Monogram ZV855 Owner's manual

Category
Cooker hoods
Type
Owner's manual
Installation
Instructions
Island Vent Hood
ZV850, ZV855
Hotte Aspirante/lot
Instructions d'instollotion
Lo section frangaise commence 6 la page 22
Campanade ventilaci6n en isla
InstruccJones de JnstalacJ6n
La secci6n en espa6ol empieza en la p6gina 43
131-10725-1 I
GE 11/02/09
Safety Information
READ AND SAVE THESE INSTRUCTIONS
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT- Savetheseinstructionsfor
local inspector's use.
IM PORTANT- Observeallgoverningcodes
and ordinances.
Note to Installer - Be sure to leave these
instructions with the Consumer.
Note to Consumer - Keep these instructions
with your Owner's Manual for future reference.
Skill Level- Installation of this appliance requires
basic mechanical and electrical skills.
Completion Time - i to 3 Hours.
Proper installation isthe responsibility of the installer.
Product failure due to improper installation is not
covered under the warranty.
ForMonogram localserviceinyour area,call 1.800.444.1845.
For Monogram service in Canada, call 1.800.561.3344.
For Monogram Parts and Accessories, call 1.800.626.2002.
_CAUTION:
Due to the weight and size of these vent hoods and
to reduce the risk of personal injury or damage to the
product, TWO PEOPLE ARE REQUIRED FOR PROPER
INSTALLATION.
_WARNING:
To reduce the risk of fire or electrical shock, do not
use this range hood with any external solid-state speed
control device. Any such alteration from original factory
wiring could result in damage to the unit and/or create
an electrical safety hazard.
TOREDUCETHERISKOFFIRE,USEONLYMETALDUCTWORK.
-&WARNING:TOREDUCETHERISKOF
FIRE,ELECTRICALSHOCK OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended
by the manufacturer. If you have any questions,
contact the manufacturer.
8.
Before servicing or cleaning the unit, switch
the power off at the service panel and lock the
service disconnecting means to prevent the power
from being switched on accidentally. When the
service disconnecting means cannot be locked,
securely fasten a prominent warning device,
such as a tag, to the service panel.
-&CAUTION: FOR GENERAL VENTILATING
USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS
MATERIALS,EXPLOSIVEMATERIALSOR VAPORS.
-&WARNING:TOREDUCETHERISKOF
FIRE,ELECTRICALSHOCK OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
Installation work and electrical wiring must be done
by qualified person(s)in accordance with all applicable
codes and standards, including fire-rated construction.
Sufficient air is needed for proper combustion
and exhausting of gases through the flue (chimney)
of fuel burning equipment to prevent back-drafting.
Follow the heating equipment manufacturer's
guidelines and safety standards, such as those
published by the National Fire Protection Association
(NFPA),the American Society for Heating, Refrigeration
and Air Conditioning Engineers (ASHRAE)and the local
code authorities.
When cutting or drilling into walls or ceilings, do not
damage electrical wiring and other hidden utilities.
Ducted systems must always bevented
to the outdoors.
Local codes vary. Installation of electrical connections
and grounding must comply with applicable codes.
In the absence of local codes, the vent should be
installed in accordance with National Electrical Code
ANSI/NFPA70-3_990or latest edition.
-&CAUTION: TOreduce riskoffireandto
properlyexhaustair,be suretoductairoutside-donot
vent exhaust air into spaces within walls or ceilings or
into attics, crawl spaces or garages.
Design Information
CONTENTS
Design Information
Models Available ................................................................................3
Product Dimensions ..........................................................................3
Advance Planning
Ductwork Planning ..........................................................................4
Ceiling Framing for Adequate Support ..................................4
Installation Preparation
Duct Fittings ..........................................................................................5
Power Supply ......................................................................................6
Tools and Materials Required ......................................................6
Remove the Packaging ..................................................................7
Check Installation Hardware ......................................................7
Determine Installation Height ......................................................8
Install Ceiling Support Structure ........................................9-11
Installation Instructions
Installation - Vented to the Outside ..............................12-16
Step 1, Mount Template ..............................................................12
Step 2, Install Upper Support Frame ......................................12
Step 3, Install Lower Support Frame......................................12
Step 4, Secure Wiring ....................................................................13
Step 5,Sizeand Install Ductwork ............................................13
Step 6,Install Decorative Duct Covers..................................14
Step 7,Install Hood ........................................................................15
Step 8, Connect Electrical............................................................15
Step 9, Slide Duct Cover
Down, Install Side Utensil Rods................................................15
Step 10, Install Filters....................................................................16
Step 11, Finalize Installation ......................................................16
Installation Instructions
Installation - Redrculating ..................................................17-21
Step 1,Mount Template ..............................................................17
Step 2,Install Upper Support Frame......................................17
Step 3, Install Lower Support Frame......................................18
Step 4, Secure Wiring ....................................................................18
Step 5,Sizeand Install Ductwork ............................................18
Step 5,Install Decorative Duct Covers..................................19
Step 7,Install Hood ........................................................................20
Step 8, Connect Electrical............................................................20
Step 9, Slide Duct Cover
Down, Install Side Utensil Rods................................................20
Step 10, Install Filters....................................................................21
Step 11, Finalize Installation ........................................................
MODELS AVAILABLE
Model ZV850, 360 CFM
Model ZV855, 500 CFM
These hoods mag be installed to vent to the outdoors,
or theg mag be installed for recirculating operation.
All necessarg parts for recirculating operation are
supplied with the hood. No kits required.
Thesevent hoods can be installed over ang 30" or 36"
Monogram electric or gas cooktop except Monogram
Professional cooktops or ranges larger than 30".
Reversible duct covers accommodate recirculating
operation.
The telescopic duct covers conceal the ductwork
running from the top of the hood to the ceiling.
The supplied duct cover is sized to reach ceiling heights
over 8 feet. See the table on page 8.
PRODUCT DIMENSIONS AND CLEARANCES
The vent hood must be installed 24" minimum and
30" maximum above the cooking surface.
NOTE: Installation height should be measured from
the cooking surface to the lowest part of the hood.
*Height
to Ceiling
24" Minimum
30" Maximum
L 3S-3/8" (excluding utensil rods)
36-1/2" (including utensil rods) /2't
4
8-1/4"
II
i 36" Hinilrlum
Z×8510SPSS Duct Cover Accessory
This accessorg isavailable for installation with ceiling
heights of 8' 7" to over 10 feet. See the table on page 8.
The duct cover accessorg must be on-site with the
hood at the time of installation.
Advance Planning
DUCTWORK PLANNING
The hood is designed to be vented vertically
through the ceiling. Use locally supplied elbows
to vent horizontallg through the rear wall.
Determine the exact location of the vent hood.
Plan the route for venting exhaust to the outdoors.
Use the shortest and straightest duct route
possible. For satisfactorg performance, duct run
should not exceed 100' equivalent length for ang
duct configurations.
Refer to "Duct Fittings" chart to compute the
maximum permissible length for duct runs to
the outdoors.
Use rigid metal ductwork onlg.
ThroughThe Ceiling
Flat ..........
Standing
Vent Between
CeilingJoists
This vent hood must use 6" round duct. The
6" round duct can transition to 3-1/4" x 10"
or 3-1/4" x 12".
Install the house duct to run horizontallg between
ceiling joists or straight up through the roof.
Install a wall or roof cap with damper at the
exterior opening. Order the wall or roof cap
and ang transition and length of duct needed
in advance.
WA RNING: TOREDUCETHERISK
OF FIRE, USE ONLY RIGID METAL DUCTWORK.
CEILING FRAMING FOR ADEQUATE
SUPPORT
These vent hoods are heavg. Adequate structural
support must be provided. The ceiling structure
must be capable of supporting the weight of the
hood and ang inadvertent user contact loads
(approximatelg 200 pounds). The hood support
frame will be supported bg 2 x 4 minimum cross-
framing.
Installation will be easier if the vent hood is
installed before the cooktop or countertop below
is installed.
Accessory Duct Cover
A duct cover accessorg mag be required for gour
installation, depending on ceiling height.
4
Installation Preparation
DUCT FITTINGS
Use this chart to compute
maximum permissible lengths
for duct runs to outdoors.
NOTE: Do not exceed maximum
permissible equivalent lengths!
Maximum duct length:
100 foot for range hoods.
Flexible ducting:
If flexible metal ducting is used,
all the equivalent feet values in
the table should be doubled.
The flexible metal duct should
be straight and smooth and
extended us much us possible.
DO NOT use flexible plastic
ducting.
NOTE: Any home ventilation
system, such as a ventilation hood,
may interrupt the proper flow of
combustion air and exhaust
required by fireplaces, gas
furnaces, gas water heaters and
other naturally vented systems.
To minimize the chance of
interruption of such naturally
vented systems, follow the
heating equipment manufacturer's
guidelines and safety standards
such as those published by NFPA
and ASHRAE.
Duct Piece Dimensions
Round.
straight
3-1/4" x 10"
straight
90° elbow
Equivalent
Length*
1 ft. (per
foot length)
1 ft. (per
foot length)
12 ft.
Quantity
Used
45° elbow 7 ft.
3-1/4" x 10" 14 ft.
3-1/4" x 12" 10 ft.
90 ° elbow
3-1/4" x 10" 8 ft.
3-1/4" x 12" 6 ft.
45 ° elbow
---_ 3-1/4" x 10" 33 ft.
3-1/4" x 12" 24 ft.
90°flat elbow
6" round to 2 ft.
rectangular
_,, Rectangular to 8" 2 ft.
round
3-1/4" x 10" 4 ft.
3-1/4" x 12" 4 ft.
6" round to rectangular
transition 90° elbow
3-1/4" x 10" 4 ft.
3-1/4" x 12" 4 ft.
Rectangular to 6" round
transition 90° elbow
Round wall cap
with damper
24 ft.
3-1/4" x 10" 24 ft.
3-1/4" x &2" 18 ft.
Rectangular wall cap
with damper
<_ Round roof cap 33 ft.
*Actual length of straight duct plus duct fitting
equivalent. Equivalent length of duct pieces are
based on actual tests conducted by GE Evaluation
Engineering and reflect requirements for good
venting performance with any ventilation hood.
Total Duct Run,
Total
Equivalent
Length
Installation Preparation
POWER SUPPLY
IMPORTANT- (Please read carefully)
WARNING:
FOR PERSONAL SAFETY,THIS APPLIANCE MUST BE
PROPERLYGROUNDED.
Remove house fuse or open circuit breaker before
beginning installation.
Do not use an extension cord or adapter plug with
this appliance. Follow National Electrical Code or
prevailing local codes and ordinances.
Electrical supply
This vent hood must be supplied with 120V, 60Hz,
and connected to an individual, properlg grounded
branch circuit, and protected bg a 15- or 20-amp
circuit breaker or time-delag fuse.
Wiring must be 2-wire with ground.
If the electrical supplg does not meet the above
requirements, call a licensed electrician before
proceeding.
Route house wiring as close to the installation
location as possible. Route additional length from
ceiling joists to reach the junction box on the
hood.
Connect the wiring to the house wiring in
accordance with local codes.
Grounding instructions
The grounding conductor must be connected to a
ground metal, permanent wiring sgstem, or an
equipment-grounding terminal or lead on the hood.
A WARNING: The improper connection
of the equipment-grounding conductor can result
in a risk of electric shock. Check with a qualified
electrician or service representative if gou are in
doubt whether the appliance is properlg grounded.
TOOLS AND MATERIALS REQUIRED
(NOT SUPPLIED)
Pencilandtapemeasure
Safetyglasses
Spiritlevel
6loves
Hammer
Phillipsscrewdriver
at_
Flashlight
Utility knife
Electricdrill with 5/32" bits,
#2 Phillipsand7/16" socket
Stepladder
UL-listedwire nuts
10mmwrench
Metal snips
Pliers
Masking Wirecutter/stripper
tape
Sabersawor keyholesaw
Aluminized
ducttape Strainrelieffor
junctionbox
Plumb
6" roundmetal
duct,lengthtosuit
installation
120V,60Hz.15-or 20-Amp,
2-wirewith ground,properly
groundedbranchcircuit
Installation Preparation
REMOVE THE PACKAGING
CAUTION: Wear glovesto protect
againstsharp edges.
The vent hood ispacked withthe duct coverand
supportframes.
Remove the hood,portsand packaging.
Remove junctionbox cover.
Installstrainreliefonto junctionbox cover
(notsupplied).
NOTE: Additionaltools,materialsand hardware ore
requiredtoconstructgour ceilingsupport.
Check Installation Hardware
Locate the hardware accessorg bag packed with the
hood and check contents.
,exhe iFIF
woodlag
screws
2 Phillips-head 4 Flat
(6mmx 2-1/2"
or 1/4x2-1/2") ductcover washers
screws
2 Stopscrews
(Oneis intheservice
manualenvelope.
Leavethat screwin
theenvelope.)
............i] t:
Supportframes
with 8screws
and8washers
/o o'
,o Front of Hood %
\ O //
Template
Mountingscrewholes
\
Decorative
ductcovers
3 Stainless
steelgreasefilters
4 (10mm)Nuts
andlockwashers
._ 8Frame
attachmentscrews
with washers
(attachedto
accessorysupport
frames)
L%:b
2 Utensilrodswith 4 machinescrews
Additional Parts for Recirculating Operation
Air deflectorwith upper
ductconnectorand4
smallflat-headscrews
3 Charcoalfilters
Installation Preparation
DETERMINE INSTALLATION HEIGHT
Telescopic duct covers are provided to conceal
the ductwork running to the ceiling.
This hood can be installed for vented or
recirculating operation. All necessarg parts are
shipped with the hood.
24" Minimum
30" Maximum
m
36" Minimum
II
NOTE: Installation height should be measured from
the cooking surface to the bottom of the hood.
The vent hood must be installed 24" min. and
30" max. above the cooking surface. The hood
installation height, from the cooking surface to the
bottom of the hood, depends upon ceiling height
and duct cover limitations.
DUCT COVER DIMENSIONS
9-7/16"
15-3
Z×8510SPSS Duct Cover Accessory
The accessorg isavailable for installation with ceiling
heights of 8' 7" to over i0 feet. This accessorg
consists of two 26-1/4" duct covers and one 31"
upper support frame piece.
ZV850/ZV855
Installation Heights
*Possible
RECIRCULATING
Installation
Height
24"
24" to 25"
24" to 26"
24" to 27"
24" to 28"
24" to 29"
24" to 30"
25" to 30"
26" to 30"
27" to 30"
28" to 30"
29" to 30"
:30"
24"
24" to 25"
24" to 26"
24" to 27"
24" to 28"
24" to 29"
24" to 30"
24" to 30"
24" to 30"
24" to 30"
24" to 30"
24" to 30"
24" to 30"
24" to 30"
24" to 30"
24" to 30"
25" to 30"
26" to 30"
27" to 30"
28" to 30"
29" to 30"
:30"
*Based on 36" countertop height.
Installation Preparation
CONSTRUCT CEILING SUPPORT
Plan the Location of the Hood and Ductwork
Use o plumb bob to check the Iocotion.
The countertop/cooktop below the hood
must be centered with the hood.
The hood should extend beyond the front and rear
edge of the cooking appliance.
The duct in the ceiling must be centered over
the cooktop.
Align with
center of
cooktop
Ceiling
Hood
13-3/4" "i
.......................................27-1/2!!i
Cooktop
/
I
SideView
Countertop
Ceiling Support Structure
At the hood location, install cross-framing between
ceiling joists as shown. (2x4 wood supports
(]re required to support the weight of the hood.)
Arrange cross-framing in the ceiling to suit
the existing structure.
Your ceiling joists will be like one of the following
examples.
EXAMPLEA
Installcr0ss-framingsymmetricallyover
duct/c00kt0pcenterline
i
..... Jr .....
i
__ 2x4 Cross-framing
wood supports
I
I
I
I
I
I
I
I
I
I
I
Align duct
to center
of cooktop
Topview- ceilingjoistsparallelto front of hood
Cooktop
outline
Installation Preparation
CONSTRUCT CEILING SUPPORT (Continued)
EXAMPLEB
Installcross-framing
symmetricallyover
duct/cooktopcenterline
16" I
spacing 7-5/8"
8-3/4"
2x4 Cross-
framing wood
supports
\
Align duct Cooktop
to center outline
of cooktop
Top view - ceiling joists run perpendicular to front of hood
EXAMPLEC
Install cross-framing symmetrically
over duct/cooktop centerline
2x4 Cross-
framing wood
supports
16 Joist
spacing
Align duct Cooktop
to center outline
of cooktop
Top view- ceiling joists at angle to front of hood
10
Installation Preparation
CONSTRUCT CEILING SUPPORT (Continued)
Secure each 2 x/4 block with at least four (4),#10
wood screws, 3" long (not supplied). Use 8 wood
screws total for the two supports.
The cross framing must be accurately aligned
to assure correct positioning of the hood.
The cross framing must be level in all directions.
Check with a spirit level and adjust if necessarg.
IMPORTANT: The ceiling structure must be capable
of supporting the weight of the hood (approximatelg
200 pounds) and ang inadvertent user contact loads.
The hood support frame will be supported bg the
2 x 4 cross framing.
Ductwork for Installations Vented to the Outdoors
Use the shortest and straightest duct route
possible. For satisfactorg performance, duct run
should not exceed 100 feet equivalent length for
ang duct
configuration.
Refer to "Duct Fittings" chart to compute
the maximum permissible length for duct runs
to the outdoors.
/I, This vent hood must use 6" round rigid duct.
WA RNING:TOREDUCETHERISK
OF FIRE, USE ONLY RIGID METAL DUCTWORK.
Install the house ductwork to run horizontallg
between ceiling joists or straight up through
the roof.
Finish the Ceiling
Finish the ceiling surface. Be sure to mark location
of the ceiling joists and cross framing. Check to be
sure the ceiling is level; use shims if necessarg.
CrossFraming
\
/
(
7
t i
Joist : 7-5/8..... i'_ _.
, ;_;.... -...... ....
S_PPm°rt
Uppermalf.--i-" ii _i _ a e
Of Support i i-font j upenmg
Frame j OT i
l Hood ...............l
Height ......i i
Adjustment -- ! ................
Slot
Ceilingjoist
/
6" ¢
"2
\
2x4
Ventstraightup
throughthe ceiling
f
(
/
11
Installation Instructions
INSTALLATION -VENTED TO THE OUTSIDE
MOUNT TEMPLATE
Align the template with the marks on the ceiling and
tape in place.
- Be sure the template is oriented correctlLh with the
front of the hood.
Useo plumb to be sure the mounting holes will provide
parallel alignment with the countertop below.
Center punch all hole locations.
Drill pilot holes in the 4 screw
locutions. Use a 5/32" bit and drill
approximatelg 1-1/2" deep.
Cut wire access hole
i
approximatelg 1" diG. Frontof Hood
Cut the 6-1/2" duct opening ' O '
\\ /
through the ceiling. "- - -_"
Wire AccessHole
_-1 INSTALL UPPER SUPPORT FRAME
Secure the upper support frame to the ceiling
joists and/or cross framing with the 4 screws
provided. For maximum rigiditg and strength, the
screws must be driven into the center of the joists
and/or cross-framing.
Check to be sure the support frame is level,
verticallg and horizontallg.
i
Upper J
Support Frol
Frame Of
He(
]art
Frame
Opening
Lower
Support
Frame
_ CheckLevelin
BothDirections
Hood
Mounting
Flange
_-1 INSTALL LOWER SUPPORT FRAME
Insert lower support frame into the upper support
frame and Iooselg secure with 8 screws and
washers (4 on the front and 4 on the back sides).
Adjust the lower support frame up or down
to the desired height above the countertop.
Tighten screws.
.....Lowersuppor
ummg_ ///
,ano ii ............i.........
13-5/8"
/
24" Minimum
30" Maximum
Countertop
IMPORTANT: Again, check to be sure the support is
level in both directions. There is no wag to level the
hood after the hood is secured to the frame.
12
Installation Instructions
INSTALLATION -VENTED TO THE OUTSIDE
SECURE WIRING
Route house wiring through the ceiling hole and
pull o length to reach the hood junction box.
FrontSide
Support-
Frames
?
0
?
U
Ce!ling
\\\
?
0
?
--- :
House
Wiring
Tape the wire to the front of the frame support to
prevent damage during installation and service.
_-1 SIZE AND INSTALL DUCTWORK
Measure from house duct (Dim. A) to bottom of
support frame.
- Add at least 1" for duct overlap at the top.
- Subtract 3/4" for hood insertion into the bottom
of the frame.
Cut the 6" dia. duct to the required length.
HouseDuct--
Side
View
Support
Frame
Ceiling
/
.=
Dim.A i Length
DuctConnection
ToHood........ /="[_]
................................................................3/d_]]_
BottomSupport
FrameFlange
NOTE: The bottom end of the duct must be flared
slightlg, to facilitate installation of the hood.
Install duct up through support frames onto the
house duct. Push duct up until it is 3/a" from the
bottom of the support frame flange.
Secure the duct to house duct connection with
screws and seal with duct tape.
Seal duct connection with duct tape, making sure
connection is secured in place.
13
Installation Instructions
INSTALLATION -VENTED TO THE OUTSIDE
_-1 INSTALL DECORATIVE DUCT COVERS
Install Screwon
EachSide
TopDuct
Cover
Bottom Duct
Cover
!
Bottom Duct Cover
Install Stop
Screw in One
of2 Holes
Pretap or drive decorative screw into the screw holes
on the support frame. This will make screw installation
easier.
Separate the two decorative duct covers.
Select the inside or top cover with the vent hole
pattern on one end.
For this vented installation to the outside, the hole
pattern should be located at the bottom.
Locate the 2 supplied duct cover screws.
Slide the decorative duct cover over the support frame
and push to the ceiling.
Attach the inside duct cover to the hood support at
the top with 2 supplied duct cover screws.
Locate the stop screw in the hardware bag.
Install the stop screw into one of the two holes and
tighten against the frame to allow the second duct
cover to slide up and pass over.
Slide the lower duct cover over the installed upper
duct cover and push up past the stop screw location.
Back out the stop screw far enough to support the
bottom duct cover and prevent it from sliding down
onto the top of the hood.
_4,CAUTION: The stop screw must be
installed. Failure to do so could result in personal
injury or damage to the duct cover.
14
Installation Instructions
INSTALLATION -VENTED TO THE OUTSIDE
I-_ INSTALL HOOD
Align Duct
Connectorto -...
HouseDuct "-
// Align
Mounting
/J Studs
StopScrew
/
Bottom
Duct
Cover
/ Install
4lock
washer
and4 Nuts
\
\
NOTE: TWO PEOPLE ARE REQUIRED TO COMPLETE
THIS INSTALLATION!
Lift the hood up to the support frame. Carefully align
the hood mounting studs into the support frame holes,
and at the same time, guide the hood duct connector
into the duct.
Install 4 nuts and lock washers. Tighten with a 10 mm
wrench.
ooo
Check hood level in both directions.
Seal the duct connection with duct tape.
NOTE: Do not drive screws through this duct
connection. Doing so will prevent proper damper
operation.
_-1 CONNECT ELECTRICAL
Verify that power is turned off at the source.
IIWARNING:If housewiring isnot2-wire
with u ground wire, u ground must be provided
by the installer. When house wiring is aluminum,
be sure to use U.L.-upproved untioxidant compound
and aluminum-to-copper connectors.
Install strain relief onto the knockout of the junction
box cover.
Insert house wiring through strain relief and tighten.
Connect white leads to branch circuit white lead.
Connect black leads to branch circuit black lead.
Connect green/yellow leads to branch circuit green
or bare ground lead.
Secure all connections with wire nuts on each
electrical connector.
Push wires into junction box and replace cover.
Be sure wires are not pinched.
15
_-1 SLIDE DUCT COVER DOWN,
INSTALL SIDE UTENSIL RODS
Slide the lower duct cover up and above the
stop screw.
Drive the stop screw in close to the frame.
Slide the lower duct cover down against the top
of the hood. The duct cover should be seated into
the pocket on top of the hood.
Install the side utensil rods with screws as shown.
Instollotion Instructions
INSTALLATION -VENTED TO THE OUTSIDE
INSTALL FILTERS
Remove protective film on filters.
Tip the filter into the lower chonnel (It the re(It
of the opening. Push b(]ck, lift (]nd pull the knob
forw(]rd until the filter rests on the ch(]nnel.
\
Lower Filter
Channels
Inst(]ll (]11three met(]l gre(]se filters.
\\
\
\
\
Turn power on. If the filter light on the control p(]nel
glows, (]djust the right-side filter in the ch(]nnel to
eng(]ge the switch (]rm.
\
FINALIZE INSTALLATION
Remove the protective film covering the control p(]nel
on the front f(]ce of the hood (]nd (]ng other p(]ck(]ging
m(]teri(]ls.
M(]ke sure the filters (]re se(]ted properlg when
inst(]lled (]nd the filter light is not on.
Besure f(]n (]nd lights oper(]te correctlg. Refer to
the Owner's M(]nu(]l for oper(]ting instructions
(]nd the Problem Solver.
16
Installation Instructions
INSTALLATION - RECIRCULATING
_-] MOUNT TEMPLATE
Align the template with the marks on the ceiling and
tape in place.
- Be sure the template isoriented correctlg, with the
front of the hood.
Usea plumb to be surethe mounting
holeswill provide parallel alignment
with the countertop below.
Center punch all hole locations.
Drill pilot holes in the 4 screw
locations. Use a 5/32" bit and drill
approximatelg 1-1/2" deep.
Cutwire access hole approximatelg
1" dia.
r o o_
i
\o Front ofHood o
_-1 INSTALL AIR DEFLECTOR AND
UPPER SUPPORT FRAME
Theduct connector isshipped insidethe deflector.
Snap the plastic connector out of
the deflector and remove. Turn it
over. From the bottom, snap the
connector over the opening.
Slidethe assembled deflector into
the upper support frame and secure
with 4 small screws.
Securethe upper support frame to
the ceilingjoists and/or crossframing
with the 4 screws provided. Formaximum rigiditg
and strength, the screws must be driven intothe center
of thejoists and/or crossframing.
Check to be sure the support frame is level,verticallg
and horizontallg.
Install
4 Screws ] Support
Upper i_ Frame
Support Opening
Frame
- .......... _/Check Levelin
Lower _ _.-_: _Both Direc[ions
Support <- ........ m :::_-:::_*....
Frame .... "'J.........
Hood
Mounting
Flange
Assembled
i Air Deflector
/
/
NOTE:Besureplastic
connectoris installedon
the bottomofthe
deflectorasshown.
17
Installation Instructions
INSTALLATION - RECIRCULATING
_-1 INSTALL LOWER SUPPORT FRAME
Insert lower support frame into the upper support
frame and Iooselg secure with 8 screws and
washers (4 on the front and 4 on the back sides).
Adjust the lower support frame up or down
to the desired height above the countertop.
Tighten screws.
IMPORTANT: Again, check to be sure the support is
level in both directions. There is no wag to level the
hood after the hood issecured to the frame.
Hood
Mounting _
Flange
:::[:::Fi_7::[::.L 13-5/8"
/
,- . .,, .... .. |
24" Minimum
30" Maximum
Countertop
II
SECURE WIRING
Route house wiring through the ceiling hole
and pull a length to reach the hood junction box.
FrontSide
Support_
Frames _ \_
\,\
? ?
g o
? ?
C_eling
House
Wiring
Tape the wire to the front of the frame support to
prevent damage during installation and service.
_-1 SIZE AND INSTALL DUCTWORK
Measure from top duct connector (Dim. A)
to bottom of support frame.
- Subtract 3/4" for hood insertion into the bottom
of the frame.
Cut the 6" dio. duct to the required length.
Ceiling
/
DuctConnector
--...
--....
Side
View
Support
Frame
DuctConnection
ToHood........
.....I.... I
Dim.A
::Required
Duct Duct
Length
=
i
BottomSupport
FrameFlange
NOTE: The bottom end of the duct must be flared
slightlg, to facilitate installation of the hood.
Install duct up through support frames onto the
duct connector. Push duct up until it is 3/4" from
the bottom of the support frame flange. See
illustration.
Seal duct connection with duct tape, making sure
the connection is secured in place.
18
Installation Instructions
INSTALLATION - RECIRCULATING
_-1 INSTALL DECORATIVE DUCT COVERS
Pretap _
2Screw
Holes
TopDuct
Install Screwon
EachSide
Bottom Duct
Cover
Bottom DuctCover
! !
_ !_!ieaHIwlS_iJne
Pretap or drive decorative screw into the screw holes
on the support frame. This will make screw installation
easier.
Seporate the two decorative duct covers.
Select the inside or top cover with the vent hole
pattern on one end.
For this recirculating installation, the hole pattern
should be located at the top.
Locate the 2 supplied duct cover screws.
Slide the decorative duct cover over the support frame
and push to the ceiling.
Attach the inside duct cover to the hood support at
the top with 2 supplied duct cover screws.
Locate the stop screw in the hardware bag.
Install the stop screw into one of the two holes and
tighten against the frame to allow the second duct
cover to slide up and pass over.
Slide the lower duct cover over the installed upper
duct cover and push up past the stop screw location.
Back out the stop screw far enough to support the
bottom duct cover and prevent it from sliding down
onto the top of the hood.
CAUTION: The stop screw must be
installed. Failure to do so could result in personal
injurg or damage to the duct cover.
19
Installation Instructions
INSTALLATION - RECIRCULATING
I-_ INSTALL HOOD
Align Duct
Connectorto ..
HouseDuct
Align
, Mounting
Studs
\
\
\.
NOTE: Before installing the hood, the metal damper
flaps on top of the hood exhaust outlet may be removed.
Do not remove the duct transition. The damper is not
required for this recirculating operation.
NOTE: TWO PEOPLE ARE REQUIRED TO COMPLETE
THIS INSTALLATION!
Lift the hood up to the support frame. Carefully align
the hood mounting studs into the support frame holes,
and at the same time, guide the hood duct connector
into the duct.
J
f
Install4 nuts and lock washers. Tighten with a 10 mm
wrench.
Check hood level in both directions.
Seal the duct connection with duct tape.
NOTE: Do not drive screws through this duct
connection. Doing so will prevent proper dumper
operation (if present).
_-1 CONNECT ELECTRICAL
Verify that power is turned off at the source.
-4,WARNING: fhousewiring isnot2-wire
with a ground wire, a ground must be provided
by the installer. When house wiring is aluminum,
be sure to use U.L.-approved antioxidunt compound
and aluminum-to-copper connectors.
Install strain relief onto the knockout of the junction
box cover.
Insert house wiring through strain relief and tighten.
Connect white leads to brunch circuit white lead.
Connect black leads to brunch circuit black lead.
Connect green/yellow leads to brunch circuit green
or bare ground lead.
Secure all connections with wire nuts on each
electrical connector.
Push wires into junction box and replace cover.
Be sure wires are not pinched.
_-1 SLIDE DUCT COVER DOWN,
INSTALL SIDE UTENSIL RODS
Slide the lower duct cover up and above the
stop screw.
Drive the stop screw in close to the frame.
Slide the lower duct cover down against the top
of the hood. The duct cover should be seated into
the pocket on top of the hood.
Install the side utensil rods with screws us shown.
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64