AUMA SGMR Series Operation Instructions Manual

Type
Operation Instructions Manual

This manual is also suitable for

Control
Parallel
Profibus DP
Modbus
Part-turn actuators
SGM 04.1 SGM 12.1
SGMR 04.1 SGMR 12.1
with integral actuator controls
Assembly, operation, commissioningOperation instructions
Read operation instructions first.
Observe safety instructions.
These operation instructions are part of the product.
Retain operation instructions during product life.
Pass on instructions to any subsequent user or owner of the product.
Purpose of the document:
This document contains information for installation, commissioning, operation and maintenance staff. It is intended
to support device installation and commissioning.
Reference documents:
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
Table of contents Page
41. Safety instructions................................................................................................................. 41.1. Basic information on safety 41.2. Range of application 51.3. Warnings and notes 51.4. References and symbols
72. Identification........................................................................................................................... 72.1. Name plate 82.2. Short description
93. Transport, storage and packaging........................................................................................ 93.1. Transport 93.2. Storage 93.3. Packaging
104. Assembly................................................................................................................................ 104.1. Mounting position 104.2. Actuator: mount to valve 104.2.1. Actuator for assembly: prepare 104.2.2. Output drive for coupling 114.2.2.1. Mounting with coupling
135. Electrical connection............................................................................................................. 135.1. Basic information 145.2. Connection via bayonet connector 155.2.1. Cable connection 155.3. Earth connection, external
166. Indications.............................................................................................................................. 166.1. Mechanical position indicator/running indication 166.2. Indication lights
187. Signals..................................................................................................................................... 187.1. Output contacts (binary) 187.2. Analogue signals
198. Operation................................................................................................................................ 198.1. Manual operation
2
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Table of contents
198.2. Motor operation 198.2.1. Local actuator operation 208.2.2. Actuator operation from remote
229. Commissioning (basic settings of controls)....................................................................... 229.1. Cover to controls: open 229.2. Setting via hardware (switches) or via software 239.3. Type of seating: set 249.4. Torque switching: set 259.5. Operating time: set 279.6. Cover to controls: close
2810. Commissioning (basic settings at actuator)........................................................................ 2810.1. End stops in part-turn actuator 2910.1.1. End stop CLOSED: set 2910.1.2. End stop OPEN: set 3010.2. End position detection: verify setting 3010.3. End position detection: set again via local controls 3110.3.1. End position CLOSED: set again 3210.3.2. End position OPEN: set again 3210.4. Switch compartment: open 3310.5. Mechanical position indicator: set 3310.6. Switch compartment: close
3411. AUMA CDT software (accessories).......................................................................................
3512. Corrective action.................................................................................................................... 3512.1. Fault indications and warning indications 3612.2. Fuses 3612.2.1. Fuses within the actuator controls 3612.2.2. Motor protection (thermal monitoring)
3713. Servicing and maintenance................................................................................................... 3713.1. Preventive measures for servicing and safe operation 3713.2. Maintenance 3713.3. Disposal and recycling
3814. Technical data......................................................................................................................... 3814.1. Type range relevant data 3814.2. Features and functions of actuator 3914.3. Features and functions of actuator controls 4014.4. Service conditions 4014.5. Further information
4115. Spare parts............................................................................................................................. 4115.1. Part-turn actuators SGM 04.1 SGM 12.1/SGMR 04.1 SGMR 12.1
4316. Certificates.............................................................................................................................. 4316.1. Declaration of Incorporation and EC Declaration of Conformity
44Index........................................................................................................................................
46Addresses...............................................................................................................................
3
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1 Table of contents
1. Safety instructions
1.1. Basic information on safety
Standards/directives AUMA products are designed and manufactured in compliance with recognised
standards and directives.This is certified in a Declaration of Incorporation and an
EC Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Safety instructions/warn-
ings All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitably qualified personnel having been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation Prerequisites for safe and smooth operation:
Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
Only operate the device if it is in perfect condition while observing these instruc-
tions.
Immediately report any faults and damage and allow for corrective measures.
Observe recognised rules for occupational health and safety.
Observe the national regulations.
During operation, the housing warms up and surface temperatures > 60 °C may
occur.To prevent possible burns, we recommend checking the surface temper-
ature using an appropriate thermometer and wearing protective gloves, if re-
quired, prior to working on the device.
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2. Range of application
AUMA part-turn actuators are designed for the operation of valves, e.g. butterfly
valves and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:
Industrial trucks according to EN ISO 3691
Lifting appliances according to EN 14502
Passenger lifts according to DIN 15306 and 15309
Service lifts according to EN 81-1/A1
4
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Safety instructions
Escalators
Buried service
Continuous submersion (observe enclosure protection)
Potentially explosive atmospheres
Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3. Warnings and notes
The following warnings draw special attention to safety-relevant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning may result in minor or moderate injury. May also be used
with property damage.
Potentially hazardous situation. Failure to observe this warning may result in
property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
Measures to avoid the danger
Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.4. References and symbols
The following references and symbols are used in these instructions:
Information The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
5
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1 Safety instructions
< > Reference to other sections
Terms in brackets shown above refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may quickly be found.
6
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Safety instructions
2. Identification
2.1. Name plate
Figure 1: Arrangement of name plates
[1] Actuator name plate
[2] Additional plate, e.g. KKS plate (Power Plant Classification System)
Description of actuator name plate
Figure 2: Actuator name plate (example)
[1] Name of manufacturer
[2] Address of manufacturer
[3] Type designation (see explanation below)
[4] Commission number (see explanation below)
[5] Actuator serial number (see explanation below)
[6] Operating time
[7] Torque range
[8] Current type, mains voltage, mains frequency
[9] Electric power (motor)
[10] Wiring diagram number
[11] Control (see explanation below)
[12] Can be assigned as an option upon customer request
[13] Enclosure protection
[14] Type of lubricant
[15] Setting range of swing angle
[16] Permissible ambient temperature
[17] Rated current
[18] Type of duty
7
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1 Identification
Type designation Figure 3:Type designation (example)
1. Type and size of actuator
2. Flange size
Type and size These instructions apply to the following devices types and sizes:
Part-turn actuators for open-close duty: SGM 04.1, 05.1, 07.1, 10.1, 12.1
Part-turn actuators for modulating duty: SGMR 04.1, 05.1, 07.1, 10.1, 12.1
Commission number An order-relevant commission number (order number) is assigned to each device.
This commission number can be used to directly download the wiring diagram (in
German and English language), inspection records and further information regarding
the device from the Internet:http://www.auma.com. For some details, the customer
number might be required.
Actuator serial number Table 1: Description of serial number (with example)
N S 123451205
1st + 2nd position: Assembly in week
In our example:Week 0505
3rd + 4th position:Year of manufacture
In our example:Year of manufacture: 201212
All other positions Internal works number for unambiguous product identificationN S 12345
Control 24 V DC = Control via parallel interface at 24 V DC control voltage.
0/4 20 mA = Control via parallel interface via analogue input 0/4 20 mA.
2.2. Short description
Part-turn actuator Definition in compliance with EN ISO 5211:
A part-turn actuator is an actuator which transmits a torque to the valve for less than
one full revolution. It need not be capable of withstanding thrust.
AUMA part-turn actuators are driven by an electric motor. For control in motor
operation and for processing the actuator signals, controls are integrated within the
housing.The actuator can be operated easily on site via the local controls. A
handwheel or crank is provided for manual operation. Manual operation is possible
without change-over.
The swing angle is limited by internal end stops. Switching off in end positions may
be either by limit or torque seating.
AUMA CDT The AUMA CDT software (accessories) can be used to establish a connection to a
computer (PC, laptop or PDA). Among others, the software can be used to read in
and out data and to save and modify settings.
The connection between computer and the integral actuator controls is made using
a service cable.
8
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Identification
3. Transport, storage and packaging
3.1. Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Risk of death or serious injury.
Do NOT stand below hovering load.
Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
3.2. Storage
Danger of corrosion due to inappropriate storage!
Store in a well-ventilated, dry room.
Protect against floor dampness by storage on a shelf or on a wooden pallet.
Cover to protect against dust and dirt.
Apply suitable corrosion protection agent to uncoated surfaces.
Long-term storage If the device must be stored for a long period (more than 6 months) the following
points must be observed in addition:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
Plastic protective caps supplied when leaving the factory are for transport protection
only.They have to be replaced for long-term storage. (Heed protection type indicated
on name plate.)
3.3. Packaging
Our products are protected by special packaging for transport when leaving the
factory.The packaging consists of environmentally friendly materials which can easily
be separated and recycled.We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
9
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1 Transport, storage and packaging
4. Assembly
4.1. Mounting position
AUMA actuators can be operated without restriction in any mounting position.
4.2. Actuator: mount to valve
4.2.1. Actuator for assembly: prepare
Prior to mounting, both valve and actuator must be in the same end position!
For butterfly valves, the recommended mounting position is end position
CLOSED.
For ball valves, the recommended mounting position is end position OPEN.
In compliance with the order, the actuator is supplied either in position CLOSED or
position OPEN.The mechanical position indicator supplies information on the set
position.
If the actuator position was not modified and agrees with the valve position, the
actuator can be mounted in the supplied position.
In case the actuator is in an incorrect position:
1. Operate the actuator into the same position as the valve via push buttons OPEN,
STOP, CLOSE while in motor operation. For motor operation, please refer to
<Actuator operation at the local controls> chapter.
2. Should the electrical connection not be available at the time of assembly, the
actuator can be operated into the required end position using the handwheel.
2.1 Turn the handwheel or the crank handle until reaching the internal end
stop of part-turn actuator (same end position OPEN or CLOSED as valve).
2.2 Turn handwheel by approximately two turns (overrun) in the opposite dir-
ection.
After this procedure, the actuator can be mounted to the valve.
4.2.2. Output drive for coupling
Application For valves with output drive types according to EN ISO 5211
Capable of withstanding thrust
Assembly The actuator is mounted to the valve using a coupling placed onto the valve
shaft.
Unbored couplings must be adapted and machined to match the valve shaft
prior to mounting (e.g. with bore and keyway, two-flat or square bore)
10
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Assembly
Figure 4: Coupling variants
[1] Bore with keyway
[2] Square bore
[3] Bore with two-flats
[4] Valve shaft
[5] Output drive flange (size 12.1)
4.2.2.1. Mounting with coupling
Condition:Valve and actuator are in the same end position.
Figure 5: Coupling fitting dimensions
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Screw
Table 2: Coupling fitting dimensions
Z max [mm]Y max [mm]X max [mm]Type, size - output mounting flange 4062.5SGM/SGMR 04.1-F07 4062.5SGM/SGMR 05.1-F07 5062.5SGM/SGMR 07.1-F07 60103.5SGM/SGMR 10.1-F10 62105SGM/SGMR 12.1-F12
1. Thoroughly degrease mounting faces of output mounting flanges.
2. Apply a small quantity of grease to the valve shaft [2].
3. Place coupling [1] onto valve shaft [2] and secure against axial slipping by using
a grub screw [3], a circlip or a screw [4].Thereby, ensure that dimensions X, Y
or Z are observed (refer to figure and table <Coupling fitting dimensions>).
4. Apply non-acidic grease at splines of coupling.
5. Fit actuator.
Information: Ensure that the spigot (if provided) fits uniformly in the recess
and that the flanges are in complete contact.
11
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1 Assembly
6. If flange bores do not match thread:
6.1 Slightly rotate handwheel until bores line up.
6.2 If required, shift actuator position by one tooth on the coupling.
7. Fasten actuator with screws [4].
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
Fasten screws [4] crosswise with a torque according to table.
Table 3:Tightening torques for screws
Tightening torque TA [Nm]Screws
Threads Strength class 8.8
24M8 48M10
12
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Assembly
5. Electrical connection
5.1. Basic information
Danger due to incorrect electrical connection
Failure to observe this warning can result in death, serious injury, or property damage.
The electrical connection must be carried out exclusively by suitably qualified
personnel.
Prior to connection, observe basic information contained in this chapter.
After connection but prior to applying the voltage, observe the <Commissioning>
and <Test run> chapters.
Wiring diagram/terminal
plan The pertaining wiring diagram/terminal plan (in German and English language) is
attached to the device in a weather-proof bag, together with these operation
instructions. It can also be obtained from AUMA (state commission no., refer to name
plate) or downloaded directly from the Internet (www.auma.com).
Permissible networks
(supply networks) The actuators are suitable for use in TN and TT networks with directly earthed star
point. Use in IT networks is permitted while observing the respective <Protection on
site>.
Protection on site For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current value for respective sizing is derived from the current consumption of
the actuator (refer to electrical data sheet).
The actuators are suitable for use in current circuits with a maximum short-circuit
1-phase AC current value of 5,000 A root-mean-square (R.M.S).The output data of
the fuses to be provided on site must not exceed the following values: 15 A/250 V
at a maximum mains current of 5,000 A AC.
Use appropriate insulation monitors when working in power installations, for example
an insulation monitor measuring the pulse code.
We recommend refraining from using residual current devices (RCD). However, if
an RCD is used within the mains, the residual current device must be of type B.
Power supply for the
controls (electronics) In case of external supply of the controls (electronics):The external power supply
must have a reinforced insulation against the mains voltage in accordance with IEC
61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance
with IEC 61800-5-1.
Potential of customer
connections All input signals (control) must be supplied with the same potential.
All output signals (status signals) must be supplied with the same potential.
Safety standards All externally connected devices shall comply with the relevant safety standards.
All connected electric circuits shall comply with the requirements for protective
separation.
Cable installation in ac-
cordance with EMC Signal and bus cables are susceptible to interference.
Motor cables are interference sources.
Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
The interference immunity of signal and bus cables increases if the cables are
laid close to the earth potential.
If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
Avoid long parallel paths with cables being either susceptible to interference or
interference sources.
13
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1 Electrical connection
For the connection of remote position transmitters, screened cables must be
used.
Type of current, mains
voltage and mains fre-
quency
Type of current, mains voltage and mains frequency must match the data on the
motor name plate.
Figure 6: Name plate (example)
[1] Type of current
[2] Mains voltage
[3] Mains frequency (for 1-ph AC motors)
Connecting cables For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
The cross-sectional area of every protective earthing conductor which does not
form not part of the supply cable or the cable enclosure, shall, in any case, not
be less than:
- With mechanical protection: minimum 2.5 mm²
- Without mechanical protection: minimum 4 mm²
5.2. Connection via bayonet connector
Figure 7: Arrangement of connections
[XK1] Power terminals (mains cables)
[XK2] Control contacts
Cross sections:
Power terminals: max. 1.5 mm² flexible
Control contacts: max. 1.5 mm² flexible
Hazardous voltage at open connector (capacitor discharge)!
Risk of electric shock.
After disconnecting the power supply (removing connector for power terminals),
wait at least 5 seconds before touching the pins/sockets.
14
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Electrical connection
5.2.1. Cable connection
Observe permissible cross sections.
Use suitable crimping tools, such as Cannon four indent crimp tool.
For connecting cables, AUMA offer a suitable plug and socket assembly (AUMA
article number Z049.356), consisting of a 5-pin power plug and one 19-pin signal
plug.
1. Connect cables according to order-related wiring diagram.
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
Connect all protective earth conductors.
Connect PE connection to external protective earth conductor of connecting
cables.
Start running the device only after having connected the protective earth con-
ductor.
2. Protective earth conductor according to wiring diagram, symbol: .
5.3. Earth connection, external
The housing is equipped with an external earth connection (U-bracket) to integrate
the device in equipotential earth bonding.
Figure 8: Ground connection
Earth connection (U-bracket), external
15
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1 Electrical connection
6. Indications
6.1. Mechanical position indicator/running indication
Mechanical position indicator:
Continuously indicates the valve position
(For a swing angle of 90°, the indicator disc [2] rotates by approximately 90°.)
Indicates whether the actuator is running (running indication)
Indicates that the end positions are reached (via indicator mark [3])
Figure 9: Mechanical position indicator
[1] Cover
[2] Indicator disc
[3] Mark
[4] Symbol for position OPEN
[5] Symbol for position CLOSED
6.2. Indication lights
Figure 10: Indication lights on local controls
[1] Indication light OPEN/warning/fault (green/yellow/red)
[2] Indication light CLOSE/LOCAL/set end position (yellow/blue)
Table 4: Indication light [1] (default setting)
DescriptionSignificationColour/state Actuator is in end position OPEN.OPENilluminated in
green Stroke between selected end positions (OPEN/CLOSED)
is below the preset minimum stroke (factory setting 60 %
of maximum rotation). Refer to <Corrective action>
chapter.
Warningblinking in yellow
The number of blinking signals indicates the number of
fault signal. Refer to <Corrective action> chapter.
Faultblinking in red
Table 5: Indication light [2] (default setting)
DescriptionSignificationColour/state Actuator is in end position CLOSED.CLOSEilluminated in yel-
low
16
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Indications
DescriptionSignificationColour/state Operation mode LOCAL is active.The actuator can be
operated via push buttons.
LOCALblinking in blue
(1 Hz) Setting mode for end position setting is active.Set end positionblinking in blue
(5 Hz)
17
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1 Indications
7. Signals
7.1. Output contacts (binary)
The integral controls are equipped with 4 semiconductor output contacts.
Rated power: 24 V DC, 1A
Switches: 1 NO (standard)
Default values:
Designation of output contact in AUMA CDT soft-
ware
Designation of output contacts in
wiring diagram
Signal DOUT 1 = End position CLOSED
K 1 = End position CLOSED
Signal DOUT 2 = End position OPEN
K 2 = End position OPEN
Signal DOUT 3 = Fault
K 3 = Fault
Signal DOUT 4 = Selector sw. REMOTE
K 4 = (Selector switch) REMOTE
7.2. Analogue signals
Option
Valve position Signal: E2 = 0/4 20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT1 (position)
18
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Signals
8. Operation
8.1. Manual operation
For purposes of setting and commissioning, in case of motor failure or power failure,
the actuator may be operated manually.
The handwheel does not rotate during motor operation. Change-over from motor
operation to manual operation is not required.
Figure 11: Manual operation
Handwheel versions:
[1] Crank handle with cylindrical grip (standard)
[2] Crank handle with conical grip
[3] Handwheel with five edge ring
[4] Handwheel with five ripple ring
1. Close valve:Turn crank handle/handwheel clockwise.
Drive shaft (valve) turns clockwise in direction CLOSE.
2. Open valve:Turn crank handle/handwheel counterclockwise.
Drive shaft (valve) turns counterclockwise in direction OPEN.
Information Turning the handwheel during motor operation extends or reduces the operating
time, depending on the direction of rotation.
8.2. Motor operation
Perform all commissioning settings and the test run prior to motor operation.
8.2.1. Local actuator operation
The actuator can be locally operated by means of push buttons.
19
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1 Operation
Figure 12: Local controls
[1] Push button OPEN
[2] Push button STOP - operation mode LOCAL/REMOTE
[3] Push button CLOSE
[4] Indication light for operation mode LOCAL (blue)
Hot surfaces, e.g. possibly caused by high ambient temperatures or strong
direct sunlight!
Danger of burns
Check surface temperature and wear protective gloves, if required.
Activate operation mode LOCAL:
Hold down push button [2] for approx. 3 seconds until the indication light [4] is
blinking in blue.
If the right indication light is blinking in blue, the actuator can be operated via
push buttons [1 3]:
- Run actuator in direction OPEN: Press push button OPEN [1].
- Stop actuator: Press push button STOP [2].
- Run actuator in direction CLOSE: Press push button CLOSE [3].
Information OPEN - CLOSE operation commands can be given either in push-to-run or in self-
retaining operation mode. In self-retaining mode, the actuator runs to the defined
end position after pressing the button, unless another command has been received
beforehand.
Push-to-run operation or self-retaining is set via the controls software. Refer to
<AUMA CDT software (accessories)> chapter. It is possible to temporarily (for one
operation command) activate self-retaining by means of the push buttons:
Press and hold down push buttons OPEN [1] or CLOSE [3] for more than 3
seconds.
During this procedure, self-retaining is not saved.The setting programmed within
the software is taken over for the subsequent operation command.
8.2.2. Actuator operation from remote
Operation mode Remote can be activated via local controls.
20
SGM 04.1 SGM 12.1 / SGMR 04.1 SGMR 12.1
Operation
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48