IT Power Distribution Module 3 Pole 4 Wire 60A IEC309 380cm

APC IT Power Distribution Module 3 Pole 4 Wire 60A IEC309 380cm User manual

  • Hello! I am an AI chatbot trained to assist you with the APC IT Power Distribution Module 3 Pole 4 Wire 60A IEC309 380cm User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
s
c
AP7568 AP7598 AP7569 AP7599 AP7567A AP7516
APCModularPowerDistribution,ModularPowerAccessories,andRackPDUs
CompatibilityChart,208/415VRegions
TheAPCPowerDistributionModules(PDMs)specifiedinTable1areintendedforusein208VModularPDUs.TheycanbeinstalledinthefollowingAPCproducts:
APCModularPowerDistributionUnit 100kWModularPDUsforAPCSymmetraPX100
PDPM144F
PDPM72F5U
PDPM100F6FM
PDPM100G6FM
PDPM100L6FM
PDPM100FM
Table1:APCPowerDistributionModulesfor208VModularPDU
s
208VPowerDistributionModuleshaveblackbussplateswhichmatchtheblack208VPDUbackplane.ThesePDMsrequireone(1)ModularPDUslotposition.
Module # cords Voltage Amperage
(Qty) Circuit
Breakers
(Qty)
Connector
Compatible APC
Rack PDUs APC Rack PDU SKUS
PDM1320L53Px 3 120V 20A (3)1P
Basic
AP7530,AP9551,AP9564
(3)3wire
NEMAL520R
Metered AP7830,AP7801
Switched AP7930,AP7901
PDM3520L2120xxx 1 120V 20A (3)1P
Basic AP7562,AP7592,AP7563,AP7593,AP7564,AP7594
(1)5wire
NEMAL2120
Metered
AP7862,AP7892,AP7863,AP7893,AP8861
Switched AP8661,AP7960,AP7990,AP8961
PDM3530L2130xxx 1 120V 30A (3)1P
Basic n/a
(1)5wire
NEMAL2130
Metered
AP8865
Switched AP8965
PDM3450CS50xxx 1 208V 50A (1)3P
(1)4wire
Basic
AP7568 AP7598 AP7569 AP7599 AP7567A AP7516
B
as
i
, , , , ,
CS50
Metered
AP7868,AP7898,AP7869,AP7899,AP7867A
Switched AP7968,AP7998
PDM3460IEC309xxx 1 208V 60A (1)3P
(1)4wire
Basic n/a
(3P+PE)
Metered
AP7866,AP7866A
IEC30960A
Switched n/a
PDM2330L6xxyyy 1 208 30A (1)2P
(1)3wire
Basic AP7541,AP9570,AP9571A
NEMAL630R
Metered
AP8841,AP7811
Switched
AP8641,AP8941,AP7911A
PDMNotes:
Input frequency: 50/60Hz
Certifications: UL Listed
The PDM3460IEC309-xxx PDMs use a 5-wire IEC 309 connector with a 9 o'clock ground position.
Unlessotherwisenoted,1cordPowerDistributionModulesareavailablewiththesecordlengths:
200,260,320,380,440,500,560,620,680,740,800,860,920,980,1040,1680
Unlessotherwisenoted,all3cordPowerDistributionModulesareavailablewiththesecordlengths:
Option1:PDMwith260,380,and500cmcables
option2:PDMwith680,860,and1040cmcables
Option3:PDMwiththree1680cmcables
.
TheAPCPowerDistributionModules(PDMs)specifiedinTable2areintendedforusein415VModularPDUs.TheycanbeinstalledinthefollowingAPCproducts:
APCModularPowerDistributionUnit
s
PDPM277H
PDPM288G6H
Table2:APCPowerDistributionModulesfor415VModularPDU
s
415VPowerDistributionModuleshavegraybussplateswhichmatchthegray415VPDUbackplane.ThesePDMsrequireone(1)ModularPDUslotposition
Module # cords Voltage Amperage
(Qty) Circuit
Breakers
(Qty)
Connector
Compatible APC
Rack PDUs APC Rack PDU SKUS
PDM1320IEC3Px 3 240V 20A (3)1P
Basic n/a
(3)3wire
IEC30920A
Metered
n/a
Switched n/a
PDM3520IEC309xxx* 1 240V 20A (3)1P
Basic
AP7557NA
(1)5wire
IEC309
Metered
AP8881
Switched AP8981
PDM3540IEC309xxx 1 240V 40A (3)1P
Basic n/a
(1)5wire
IEC309
Metered
AP7856x563
Switched
n/a
Notes:
PDM input frequency: 50/60Hz
PDM certifications: UL Listed
The PDM3520IEC309-xxx and PDM3540IEC309-xxx PDMs use a 5-wire IEC 309 connector with a 6 o'clock ground position.
Unlessotherwisenoted,1cordPowerDistributionModulesareavailablewiththesecordlengths:
200,260,320,380,440,500,560,620,680,740,800,860,920,980,1040,1680
Unlessotherwisenoted,all3cordPowerDistributionModulesareavailablewiththesecordlengths:
Option1:PDMwith260,380,and500cmcables
option2:PDMwith680,860,and1040cmcables
Option3:PDMwiththree1680cmcables
*PDM3520IEC309xxxisalsoavailablewith80and140cmcordlengths
/