Bernard EZ Range Installation & Operation Manual

Type
Installation & Operation Manual

This manual is also suitable for

INSTRUCTIONS DE MISE EN SERVICE,
STOCKAGE ET ENTRETIEN
INSTRUCTIONS FOR START-UP,
STORAGE AND MAINTENANCE
ANLEITUNG FÜR DIE INBETRIEBNAHME,
LAGERUNG UND WARTUNG
NR 1208_EZ_revJ_A/F/D
Art: 5100134
EZ
Gamme
Range
TABLE OF CONTENT
1 Safety information 3
2 Assembly 3
3 Handwheel operation and declutching 3
4
Commissioning for switch actuator 4
5 Commissioning of EZ LOGIC actuator 8
6 Torque limiter 20
7 Maintenance and storage instructions 20
Wiring diagram - EZ4 to EZ15 single-phase 57
Wiring diagram - EZ25 to EZ60 single-phase 58
Wiring diagram - Other EZ actuators 59
Examples of power supply circuits 60
Control panel design examples 61
Wiring diagram - EZ LOGIC 62
Wiring diagram - EZ6-EZ15 DC prewired 63
SOMMAIRE
1 Sécurité 21
2 Montage 21
3 Commande manuelle et debrayage 21
4 Mise en service - servomoteurs switch 22
5 Mise en service - servomoteurs EZ LOGIC 26
6 Limiteur de couple 38
7 Entretien et stockage des servomoteurs 38
Câblage des actionneurs EZ4 à EZ15 monophasé 57
Câblage des actionneurs EZ25 à EZ60 monophasé 58
Câblage des autres actionneurs EZ 59
Exemples de circuits de puissance 60
Exemples de réalisation de coffrets de commande 61
Schéma de câblage - EZ LOGIC 62
Câblage des actionneurs EZ6-EZ15 courant continu précâblé 63
INHALTSVERZEICHNIS
1 Sicherheitsinformationen 39
2 Montage 39
3 Handradbetätigung und auskuppeln 39
4 Inbetriebnahme für auf/zu antriebe 40
5 Inbetriebnahme antrieb EZ LOGIC 44
6 Drehmomentbegrenzer 56
7 Wartungsanleitung und hinweise zur lagerung 56
Antriebverdrahtung - EZ4 bis EZ15 einphasig 57
Antriebverdrahtung - EZ25 bis EZ60 einphasig 58
Antriebverdrahtung - Andere EZ antriebe 59
Beispiele für Stromversorgungskreise 60
Beispiele für Schalttafelausführungen 61
SCHALTPLAN - EZ LOGIC 62
Antriebverdrahtung - EZ6-EZ15 gleichstrom vorverkabelt 63
3
English
1 SAFETY INFORMATION
This device complies to current applicable safety standards. Installation, maintenance and use of
this actuator will have to be done by skilled and trained staff only.
Please read carefully the whole document prior to mounting and starting-up.
2 ASSEMBLY
Actuator should be secured directly to the valve using proper bolts or via a proper interface.
After assembly, the actuator can operate in any position. However, cable glands should not be
oriented upwards (loss of water tightness) and the motor will preferably not be positioned at the
bottom (potential internal condensation trap)
Note 1 : Do not handle the actuator by handwheel, it could damage the gearworm.
Note 2 : If the actuator was delivered mounted on the valve, the basic settings should have been done.
Note 3 : see §.7 for details on storage precaution prior to starting-up.
3 HANDWHEEL OPERATION AND DECLUTCHING
In general, the handwheel does not turn during electrical operation. Even if turning, the solid
handwheel does not have any protruding part and therefore does not present any risk of any kind
for the operator. Moreover, for the actuators with the highest torque, the torque limit system
brings an additional level of protection.
EZ4 to EZ15 models:
These actuators are equipped with a manually declutchable handwheel.
To operate manually the actuator, turn while pulling the handwheel
in order to mechanically engage it.
To declutch the handwheel, just push it back towards the actuator
body.
EZ100 to EZ1000 models:
These actuators are provided with an automatic declutching hand-
wheel, with motor drive priority. In order to operate manually the
actuator, turn the arrow of the handwheel clutch button in front of the
triangular sign on the housing (it might be necessary to turn the hand-
wheel by a few degrees to release the claws). When the motor starts,
it returns automatically into declutched position.
EZ60 models:
These actuators are equipped with declutchable intermediate gears. By moving the clutch lever, the
motor is physically disengaged from the gears. Once the manual handwheel operation has been
completed, do not forget to clutch the motor back. Otherwise, once started-up, it would run and heat
up until the motor thermal protection switch closes. If repeated, these conditions can generate a motor
breakdown .
4
FOR AN ACTUATOR WORKING SWITCH,
READ DIRECLY PARAGRAPH 4
FOR AN ACTUATOR WORKING WITH EZ LOGIC,
READ DIRECLY PARAGRAPH 5
4 COMMISSIONING FOR SWITCH ACTUATOR
4.1
ELECTRICAL CONNECTIONS AND PRELIMINARY TESTS
All components of the actuator are wired to a common
terminal strip. Remove the cover and pass the cables through the cable
glands (M20). Refer to the wiring diagram for details on the terminals
numbering system.
Both thermal protector and torque limit switches must be integrated into
your control system (see wiring examples) in order to prevent potential
damage to the actuator or valve.
The following points must be checked:
a) Make sure that power supply voltage is in accordance with the data engraved on the actuator
nameplate
b) Check that all cable glands are correctly tightened,
c) Move the valve manually to an half-open position,
d) Operate an electrical opening and check that the motor rotates in the right direction. Press
manually on the «OPEN» travel limit switch ; the motor should stop.
In the same way, check that the closing electrical command as well as the «CLOSED» travel
limit switch are working correctly,
e) All models except EZ4 to EZ15 : Operate an electrical opening. Press manually on the «OPEN» torque
limit switch ; the motor should stop. In the same way, operate an electrical closing check that
the «CLOSED» torque limit switch is working correctly,
If any misfunction was detected at this stage, please check the overall wiring.
For safer working conditions, we recommend that the power supply now be switched off especially
if the actuator output max. torque exceeds 300 N.m.
4.2
SETTING OF MECHANICAL STOPS AND TRAVEL LIMIT SWITCHES
Mechanical stops description and function :
These items avoid any over-travelling during handwheel operations.
The stops can be positioned either on the actuator itself or on the 1/4 Turn
worm gearbox if any.
Actuators and gears are supplied and tested for a 90° operation.
Fine adjustment of the stop screws position is possible within a limit
of ± 2° maximum.
5
English
Travel limit switches description and function:
The cams operating the limit switches are on a cylindrical block which does not require any disas-
sembly. Each cam can be set independently of the others. The white and black cams are for OPEN
and CLOSE travel limit switches. The other cams actuate additional limit switches (Example : For
signalling).
How to operate the cams:
a) Put a screwdriver in the slot of the button encircled by the same color as the cam to be set,
b) Press lightly to disengage the cam of locked position,
c) By turning the screwdriver rotate the cam to the position in which it can trip the limit switch,
d) Remove screwdriver and ensure that the button has come back to its original position, thus
locking the cam in chosen place.
Procedure of mechanical stops and travel limit switches setting:
a) Loosen stop screws by 2 turns.
b) Manually drive the valve to the closed position. If mechanical stops
are reached before the valve closing is completed, it means that the
2° maximum adjustment tolerance has been exceeded ; do not try
to go beyond this limit.
c) Set the cam of the «CLOSED» travel limit switch.
d) Turn stop screws clockwise to the mechanical contact, reloosen 1.5
turn, and secure by lock nut.
Proceed in the same way in open position.
Perform complete electrical valve opening and closing operations.
It is mandatory that the motor stops on the travel limit switch and
not on the mechanical stop.
4.3 POSITION FEEDBACK POTENTIOMETER
(EZxxxx FA XX 123 A1 only)
The potentiometer used for actuator signal feedback is driven by the travel cam block system.
0% position corresponds to a closed valve. 100% to an open valve.
Circuit board mounted version
To mount the potentiometer device on the switch plate, clip it without
the position indicator on the camblock and screw it on the support
column. Screw the position indicator back.
Setting of potentiometer zero is achieved thanks to the «0% postion»
screw.
Drive the actuator to the closed position.
Resistance value is measured between terminals 16 and 17.
Hold the pinion located just under the plate with the «0% position»
marking while driving the potentiometer screw. Adjust the potentiome-
ter so that the resistance value exceeds 0 Ohm and regularly increases
then turn backwards to reach a value as close to 0 Ohm as possible.
Drive the actuator to the open position and write down the resistance
value corresponding to the 100% position.
Come back to the closed position and check that, for the 0% position,
the resistance shows a close to zero repeatable value.
6
On support column mounted version (EZ4 to EZ15 actuactors)
To mount the potentiometer device, screw the support column on the mounting plate and engage the driving
pinion into the camblock wheel.
To adjust the potentiometer resistance value, loosen the nut with the
wrench and rotate potentiometer until the signal requested is archieved.
To set the 0%, drive the actuator to the closed position.
Resistance value is measured between terminals 16 and 17.
Rotate the potentiometer so that the resistance value exceeds 0 Ohm
and regularly increases then turn backwards to reach a value as close
to 0 Ohm as possible.
Retighten nut after setting.
Drive the actuator to the OPEN position and write down the resistance value corresponding to the
100% position. Come back to the closed position and check that, for the 0% position, the resistance
shows a close to zero repeatable value.
Signal inversion:
To inverse the signal variation direction, invert potentiometer wires on the actuator terminal board
(e.g. for a connection on 16/17/18, invert 16 and 18).
4.4 «TAM» POSITION TRANSMITTER
(EZxxxx FA XX 123 A2 only)
The TAM transmitter delivers a 4 to 20 mA signal linearly proportional
to the angular position of the valve.
Electric connections
Refer to the wiring diagram supplied with the actuator.
FIltered or stabilised power supply should be provided within the 12
to 32 VDC range. Maximum admissible ohmic load values are given in
the table :
Energy Supply
DC (VOLT)
Max. admissible
load Ohm
12 150
24 750
30 1050
7
English
Signal direction inversion
The TAM transmitter, when supplied with a standard actuator, provides a signal that rise from close
position to open position, the standard opening direction being counter-clockwise.
If an opposite signal variation is required, simply move 2 jumpers on the board near the potentiometer.
Direct signal : jumpers on 1-3 and 2-4
Reversed signal : jumpers on 1-2 and 3-4
Settings
Connect a milliampermeter at the place of burden.
- Always start by adjusting the 4mA.
- Drive actuator to the position corresponding to the 4 mA (closed
position),
- Hold the pinion located just under the plate with the «0% position»
marking while driving the potentiometer screw. Adjust the poten-
tiometer so that the output current reaches a minimum value. Turn
backwards until the current value regularly increases then turn
backwards again and stop as soon as the minimum value determined
here above has been reached. The potentiometer is then positioned
at the very beginning of its track.
- Then, use the TAM adjustment screw marked as «0/4mA» to adjust
the current to a value as close to the 4 mA as possible.
- Drive actuator to the position corresponding to the 20 mA (open position),
- Turn the screw marked «20mA» in order to read exactly 20 mA on the milliampermeter.
- Come back to the closed position and check that, for the 0% position, the signal current shows
a close to 4 mA and repeatable value.
4.5 AUXILIAIRY CONTROL SWITCHES
The OPEN and CLOSED signalling can be managed separately by two separated control switches.
These switches are actuated by brown and grey cams.
They can be connected through terminals 20 to 25 as follow :
4.6 HEATING RESISTOR
Each actuator includes a heating resistor. As soon as the actuator is installed in the field, it is
recommanded du supply the resistor to prevent condensation.
4.7 CAUTION
Replace covers immediately after start-up and make sure that their seals are clean. Never fail
to replace the protection covers. If water ever enters, dry thoroughly before replacing covers.
Peržengimo ribotuvas
Atidaryta padėtis
Peržengimo ribotuvas
Uždara padėtis
8
5 COMMISSIONING OF EZ LOGIC ACTUATOR
5.1
PRODUCT DESCRIPTION
According to the reference, the EZ LOGIC control can work with single-phase, 3-phase or 24VDC.
Moreover, EZ LOGIC features a local command, a 7-segment display giving a percentage of opening
and several LED for signaling.
EZ LOGIC control can be proposed in two versions:
ON/OFF: Only the ‘valve opened’ and ‘valve closed’ positions are managed. The electronic board
receives a command by ‘dry contacts’ or by ‘voltage’ to ‘Open’, ‘Close’ or ‘Stop’. These actuators can
be identified on the rating plate by the following code:
EZxxxx FL XX 123 A0 are equipped with ON/OFF board
They work exclusively as ON/OFF
POSITIONING: The EZ LOGIC control receives an analog input signal (4/20mA as standard, 0/20mA
or 0/10VDC are also possible) and manages the valve positioning. A position feed-back is given to
the remote command. These actuators can be identified on the rating plate by the following code:
EZxxxx KL XX 123 A0 are equipped with positioning board
They can also work as ON/OFF
5.1.1 Keyboard
1
9
10
7
6
3
5
4
2
8
Description
1.
7-segment display
(Percentage of opening, user’s indications)
2. Selection key LOCAL / REMOTE and Escape
3. CLOSING and ‘Go down’ key
4. STOP and validation key
5. OPENING and ‘Go up’ key
6. VALVE CLOSED Led (Possible customization
Green/Red), flashing during closing operation)
7. VALVE OPENED Led (Possible customization Red/
Green) blinking during opening operation)
8. SETTING Led. Light is ON in setting mode.
9. ALARM Led. Light is ON in case of alarm and fault
code is displayed
10. LOCAL Led. Light is ON in local mode
Local command Inhibition
5 sec.
The keypad is protected against unexpected local command by a
local command inhibition.
This function is activated automatically after 1 minute without tou-
ching the keypad or by pressing the STOP key for 5 seconds.
When local control is locked, the display will show a key
.
To unlock, press the STOP key for 5 seconds.
9
English
5.1.2 Power board
Inputs/Outputs are connected through screwed terminals. The terminals have a clear marking
between 1 to 20 for command and signaling, and L1/L2/L3/PE for 3-phase power-supply, L/N/PE for
single-phase or + /- / PE for 24VDC.
The power-board includes an additional control-board connected to the sensors and the keypad.
5.2 WIRING
The wiring must be done according to the wiring diagram located inside the actuator.
To ensure properly the water-tightness, actuators must be equipped with M20 cable-glands (not
delivered with the actuator). A total of 3 cable entries are available.
Attention : Do not open under voltage
5.2.1 Opening of actuator
Control board
Ribbon cable
Isolated side
Remove the cover by unscrewing the 4
captive screws.
A ribbon cable coming from the key-
board is connected to the control board.
TO AVOID ANY DAMAGE, THE RIBBON
CABLE IS DESIGNED TO BE SELF-DIS-
CONNECTED WHEN THE COVER IS
REMOVED.
After wiring, it is necessary to connect
again the ribbon cable onto the control
board connector reaching the bottom
end (See picture).
Pay attention to respect the sense of
connection, the ribbon cable is not re-
versible. Do not twist the ribbon cable.
10
5.2.2 Power supply
Connect the power board according to the voltage indicated
on the rating plate.
- 3-Phase : L1/ L2 / L3 / PE
- Single-phase : L / N / PE
- 24VDC : + / - / PE
5.2.3 Remote command
The EZ LOGIC actuator’s remote control system can be operated using an external voltage supply
or dry contact command (internal 24VDC).
The input circuits are fully opto-isolated. The pulse command system requires four connecting wires
on the client terminal strip: Common, stop, open and close. If the stop push-button is not used, do
not connect the STOP wire, open (or close) switch must be maintained to operate the actuator.
Dry contact command
In case of dry contact control, a jumper must be fitted across terminal 9-10.
8
9
10
11
12
13
14
OPEN
CLOSE
STOP
8
9
10
11
12
13
14
OPEN
CLOSE
GND
+24V
GND
+24V
Voltage command
Remote control can use either in AC or DC voltage.
Use common terminal 9 for low voltages from 10 to 55V.
Use common terminal 8 for voltages from 90 to 250V.
Caution: Never connect voltage sources above 55V on common terminal 9
8
9
10
11
12
13
14
OPEN
CLOSE
10 - 55V ~
STOP
8
9
10
11
12
13
14
OPEN
CLOSE
90 - 250V ~
STOP
+
-
-
+
L3 L2/L L1/N PE
+ - PE
Pulse remote commande
(self-holding)
Maintained remote command
(without self-holding)
To remove self holding of the board, don’t connect 14
11
English
INPUT POSITION SIGNAL FOR POSITIONNER (EZxxxx KL XX 123 A0 only)
EZ LOGIC actuators with reference EZxxxx KL XX 123 A0 can perform control functions in response
to a control signal (e.g. 4 – 20 mA). No prior set-up is required as the signal is automatically adjusted
to the 0 to 100% positions.
15
16
-
+
4 - 20 mA
0 - 20 mA
0 - 10 V
Impedance of 15/16 input:
On 0/4-20mA signal : 162 Ohms
On 0-10VDC signal : 4052 Ohms
POSITION FEEDBACK (EZxxxx KL XX 123 A0 only)
EZ LOGIC actuators with reference EZxxxx KL XX 123 A0 can incorporate an analog position signal.
No prior set up is required as the signal is automatically adjusted to the 0 to 100% positions. The
default signal is in 4-20 mA (4 mA at 0% and 20 mA at 100%)
The external supply of the current loop can be in series (2-wire connection allowing 4/20mA signal
only) or in parallel (3-wire connection allowing 4/20 or 0/20mA)
17
18
19
20
12 - 30V
-
+
A
17
18
19
20
12 - 30V
-
+
A
To obtain a 0-10VDC position signal, set the position signal (according to chapter 5.4) into 0-20mA
and put a 500 Ohms resistor in series. The voltage has to be read on both sides of the resistor.
17
18
19
20
24 - 30V
-
+
-
+
0-10V
500
Ohms
Max total impedance of the current loop: 750 Ohms with 24VDC supply
Position signal 4/20 mA Position signal 0/20 or 4/20 mA
Position signal 0/10 VDC
12
5. 2.4 Opened/Closed signaling
EZ LOGIC board is equipped with two signaling relays for ‘opened’ and ‘closed’ positions (Latching
relays). These relays signal either the position 0% or 100% of the open valve.
5. 2.5 Alarm signaling
An ‘Alarm’ relay (monostable relay) switches off when a fault is detected. The reported faults are:
- loss of power supply
- loss of a phase (in three-phase)
- Primary fuse or control fuse out of order
- Motor thermal overload
- trigger force limiters
- Motor jammed
- Loss of input signal (with 4-20mA positioner)
- Position sensor out of order
- Torque sensor out of order
- Selector in local
To connect the relays see diagram page 57-59 according to your model.
5.3 FAST COMMISSIONING
2
1
The valve set-up is non-intrusive. After being wired, connect again the
ribbon cable (according to § 5.2.1) and shut carefully the actuator’s
cover (the seal must be well fitted to avoid any leakage).
Actuators and gears are supplied and tested for a 90° operation.
Fine adjustment of the stop screws position is possible within a limit
of ± 2° maximum.
Loosen the two lock nuts (1) first the 2 ‘stop screws’ (2) by 2 turns.
This allows increasing the of 2° the possible rotation of the output.
To enter the SETTING mode:
- If the KEY logo appears , it’s necessary to turn off the local
command inhibition by pressing OK during 5 sec
- Press Local/Remote during 3 seconds
Local light is ON
- Press simultaneously Local/remote and Stop keys during 3 sec
is displayed and the Setting light is ON
- Press OK (Stop) to enter in the valve set-up menu
is displayed
13
English
To do the set-up
- Use the local command to reach the ‘valve closed’ position. If mechanical stops are reached
before the valve closing is completed, it means that the 2° maximum adjustment tolerance has
been exceeded; do not try to go beyond this limit.
- Record the position by pressing OK
is displayed
- Turn closing stop screws clockwise to the mechanical contact, reloosen 1.5 turn, and secure by
lock nut.
- Use the local command to the ‘valve opened’ position
- Record the position by pressing OK
Actuator goes back to menu The
actuator is well set
- Turn opening stop screws clockwise to the mechanical contact, reloosen 1.5 turn, and secure by
lock nut.
- Press Esc. (Local/Remote) to return to the user’s mode in local mode
‘Setting’ light turns
off. If Err code appears, it means the setting is not recorded or the operation is less than 60°:
Start the set-up procedure from the beginning again.
- Operate the valve 2 or 3 times to check the limits and adjust the mechanical stop according to
chapter 5.2.1
- Press Local/remote to leave the ‘Local’ mode
‘Local’ light turns OFF
Actuator must stop according to the position sensor
and not on the mechanical stops.
14
5.4 CONFIGURATION BY SWITCHES
mA
V
SW500
SW400
1 2 3 4
1 2
ON
It’s possible to change some parameters by changing the
position of the zip-switches located on the control board.
To do this, it’s necessary to use a small screwdriver or a
pen.
Switches have the following names written on the board:
SW400 and SW500.
Note : Changes must be done out of voltage. The new
settings are taken into account after a power cut.
5.4.1 Motor direction of rotation
SW400
1 2 3 4
ON
1 2 3 4
ON
Clockwise
Counter
clockwise
As standard, the actuator closes clockwise (rotation viewed from the
top of the valve). To close counter-clockwise, set S1 switch in position
ON
5.4.2 Remote position signal (EZxxxx KL XX 123 A0 only)
SW400
1 2 3 4
ON
0/20 mA
mA
V
SW500
1 2
ON
SW400
1 2 3 4
ON
1 2 3 4
ON
4/20mA0/20 mA
As standard, the input position signal is 4/20mA (4=0% opening). The
position feed-back is identical. (Reminder: The position feed-back
needs external supply from 12 to 30VDC).
- It’s possible to give a 0/20mA input signal. Set S2 switch in position
OFF. The position feed-back will also become 0/20mA.
- It’s possible to give a 0/10VDC input signal. Set S2 switch in position
OFF and the two SW500 switches in position V
5.4.3 Selection of ON-OFF operation (EZxxxx KL XX 123 A0 only)
SW400
1 2 3 4
ON
1 2 3 4
ON
Proportionnal
OFF ON
As standard, the EZxxxx KL XX 123 A0 actuators operate according to
proportional input signal.
- It’s possible to work ON/OFF by setting the S3 switch in position OFF.
Once S3 is OFF, the analog input signal will become inefficient. Then,
remote command will be able to work with dry contacts command or
voltage command (see chapter 5.2.3)
15
English
5.5 CONFIGURATION BY PROGRAMMING
5.5.1
Flowchart
The main menu of the flowchart proposes 4 entries:
- Set Position
: Allows doing the set-up on valve
- Set Configuration
: Allows doing the setting of the local command, the safety
position in case of loss of 4/20 mA signal, color of the light ‘valve opened’ and ‘valve closed’
- Read Configuration
: Allows reading the configuration local command, voltage,
closing direction.
- Read Error
: Allows reading the ‘alarm’ codes if present (several codes may appear
simultaneously)
OR OR
OR
OR
OR
OR
OR
See Chapter 5.3
To validate and return
to upper menu,
press Esc. (Escape)
User mode
3 sec
+
16
5.5.2 To enter the main menu
- If the KEY logo appears , it’s necessary to turn off the local
command inhibition by pressing OK during 5 sec
- Press Local/Remote during 3 seconds
Local light is ON
- Press simultaneously Local/remote and Stop keys during 3 sec
is displayed and the Setting light is ON
- Move in the main menu by using UP (Open) and DOWN keys (Close)
- To enter in a sub-menu, press OK (Stop)
5.5.3 Description of ‘set configuration’ menu
(set cfg - configuration by programming)
- To enter the ‘Set Configuration’ menu, move in the main menu like described in chapter 5.5.2 and
press OK (Stop) when
is displayed.
- Go UP and DOWN to reach the sub-menus described below
- Press OK to enter the sub-menus
Set the local command (
)
As standard, the local command works by pulse command (
). For a maintained com-
mand, select ‘Local Hold’ (
) and validate by pressing OK (Stop)
Set the failsafe position (
)
You can set a failsafe position with a 4-20 mA signal only. Then the valve goes failsafe in case of
loss of the proportional signal.
The user can also choose ‘open’ or ‘close’.
For ‘Opened’ failsafe position, select
and confirm by pressing OK
For ‘Closed’ failsafe position, select
and confirm by pressing OK
For ‘stayput’ failsafe position, select
and confirm by pressing OK
Set the ‘Valve opened’ and ‘Valve closed’ LED colors (
)
Default configuration is the following:
the red light indicates that the valve is closed
the green light indicates that the valve is open
You can change the colors assignment so that the red light indicates that the valve is open.
To reverse LEDs assignment, enter in LED CONFIGURATION menu, select and confirm by pressing
OK.
Then the red LED indicates ‘Open’ position and the green LED indicates ‘Closed’ position.
You can restore initial configuration using the same menus.
17
English
5.5.4 Description of ‘read configuration’ menu ( )
- To entrer Read Configuration menu, move in the main menu like described in chapter 5.5.2 and
press OK (Stop) when
is displayed.
- Go UP and DOWN to reach the sub-menus
- Press OK to enter the sub-menus
- Read the setting of the local command.
- Read the setting of the proportional command.
If proportional command is ON, press OK to read the type of input signal.
If the selected input signal is 4/20, press OK in order to read the failsafe position.
You can return to the upper menu by pressing Esc. (Escape).
- Read the nominal voltage (Single phase or 24VDC) or (3-phase)
- Read the closing direction (Close clockwise) or (Close Counter- ClockWise)
5.5.5 Read the existing alarm codes ( )
- To enter the Read Error menu, move in the main menu like described in chapter 5.5.2 and press
OK (Stop) when
is displayed.
- Go UP and DOWN to read the codes
- If there’s no alarm, display is
Code Alarm Condition
--- No fault found
E01 Max torque reached Not available on EZ4 à EZ15
E02 Thermal overload
E03 Loss of one phase For 3-phase supply
E04 Loss of 4/20mA input signal Not applicable with 0/20mA
E05 Rotor is jammed
E06 Position sensor in fault
E07 Torque sensor in fault Not available on EZ4 to EZ15
18
5.6 TROUBLE SHOOTING
Trouble To be checked
Impossible to enter the Local
mode
Display shows KEY
Unlock the local command by pressing STOP during 5s
No possible command from
the remote
Check that ‘local’ signaling light is OFF, else press shortly LO-
CAL/REMOTE key to quit the local mode
Check that S3 switch if in OFF position
If command given by dry contacts, check the 24VDC between
terminal 10 & 11, else check F502 fuse on the power board
(Actuators working with AC) or F505 (Actuators working with
24VDC)
No possible command from
the keypad (local)
Check that ‘local’ signaling light is ON, else presss LOCAL/RE-
MOTE key during 3s to enter the local mode
No operation :
No display, no signaling, no
motor activity
Check the ribbon cable between the keypad and the control
board (check if the cable is not reversed inside the connector)
Check the power supply wiring, if there is a voltage, if this
voltage is the voltage written on the rating plate. Check if the
polarity is not reversed for DC voltage
Check fuse F501 on AC power board or F505 on DC power
board, if no fault found please contact Bernard Controls
Receiving a command, actua-
tor doesn’t operate but cor-
responding light (red or green)
is blinking
Check the motor cable
if Ok, check if the voltage is in accordance with the rating plate
Actuator operate in the
wrong direction
Check switch (S1 , SW400) defining the closing direction
Actuator doesn’t operate
according to 0-20mA analog
input signal
Check if this actuator is equipped with positionner (EZxxxx KL
XX 123 A0)
Check if any fault code is displayed (E04 )
Check the good position of the configuration switches (SW400
S2 = OFF, S3 = ON et SW500 S1 & S2 = mA)
Check the wiring of the 0-20mA proportionnal input signal
0-20mA
Actuator doesn’t operate ac-
cording to 0-10V analog input
signal
Check if this actuator is equipped with positionner (EZxxxx KL
XX 123 A0)
Check if any fault code is displayed
Check the good position of the configuration switches (SW400
S2 = OFF, S3 = ON et SW500 S1 & S2 = V)
Check the wiring of the 0-10V proportionnal input signal
Actuator doesn’t operate
according to 4-20mA analog
input signal
Check if this actuator is equipped with positionner (EZxxxx KL
XX 123 A0)
Check if any fault code is displayed
Check the good position of the configuration switches (SW400
S2 = ON, S3 = ON et SW500 S1 & S2 = mA)
Check the wiring of the 4-20mA proportionnal input signal
4-20mA
19
English
Display doesn’t work or key-
pad is inactive
Check the ribbon cable between the keypad and the control
board (check if the cable is not reversed inside the connector)
Check the fuses
Check the power supply
No position feedback
Check if this actuator is equipped with positioner
(EZxxxx KL XX 123 A0)
Check the good wiring and supply of the current loop
No remote signaling (Valve
opened, valve closed, alarm)
Check the wiring between remote and signaling relays
(terminal 1 to 7)
E01 is displayed This fault message mean the maximum torque is reached
check that the valve torque is not too high
Check that mechanical stops are not stopping the movement
before reaching ‘opened’ or ‘closed’ position on the position
sensor
E02 is displayed This fault message means there was a thermal overload of the
motor due to intensive operation.
The motor must cool down and the reset will be automatic.
If the fault code remains ON, please contact Bernard Controls
E03 is displayed
This message means there is a loss of one phase
Check the power connection and the presence of the 3 phases
and the supply voltage
E04 is displayed This message means the 4-20mA input signal has been lost
Check that the 4-20mA is active and in the 4 to 20 mA range.
E05 is displayed This fault message mean the actuator (or its motor) is jamming
Check that the torque is not too high
Check that mechanical stops are not stopping the movement
before reaching ‘opened’ or ‘closed’ position on the position
sensor
E06 is displayed
Position sensor is out of order
Check the ribbon cable between the position sensor and the
control board
E07 is displayed
Check if torque sensor is well connected to the control board
(not available on EZ4 to EZ15)
Check if the torque sensor cable is not damaged
Check also is the cable is not reversed in the connector
20
6 TORQUE LIMITER
EZ25 to EZ1000 actuators are equipped with a torque limiter.
IMPORTANT :
With EZ SWITCH, the Torque limiter give pulse contact at the maximum
possible torque.
After stopping the motor, the information is not mechanically memo-
rized. Therefore store information via an self-maintained relay (see
example of cable at the end of document).
On EZ LOGIC, the torque is measured by a strain gauge. The torque
information memorized by the control board.
7 MAINTENANCE AND STORAGE INSTRUCTIONS
Maintenance
If actuators is correctly mounted and sealed, no special maintenance is required. Check once a year
function of motor and make sure that switch compartment is condensation free. If environment is
humid, we recommend to connect the anti-condensation heater resistance, thus protecting electric
parts from alteration (On EZ LOGIC, heater resistance function is included in the power board).
Actuators are lubricated for lifetime.
Storage
The actuators includes electric equipment as well as grease lubricated gear stages. In spite of the
weatherproof enclosure, oxydising, jamming and other alterations are possible if actuator is not
correctly stored.
Actuator stored in a warehouse
a) The actuators should be stored under shelter, in a clean, dry place and protected from successive
changes in temperature. Avoid storage on the floor.
b) Supply the heating resistor in the case of presence of moisture.
c) Check that plastic plugs of the cable entries are well in place. Ensure the tightness of covers and
enclosures containing electrical components.
Actuator installed but waiting for electrical connection
If there is a long wait between the actuator mounting and electrical connection works:
a) Check the proper sealing of the cable-glands electrical boxes,
b) Cover the motor with plastic film,
c) Supply the heating resistor in the case of presence of moisture.
Storage of actuators equipped with electronic components
Long term storage of electronic components which are not in service increases the malfunction risk. This
practice is therefore highly unadvisable.
Control after storage
a) Check visually the electrical components,,
b) Operate manually the switches to check the proper mechanical work,
c) Operate apparatus manually,
d) Carry out the commissioning of the actuator according to the instructions attached to each device
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Bernard EZ Range Installation & Operation Manual

Type
Installation & Operation Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages