SICK VICOTEC410 Operating instructions

Category
Measuring, testing & control
Type
Operating instructions
OPERATING INSTRUCTIONS
Installation
Operation
Maintenance
Front page
VICOTEC410
CO and Visibility Measuring Device
2 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
Document Information
Described Product:
Product name: VICOTEC410
Variants:
Document ID
Title: Operating Instructions VICOTEC410
Part No.: 8008981
Version: 2.0
Release: 2012-09
Manufacturer
SICK AG
Erwin-Sick-Str. 1 · 79183 Waldkirch · Germany
Phone: +49 7641 469-0
Fax: +49 7641 469-1149
E-mail: info.pa@sick.de
Original Documents
The English edition 8008981 of this document is an original docu-
ment of SICK AG.
SICK AG assumes no liability for the correctness of an unauthor-
ized translation.
Please contact the manufacturer or your local representative in
case of doubt.
Legal information
Subject to change without notice.
© SICK AG. All rights reserved.
Glossary
Skilled persons: Persons who, based on their technical training
and knowledge as well as knowledge of the relevant regulations,
can assess the tasks given and recognize the dangers involved.
Competent person: Persons who, based on their technical training
on, and knowledge concerning the specific device, as well as
knowledge of the relevant regulations, can assess the tasks given
and recognize the dangers involved.
Instructed person: Persons properly instructed on the tasks
assigned, possible risks and necessary protective measures.
VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG 3
Warning Symbols Warning levels / Signal words
DANGER
Risk or hazardous situation which will result in severe personal
injury or death.
WARNING
Risk or hazardous situation which could result in severe personal
injury or death.
CAUTION
Hazard or unsafe practice which could result in personal injury or
property damage.
NOTICE
Hazard which could result in property damage.
Information Symbols
Hazard (general)
Hazard by voltage
Important technical information for this product
Important information on electric or electronic func-
tions
Nice to know
Supplementary information
Link to information at another place
Contents
1 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
1 Important Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Main safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.1 A
uthorized personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.3 Prerequisite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.4 Correct handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.5 Avoiding consequential damage arising from device malfunctions . . . . . . . . . . . . . . 6
1.1.6 Environmentally acceptable behavior and disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2.1 Purpose of the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2.2 Installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Responsibility of user. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Additional documentation/information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1 Product identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Features of the VICOTEC410 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2.1 Method of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3 Device variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3.1 Standard components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3.2 Optional equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4 Functional principle/measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5 Special features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.1 Special device version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.6 Device components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.6.1 VICOTEC410 sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.6.2 Evaluation unit RCU410 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7 RCU interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7.1 RCU interfaces– standard version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7.2 RCU410 interfaces – Profibus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.8 Fog correction via the RCU410 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.9 Screening out fog on measuring points close to the portals . . . . . . . . . . . . . . . . . . . . . 13
2.10 Fog correction via control technology before the portals . . . . . . . . . . . . . . . . . . . . . . . . 14
3 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1 Project planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.1 Protection devices/protective measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3 Material required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4 Preparing the installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4.1 Overview of installation work. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.5 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6.1 Fitting the mounting brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.6.2 Installing the sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Contents
VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG 2
3.7 Installing the terminal boxes and connection unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.7.1 Fitting the terminal boxes (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.7.2 Fitting the connection unit to distant evaluation unit . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.8 Installing the evaluation unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.9 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.9.1 Connecting VICOTEC410 cabling variants. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.9.2 Connecting the VICOTEC410 sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.10 Evaluation unit connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.10.1 Evaluation unit as standard version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.10.2 Evaluation unit connections - PROFIBUS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4Start-up / Switching on. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.1 Necessary technical knowledge for start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.2 Safety information on start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.3 Preparing for start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.4 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.4.1 Function buttons and menu overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.4.2 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.5 Commencing start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.5.1 1st step: Power supply ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.5.2 2nd step: Setting VICOTEC410 parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.5.3 Fog correction with additional VICOTEC411 measuring point close to portal . . . . 45
4.5.4 Connecting the PROFIBUS during start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4.5.5 Call up Parameter mode in the Profibus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.5.6 Zero adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.6 Function test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5.1 Authorized persons/access protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.1.1 Recognizing an unsafe operating state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.2 Standard procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.2.1 Checking malfunction displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
5.3 Menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
5.4 Status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6Shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.1 Technical knowledge necessary for shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.2 Safety information on shutting down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.3 Shutdown preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.4 Switch-off procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.5 Switching the device off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.6 Protective measures for the shutdown device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.6.1 Measures for short-term shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.6.2 Measures for long-term storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.7 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.8 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Contents
3 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.1 VICOTEC410 maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.1.1 Maintenance planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.2 Maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7.2.1 Cleaning the sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7.3 Spare Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.3.1 Recommended spare parts for 2 years operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8 Clearing Malfunctions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.1 VICOTEC410 malfunction handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.1.1 Troubleshooting and clearing malfunctions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
8.1.2 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.1.3 Further tips on troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.1.4 Sensor values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
9 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
9.1 Compliances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.1.1 Electrical protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.1.2 Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.1.3 Laws, standards, guidelines complied with . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.2 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.2.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.2.2 Dimensions, VICOTEC410 sensor and evaluation unit . . . . . . . . . . . . . . . . . . . . . . . . 78
9.2.3 Dimensions, connection unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
10 Important Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
10.1 Main safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
10.1.1 Authorized personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
10.1.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
10.1.3 Prerequisite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
10.1.4 Correct handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
10.1.5 Avoiding consequential damage arising from device malfunctions . . . . . . . . . . . . . 82
10.1.6 Environmentally acceptable behavior and disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . 82
10.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
10.2.1 Purpose of the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
10.2.2 Installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
10.3 Responsibility of user. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
10.4 Additional documentation/information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Important Information
VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG 6
Subject to change without notice
VICOTEC410
1 Important Information
Main safety information
Main operating information
Intended use
Own responsibility
7 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
Important Information
Subject to change without notice
1.1 Main safety information
1.1.1 Authorized personnel
Persons responsible for safety must ensure the following:
All work on device parts is carried out by qualified personnel only. Qualified persons are
those who, based on their training, experience or instruction as well as their knowledge
of relevant standards, regulations, accident prevention rules and plant conditions, are
authorized by those responsible for safety for personnel and the plant to carry out such
work. It is decisive that these persons can recognize and avoid possible hazards in a
timely manner.
Skilled persons are persons according to DIN VDE 0105 or IEC 364 or directly compara-
ble standards such as DIN 0832.
These persons have adequate knowledge through training
These skilled persons have the delivered Operating Instructions as well as the associ-
ated system documentation available during all work, and observe these documents
with regard to avoiding hazards and damage.
Contact the manufacturer before using this measuring device for other purposes where the
device functionality cannot be judged properly within such applications.
1.1.2 Intended use
The VICOTEC410 measuring system and its system components are only to be used for
measuring visibility and/or CO concentrations in road tunnels.
1.1.3 Prerequisite
All planning, assembly, installation, start-up, maintenance and repair work must be carried
out by adequately instructed personnel only and checked by the responsible skilled per-
sons.
1.1.4 Correct handling
Use the system in accordance with the technical data and specifications regarding per-
missible usage, assembly, connection, ambient, and operating conditions (refer to the
order documents, device user information (type plates etc.), as well as the documenta-
tion supplied with the system).
Persons carrying out the work must be aware of, and observe general assembly and
safety regulations,
Act according to local, system-specific conditions and risks arising from technical oper-
ating and regulations, in particular local road safety regulations.
Ensure proper use of tools and hoist and transport equipment.
Provide sufficient protection devices and personal safety equipment and ensure that
these are used by the personnel.
Secure system components delivered without a degree of protection with effective pro-
tection devices on-site.
Observe all measures necessary for conservation of value, e.g. during transport and
storage and/or maintenance and inspection.
Important Information
VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG 8
Subject to change without notice
1.1.5 Avoiding consequential damage arising from device malfunctions
In order to avoid malfunctions that can lead to direct or indirect person or property dam-
age, the operator must ensure:
Personnel responsible for maintenance can be informed at any time and as quickly as
possible.
Maintenance personnel are trained to be able to respond to malfunctions on the
VICOTEC410 and to react correctly to related operational malfunctions.
Defective operating resources are switched off immediately in case of doubt.
That switching off does not lead directly to subsequent malfunctions.
Switching outputs “Data valid” for CO and VIS are wired correctly and are processed in
the control station without having to close the tunnel.
1.1.6 Environmentally acceptable behavior and disposal
Observe applicable waste disposal regulations to protect the environment.
Sensor subassemblies are easy to dismantle and disposed of as waste.
Sensor outer housing, optics chassis and brackets are made of aluminium and can be
recycled.
1.2 Intended use
1.2.1 Purpose of the device
Operate the VISOTEC410 visibility/CO measuring device as specified by the manufacturer,
i.e. only use the VICOTEC410 measuring system and its system components to measure
visibility and/or CO concentrations in road tunnels.
1.2.2 Installation location
The opto-electronic VICOTEC410 measuring device supports continuous, delay-free mea-
surement of visibility and CO concentrations in road tunnels. The sturdy, compact sensors
are designed as contact-free, direct in-situ measuring devices.
.
NOTICE: Procedure when cleaning the tunnel
Switch the VICOTEC system to operating mode “Maintenance”
Be sure to cover sensor tubes with closure caps
Never touch sensors directly with washing brushes (risk of modifying
optical alignment which can cause a device malfunction)
After cleaning, check the optical interfaces of the sensors for contami-
nation; when necessary, clean the optical interfaces in accordance with
maintenance regulations, see p. 62, §7.2.1.
NOTICE: Suitable disposal!
Do not dispose of electronic components from VISOTEC410 system compo-
nents as household waste. Dispose of these components in a suitable facil-
ity.
9 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
Important Information
Subject to change without notice
1.3 Responsibility of user
These Operating Instructions serve understanding the function, and explain assembly,
installation and maintenance work as well as how to operate the VICOTEC410. Other docu-
ments may contain more detailed information but can never replace these Operating
Instructions.
Target groups of this document
SICK Service technicians or trained customer personnel; qualified technicians/engi-
neers - with excellent device knowledge
Operators. customer installation personnel, technicians for measurement and control
technology, electric, electronics - with basic device knowledge
Correct use
Only use the device as described in these Operating Instructions (--> page 44). The
manufacturer bears no responsibility for any other use.
Carry out the specified maintenance work.
Do not remove, add or change any components in or on the device unless such changes
are officially allowed and specified by the manufacturer. Otherwise any warranty by the
manufacturer becomes void.
Special local conditions
Follow all local laws, regulations and company-internal operating directives applicable
at the installation location.
Keeping documents
These Operating Instructions:
Must be available for reference.
Must be passed on to new owners.
1.4 Additional documentation/information.
Check the contents of the CD delivered with the product (PN:2058621).
Read the Operating Instructions before starting the work! Observe all warning
information exactly!
Product Description
VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG 10
Subject to change without notice
VICOTEC410
2 Product Description
Product identification
Functional principle
Characteristics
Variants
11 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
Product Description
Subject to change without notice
2.1 Product identification
The type plate is located
Sender or reflector/receiver unit: On the back of the housing.
RCU410: On the right outer side of the housing.
2.2 Features of the VICOTEC410
Simultaneous and single visibility and CO concentration measurement
Comfortable operation via a menu-controlled graphic display on the evaluation unit
Automatic adjustment function (AutoAdjust) for simple start-up
Minimum effort for installation, start-up and maintenance.
The option of simultaneous as well as single visibility and CO concentration measurement
opens up flexible application possibilities for the VICOTEC410, such as:
Monitoring short tunnel sections or underpasses with one measuring point
Monitoring longer tunnel sections
Integrating a fog sensor for each tunnel portal (max. 2 fog sensors)
Fig. 1 VICOTEC410 system layout
Product name: VICOTEC410
Product variants:
VICOTEC411 (VIC411), VICOTEC412 (VIC412), VICOTEC414
(VIC414)
Firmware version: Program RCU410 (9054915 Version O362)
Manufacturer:
SICK AG
Erwin-Sick-Str. 1 · 79183 Waldkirch · Germany
Fog sensor
V
isibility,
CO concentr
ation
Tunnel lenght
Dis
tance*
Fog sensor
VICOTEC410 standard device
Control center (provided by customer)
Ventilation system
Product Description
VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG 12
Subject to change without notice
2.2.1 Method of operation
The VICOTEC410 operates independently.
The measuring principles used support extensive options for excellent self-monitoring
When a malfunction occurs, the VICOTEC410 switches automatically toMalfunction
mode. The analog outputs are set to the parameter value set for malfunctions, “Live
zero”, or the last valid value.
Operating states are signaled by status signals and entered in a logbook.
Each sensor pair of a measuring point has one or two opto-electronic measuring devices
that deliver, independent of each other, visibility and/or CO concentration measured val-
ues. The CO measuring unit (IR unit) comprises an infrared sender and an infrared receiver.
The visibility measuring unit (VIS unit) is arranged in parallel and comprises a sender/
receiver unit and a triple reflector.
2.3 Device variants
2.3.1 Standard components
Sensor pair (sensor “left”, “right”)
Control unit RCU410
2 mounting brackets
Extension cable, 12 m, 6 pole; plug and socket C16-1
Connection cable, 2 m for sensor - control unit connection
Fig. 2 Device versions
Sensor “left” Sensor “right”
Evaluation unit RCU410
Type plate
Table 1
Device variants Measuring task
VICOTEC411 Single visibility measurement
VICOTEC412 Single CO concentration measurement
VICOTEC414 Simultaneous visibility and CO concentration measurement
13 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
Product Description
Subject to change without notice
2.3.2 Optional equipment
The VICOTEC410 can also be configured with
1 terminal box, “sensor left
1 terminal box, ”sensor right”
Connection unit with separate voltage supply (230 V AC); allows locating the RCU410
up to 1000 m away (CAN bus)
Repeater for RS422
Additional prefabricated connection cables:
1 connection cable, 1 m for sensor - evaluation unit connection
1 extension cable, 24 m, 6 pole; plug and socket; C16-1, to connect both sensors
2 mounting brackets incl. fixing accessories in material 1.4529 or 1.4571
Plastic separator plate for using the stainless steel consoles
Surge protection elements
2.4 Functional principle/measuring principle
Visibility measuring principle: Transmission measurement (NDIR), auto-collimation
method
CO concentration measuring principle: Negative gas correlation
2.5 Special features
Sturdy design proven in hundreds of tunnels
Long optical measuring distance (2 x 10 m) for exact measured value recording and
simple installation, even in curves, as well as easy alignment
Automatic contamination compensation on visibility and CO measuring channel
Simple and fast check of all measured variables possible using closed gas cells (CO) or
neutral density glasses (visibility)
Early alarm for maintenance request (contamination) for optimized maintenance cycle
planning
Effective dust protection tubes, heated reflector and thermal insulation allow typical
maintenance intervals of 1 year
2.5.1 Special device version
The VIC412 (Individual measurement of CO-concentration) is also available in a 20 m
version. The measuring distance can be adjusted from 19,5 to 20,5 m.
There is no difference to the standard device with regards the optical alignment and opera-
tion of the device.
Device type: VIC412-22S07 material-no. 1054383
The 20 m - measuring distance is only available for the version VIC412 .
Product Description
VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG 14
Subject to change without notice
2.6 Device components
2.6.1 VICOTEC410 sensors
Fig. 3 Sensor versions
2.6.2
Evaluation unit RCU410
Each measuring device has an evaluation unit (Remote Control Unit), the RCU410. The
RCU410 provides the recorded measured data as analog and digital signals and performs
the following functions:
Measuring system operation
Measuring and status signals evaluation and output
Sensor voltage supply
2.7 RCU interfaces
2.7.1 RCU interfaces– standard version
3 relays:
VIS malfunction
–CO malfunction
–Service/Dust/Warning
2 analog outputs
VIS: 0 ... 20 mA; Live-Zero: 4 mA
CO: 0 ... 20 mA; Live-Zero: 4 mA
1 digital input
Service switch
The RCU410 also has an RS422 interface (electrically isolated) on which all measured
data are made available with status messages.
Sensor “left”
VICOTEC 411: VIS reflector
VICOTEC 412: CO sender
VICOTEC 414: VIS reflector/CO sender
Sensor “right”
VICOTEC 411: VIS sensor
VICOTEC 412: CO receiver
VICOTEC 414: VIS sensor/CO receiver
Visor
Dust protection tube
Sensor housing Optical visor
15 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
Product Description
Subject to change without notice
2.7.2 RCU410 interfaces – Profibus
1 digital input
Service switch
Interfaces
–PROFIBUS interface
RS422 interface
Fig. 4 RCU410 evaluation unit
2.8 Fog correction via the RCU410
VICOTEC411s are installed just as fog sensors at a maximum distance of 10 m from the
portals. These are connected to the VICOTEC4xx measuring points (tunnel sensors) via an
RS422 bus circuit. An RCU410 declared as Master then corrects the measured values of
the tunnel sensors when fog exists so that no fog is suctioned in. Details on parameter set-
tings, see p. 45, §4.5.2.
2.9 Screening out fog on measuring points close to the portals
Apart from the possibility of detecting fog and taking appropriate measures, SICK also
offers a device that does not record fog as visibility factor (e.g. VISOTEC450). This device is
used preferably at those measuring points closer than 300 m from a portal. This prevents
fog being assessed as visibility factor and initially avoids erroneous switching to suction in
fresh air.
RCU4 10
Evaluation Unit
7
120.3
Measuring
T=150 oC
T=25 ºC
150
7
CO
VIS
ppm
1/km
0
120.3
Measure
Graphic display for meas-
ured value display and
navigation
Cutout in housing cover (to
show operating elements)
Keypad for
operating the
VICOTEC410
LED status indicators
Front panel with operating
elements (behind glass cover)
Product Description
VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG 16
Subject to change without notice
2.10 Fog correction via control technology before the portals
If visibility distance measuring devices (e.g. VISIC620 from SICK) are used before the por-
tals, it is recommended to design ventilation control so that fresh air is only suctioned into
the tunnel when it can be expected that this will improve visibility or when necessary to
maintain other limit values (NO2, CO,..). An improvement in the visibility distance can then
be expected when the visibility in the tunnel (heat transmission coefficient - HTC) is much
worse than the heat transmission coefficient to be expected when suctioning in fog. In this
case, it is important to observe that a larger volume of condensation crystals is inside the
tunnel than outside the tunnel which thickens any fog suctioned into the tunnel. This effect
cannot be calculated beforehand so it is recommended modeling this in the control with an
adjustable variable (referred to here as “Delta heat transmission coefficient”) so that it can
be adapted during the tunnel operation test phase. The following Table provides assistance
for converting visibility distance into a heat transmission coefficient in stages without hav-
ing to use a complex mathematic formula. Detailed consultation can be requested from the
local SICK contact person.
This fog correction method has the advantage that measured values in the tunnel always
reflect the actual visibility. This ensures a warning or closure when visibility is poor.
Table 2 Visibility distance to heat transmission coefficient conversion Table
Visibility distance
As HTC converted visi-
bility distances
Delta HTC (only as an
example here)
HTC expected in the
tunnel
900 m 3.3/km 2/km 5.3/km
800 m 3.75/km 2/km 5.75/km
700 m 4.3/km 2/km 6.3/km
600 m 5/km 2/km 7/km
500 m 6/km 2/km 8/km
450 m 6.7/km 2/km 8.7/km
400 m 7.5/km 2/km 9.5/km
350 m 8.6/km 2/km 10.6/km
300 m 10/km 2/km 12/km
250 m 12/km 2/km 14/km
17 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
Product Description
Subject to change without notice
Installation
VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG 18
Subject to change without notice
VICOTEC410
3 Installation
Project planning
Transport
Setup
Installation
Initial start-up
19 VICOTEC410 · Operating Instructions · 8008981 V2.0 · © SICK AG
Installation
Subject to change without notice
3.1 Project planning
3.2 Safety information
The following symbols are used in these installation instructions for important safety infor-
mation for the user. The symbols are located exactly where required within the Sections.
Safety information, especially warnings, must be observed and followed.
3.2.1 Protection devices/protective measures
3.3 Material required
Table 3 Materials and Part Nos. for assembly
3.4
Preparing the installation location
Secure the place of work
Provide adequate light, power and a jack lift at the place of work
Provide fixing accessories, suitable drills and tips, circuits, socket wrench set, torque
wrench, marking material, measuring tools, spirit level.
DANGER: Hazards through electrical equipment
VICOTEC410 system components are operating resources for use in industrial
high-voltage systems. These operating resources have parts that are danger-
ous, live and possibly not insulated during installation, start-up and operation.
Unauthorized removal of required covers, incorrect usage or operation or inad-
equate maintenance of system components referred to above can cause
severe health or material damage.
WARNING: Preventive measures for operating safety
If the VICOTEC410 is used as a sensor in combination with a control system,
the operator must ensure that a failure or device malfunction on the
VICOTEC410 cannot cause unallowed damage or hazardous operating states,
or states that can endanger or obstruct traffic.
Material required Part No.
Assembly kit for mounting brackets for VICOTEC32x, 41x, dowels and
screws made of stainless steel 1.4571
2045457
Assembly kit for mounting brackets for VICOTEC32x, 41x, dowels and
screws made of stainless steel 1.4529
2045458
Insertion tool for stainless steel dowel, M12 5601225
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88