3-1->SW3-4 ARE RESERVED.
CH1
OFF
OFF
TEMP
.
PIPING
DC FAN MOTOR
BA
C
87654321
SW1(BM1)
87654321
N
(SLIM)
Room card
available
ON
Y/G
0150527035
L
WiFi
MODULE
B
A
C
WIRED
CONTROLLER
M
SENSOR
TEMP.
ROOM
ROOM CARD
CN3
CN6
T5A 250VAC
CN16
DRAIN
PUMP
M
CN9
CN10
CN4
FUSE
FLOAT
SWITCH
CN13
INDOOR UNIT
MAIN CONTROL
BOARD
I.R .RECEIVER :
INFRARED REMOTE
RECEIVER .
TEMP.:TEMPERATURE
ON
OFF
ON
62NC
A
B
M
FRESH AIR MOTOR /
EXTERNAL ALARM OUTPUT
(FUNCTION IN FUTURE )
( Contact rating_230VAC,3A)
CAPACITY
(KW)
SW1-2
SW1-3
OFF ON
ON
OFF
ON
ON
12.5
ON
ON
ON
14.0
SW1-4
unavailable
OFF
ON
SW1-5
COOL HEAT
COOL ONLY
HEAT PUMP
SW1-6
SW1-7
SW1-8
OFF
OFF
ON
INDOOR UNIT
TERMINAL BLOCK
CN8
7.1
ON
ON
OFF
ELECTRIC HEATING TERMINAL
RATING_230VAC,3A
CONNECT TO THIRD PARTY RELAY
CN15
ELECTRIC HEATING
THERMOSTAT / FUSE
(INSIDE PANEL,
WITHOUT
DIGITAL
DISPALY)
INFRARED
REMOTE
RECEIVER
CN21
5.0
ON
OFF
OFF
ON
OFF
OFF
3.5
AB50S2SC1FA
16
TO OUT DOOR UNIT
SW1-1
TYPE DEFINE
Cassette
Y/G:YELLOW/GREEN
RD:RED WHT:WHITE
BLK:BLACK
******************
.
SENSOR
CN1
CN11
CN19
SW3(BM3)
2
1
3
BLK
WHT
RD
OFF OFF ON
9.0
10.5
NOTE:
1.DASHED PARTS ARE OPTIONAL.
2.USER SHOULD NOT CHANGE THE
DIP SWITCH SW1 SW3 WITHOUT GUIDENCE
3.SW3-5->SW3-8 ARE USED FOR WIRED CONTROLLER
ADRESS SELECT. SW3-1->SW3-4 ARE RESERVED.
CH1
OFF
OFF
TEMP
.
PIPING
DC FAN MOTOR
BA
C
87654321
SW1(BM1)
87654321
N
(SLIM)
Room card
available
ON
Y/G
0150527033
L
I.R .RECEIVER
(WITH DIGITAL
DISPLAY)
WiFi
MODULE
.
B
A
C
WIRED
CONTROLLER
M
SENSOR
TEMP
.
ROOM
ROOM CARD
CN3
CN6
T5A 250VAC
CN16
DRAIN
PUMP
M
CN9
CN10
CN4
CN14
FUSE
FLOAT
SWITCH
CN13
CN4
CN3
CN2
CN7
CN1
CN6
INTELLIGENT
MOVE EYE DEVICE
M
M
LOUVER
STEP MOTOR4
LOUVER
STEP MOTOR3
M
M
LOUVER STEP
MOTOR2
LOUVER STEP
MOTOR1
INDOOR UNIT
MAIN CONTROL
BOARD
I.R .RECEIVER :
INFRARED REMOTE
RECEIVER .
TEMP.: TEMPERATURE
ON
OFF
ON
62NC
A
B
M
FRESH AIR MOTOR /
EXTERNAL ALARM OUTPUT
(FUNCTION IN FUTURE )
( Contact rating_230VAC,3A)
CAPACITY
(KW)
SW1-2
SW1-3
OFF ON
ON
OFF
ON
ON
12.5
ON
ON
ON
14.0
SW1-4
unavailable
OFF
ON
SW1-5
COOL HEAT
COOL ONLY
HEAT PUMP
SW1-6
SW1-7
SW1-8
OFF
OFF
ON
INDOOR UNIT
TERMINAL BLOCK
CN8
7.1
ON
ON
OFF
ELECTRIC HEATING TERMINAL
RATING_230VAC,3A
CONNECT TO THIRD PARTY RELAY
CN15
ELECTRIC HEATING
THERMOSTAT / FUSE
AB71S2SG1FA
17
5. Air Velocity and Temperature Distribution
2m2m
1m
1m
4m
3m
3m
4m
0m
1.5m/s
1.5m/s
1.0m/s
1.0m/s
0.5m/s
2.7m
2m
1m
0m
0.5m/s
a. Cooling / air velocity distribution
Cooling
Blowy angle: 40
Air velocity distribution
b. Cooling / temperature distribution
Cooling
Blowy angle:4 0
Temperature distribution
2.7m
27
25
22
27
25
22
4m
3m
2m2m
1m
1m
3m
4m
0m
2m
1m
0m
AB25S2SC1FA AB35S2SC1FA AB50S2SC1FA AB71S2SG1FA
/