Asco Series PV MXX Solenoid Owner's manual

Type
Owner's manual
r
q
GB
www.asco.com
DRAWING DESSIN ZEICHNUNG
DISEGNO TEKENING
DRAWING DESSIN ZEICHNUNG
DISEGNO TEKENING
GB DESCRIPTION
FR DESCRIPTION
DE BESCHREIBUNG
IT DESCRIZIONE
NL BESCHRIJVING
Modied on 19-06-2017
123620-331 Rev C ECN 275291
Page 1 of 6
1
4
5
2/2 PUSH TYPE
2/2 PULL TYPE
A
3/2 PULL TYPE
6
7
2
3
B
R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Encapsulated solenoid operator PV - MXX (Global Codication Insertion A7)
GENERAL
This installation and maintenance
instruction sheet of the solenoid is a
general supplement to the particular I&M
sheet for the valve. The identication is
made by prex PV to the catalogue number
(A7 insertion for the Global Codcation).
Always use both I&M sheets for installing
and maintaining the solenoid valve.
DESCRIPTION
The solenoid valves are designed in
accordance with Annex II of the European
Directive 2014/34/EU and IECEx Scheme:
IECEx 02. EC type examination certicate
BASATEX2168X and IECEx certificate
IECExSIR06.0109X are in compliance with
International and European standards:
ATEX IECEx
EN 13463-1
EN 60079-0 IEC 60079-0
EN 60079-18 IEC 60079-18
Classication:
II 2G Ex mb IIC Gb
II 2D Ex mb IIIC Db IP 67
INSTALLATION
ASCO components are intended to be used
only within the technical characteristics as
specied on the nameplate. Changes to the
equipment are only allowed after consulting
the manufacturer or its representative.
These solenoid valves are intended
for installation in potentially explosive
atmospheres, Group II gases, vapors,
mists or dusts (Group G/D, category 2). The
surface temperature classication depends
on wattage and ambient temperature which
are stated on the nameplate.
ELECTRICAL INSTALLATION
Wiring must comply with local and national
regulations of explosion proof equipment.
The electrical connection is made via a
2 or 3 core cable. The 3 core cable is
provided with a green/yellow coloured lead,
the internal ground wire. The cable of the
solenoid must be static at -40°C and may
be exed above -8°C. The solenoid shall
be connected to a supply, protected by
fuse capable of extinguishing a prospective
short current.
GROUNDING
To minimise the possibility of personal or
property damage, ensure that grounding of
the coils is maintained through the life of the
valve. The washer, spring (item 5) provides
reliable connection between the coil and
the sol.base sub-assembly if correctly
maintained.
CAUTION
Electrical load must be within the range
stated on the nameplate (max. 1.1 times
rated voltage). Failure to stay within the
electrical range of the coil rating results in
damage to or premature failure of the coil.
It will also invalidate the approval.
SERVICE
To prevent the possibility of personal or
property damage, do not touch the solenoid.
It can become hot under normal operation
conditions. If the solenoid valve is easily
accessible, the installer must provide
protection preventing accidental contact.
To prevent electrostatic hazard, clean coil
surface only with a damp cloth. Do not use
solvents.
MAINTENANCE
Maintenance depends on service conditions.
Periodic cleaning is recommended, the
timing of which will depend on the media
and service conditions. During servicing,
components should be examined for
excessive wear. A complete set of internal
parts is available as a spare parts kit.
If a problem occurs during installation/
maintenance or in case of doubt please
contact ASCO or authorized representative.
CAUTION: Before servicing the solenoid
valve, turn off electrical power, depressurize
valve and vent uid to a safe area. Solenoid
must be fully reassembled to complete the
magnetic circuit. In case of any replacement
of parts by the user, the traceability of the
final product can not be guaranteed by
ASCO. Wrong assembly will invalidate the
approval.
PETROL VENDING APPLICATIONS
These solenoid valves are particularly suited
for use in zone 1 Petrol Vending Applications
and meet the relevant requirements of
EN 13617-1.In addition, they fulfill the
requirements of PAS022:1997 clause 4.8
Annex 1 for vapour recovery systems. When
used as a part of a vapour recovery system
special attention should be taken to ensure
that there is no external leakage of the valve
accordingly to this standard and all seals
must be replaced during maintenance.
For additional information visit our
website: www.asco.com
1. Clip, retaining
2. Adapter
3. Spacer
4. Coil
5. Washer, spring
6. O-ring, plugnut
7. Sol. base sub-assembly
1. Clip de maintien
2. Adaptateur
3. Bague d'espacement
4. Bobine
5. Rondelle élastique, ressort
6. Joint torique, culasse
7. Sous-ensemble de la base
du sol.
1. Klammerhalterung
2. Zwischenstück
3. Distanzstück
4. Magnetspule
5. Federscheibe
6. Dichtungsring, Gegenanker
7. Haltemutter
1. Clip di ssaggio
2. Adattatore
3. Distanziatore
4. Bobina
5. Rondella, molla
6. Anello di ritenuta, nucleo sso
7. Gruppo cannotto solenoide
1. Bevestigingsclip
2. Adapter
3. Opvulring
4. Spoel
5. Veerring
6. O-ring, vaste kern
7. Kopstuk/deksel-combinatie
2/2 PULL TYPE
TYPE EXTRACTION 2/2
2/2-ZUGAUSFÜHRUNG
TIPO AD ESTRAZIONE 2/2
2/2 TREK
2/2 PROPORTIONAL TYPE
TYPE PROPORTIONNEL 2/2
2/2-PROPORTIONALAUSFÜHRUNG
TIPO PROPORZIONALE 2/2
2/2 PROPORTIONEEL
3/2 PULL TYPE
TYPE EXTRACTION 3/2
3/2-ZUGAUSFÜHRUNG
TIPO AD ESTRAZIONE 3/2
3/2 TREK
2/2 PUSH TYPE
TYPE POUSSOIR 2/2
2/2-DRUCKAUSFÜHRUNG
TIPO A PRESSIONE 2/2
2/2 DUW
3/2 PULL TYPE
TYPE EXTRACTION 3/2
3/2-ZUGAUSFÜHRUNG
TIPO AD ESTRAZIONE 3/2
3/2 TREK
2/2 PUSH TYPE
TYPE POUSSOIR 2/2
2/2-DRUCKAUSFÜHRUNG
TIPO A PRESSIONE 2/2
2/2 DUW
2/2 PULL TYPE
TYPE EXTRACTION 2/2
2/2-ZUGAUSFÜHRUNG
TIPO AD ESTRAZIONE 2/2
2/2 TREK
TORQUE CHART
A
B
20±3
9±1
175±25
77±10
ITEMS NEWTON.METRES INCH.POUNDS
SERIES PV - MXX
(Global Codication Insertion A7)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Asco Series PV MXX Solenoid Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI