NobelCom FAC/D-DP User manual

Type
User manual

The NobelCom FAC/D-DP is an automatic filter designed to treat raw water from municipalities or wells. It effectively removes impurities, chlorine, and organic substances, providing clean and safe water for various applications. Here is a brief overview of its capabilities:

  • Filtration: The filter utilizes quartz sand and activated carbon to effectively remove suspended solids, dirt, and other impurities from the water.

  • Activated Carbon: The activated carbon in the filter adsorbs chlorine, organic substances, and other contaminants, improving the taste, smell, and overall quality of the water.

The NobelCom FAC/D-DP is an automatic filter designed to treat raw water from municipalities or wells. It effectively removes impurities, chlorine, and organic substances, providing clean and safe water for various applications. Here is a brief overview of its capabilities:

  • Filtration: The filter utilizes quartz sand and activated carbon to effectively remove suspended solids, dirt, and other impurities from the water.

  • Activated Carbon: The activated carbon in the filter adsorbs chlorine, organic substances, and other contaminants, improving the taste, smell, and overall quality of the water.

rev. 2
Page 1 of 21
fcd-dp_mi-r2.doc
AUTOMATIC FILTERS WITH
DIFFERENTIAL PRESSURE
CONTROL SERIE : FC/D-DP
FAC/D-DP
FC/D-DP-DUAL
FAC/D-DP-DUAL
INSTRUCTIONS MANUAL
WARNING!
The equipment must be used only for the utilization for which they have been
designed, as shown in the technical documentation.
Read carefully this leaflet until the end before starting any operation.
Proceed strictly according to all directions included in this manual.
Automatic filters series FC/D and FAC/D are designed to treat raw water supplied from
municipalities or from well.
ANY OTHER APPLICATIONS OF THE EQUIPMENT DIFFERENT THAN THE MENTIONED
ONES IS MADE UNDER THE ONLY RESPONSIBILITY OF THE USER.
For any assistance concerning the installations, maintenance or utilization of the equipment
apply the NOBEL Service Center closest to you or directly :
NOBEL S.r.l. via Monfalcone 8 – I-20132 Milano
tel. +39 02 2827968 fax +39 02 2610839
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 2 of 20
fcd-dp_mi-r2.doc –
r.2
INDEX
1.Safety .........................................................................................................................................................3
1.1.General.................................................................................................................................................3
1.2.How to displace the unit .......................................................................................................................3
1.3.Hydraulics ............................................................................................................................................3
1.4.Electrical...............................................................................................................................................3
1.5.How to store and delivery.....................................................................................................................3
2.Principles of working ..................................................................................................................................4
2.1.Quartz-sand filters FC/D ......................................................................................................................4
2.2.Activated-carbon filters FAC/D.............................................................................................................4
3.Technical characteristics ............................................................................................................................5
3.1.Assumed raw water characteristics .....................................................................................................5
3.2.Technical characteristics (general) ......................................................................................................5
3.3.Characteristics for each model ............................................................................................................5
3.4.Dimensions ..........................................................................................................................................6
3.5.Weights ................................................................................................................................................6
4.Installation ..................................................................................................................................................7
4.1.How to remove packaging ...................................................................................................................7
4.2.How to move and lift the unit................................................................................................................7
4.3.Placing & commissioning .....................................................................................................................7
4.4.Hydraulic connections ..........................................................................................................................8
4.5.How to load the media filter..................................................................................................................9
4.6.Electrical wiring connections................................................................................................................9
5.End cycle and regeneration......................................................................................................................10
5.1.End cycle............................................................................................................................................10
5.2.Regeneration......................................................................................................................................10
5.3.Inhibit of the regeneration ..................................................................................................................11
CONTROL PANEL ......................................................................................................................................12
6.1.Functions of the logical programmer..................................................................................................12
6.2.Signals on the display of the programmer .........................................................................................13
6.3.How to use the buttons function of the programmer..........................................................................13
7.SETTINGS................................................................................................................................................14
7.1.How to set current time and day of the week.....................................................................................14
7.2.How to set day and time of regeneration ...........................................................................................14
7.3.How to set time of phases, delay, pressure drop value .....................................................................15
7.4.Factory set..........................................................................................................................................16
8.Starting-up ................................................................................................................................................17
9.SERVICE & MAINTENANCE ...................................................................................................................18
9.1.Media filter, nozzles ...........................................................................................................................18
9.2.Disposal..............................................................................................................................................19
10. MAIN COMPONENTS...........................................................................................................................19
11. TROUBLE-SHOOTING GUIDE ............................................................................................................20
Annex
DRAWING 1: dimensions WIRING DIAGRAM
DRAWING 2: components models
FC05/D÷FC11/D, FAC05/D÷ FAC11/D
running test certificate
DRAWING 3: components models
FC15/D÷FC80/D, FAC15/D÷FAC60/D
solenoid valves manual
DRAWING 4: installation models
FC05/D÷FC11/D, FAC05/D÷ FAC11/D
diaphragm valves manual
DRAWING 5: installation models
FC15/D÷FC80/D, FAC15/D÷FAC60/D
DRAWING transducers installation
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 3 of 21
fcd-dp_mi-r2.doc –
r.2
1. Safety
1.1. General
The equipment has been designed and constructed according to D.P.R. n° 459 of 24th July
1996 (regulation for accomplishment of Norms 98/37/CEE, 91/368/CEE, 93/44/CEE and
93/68/CEE regarding the unification of States members laws in so far as machines are
concerned).
It has been designed and constructed according to European Norms UNI EN 292-1, UNI EN
292-2, UNI EN 292-2/A1, UNI EN 983, CEI EN 60439-1, CEI EN 60 204-1.
Only authorized and skilled personnel will be allowed to carry out installation, start up as well
as routine and planned maintenance.
1.2. How to displace the unit
Particular care and attention should be put in during moving and displacing of heavy items, in
order to avoid injuries to persons or damage (see § 3.5 pag. 6). The heavy parts must be lifted
and displaced always hooking and lifting them by the points shown on the drawings (see fig. 1)
and using only suitable ropes, hooks and/or chains, according to the weight (see weight table).
1.3. Hydraulics
All operations must be performed by and/or under direct supervision of skilled and authorized
operators, using proper tools and personal protection devices if required (CE marked).
Before any operation of taking out pipes or part of hydraulic system, it is required to release
the pressure inside and empty the part of the system.
1.4. Electrical
Before starting any operation on electrical devices, be sure that main power supply is OFF.
All operations must be performed by skilled and authorized operators.
In case of liquid leakage, switch off the main power supply before operate. Before the
switching ON, be sure all the parts of the system are perfectly dry. Check that the available
electrical power is correct before connection. Do not make preliminary wiring connections.
1.5. How to store and delivery
t = ºC
t = ºF
humidity rel.
notes
closed rooms
5÷45 41÷113 5÷95%
without condensate
open space
5÷45 41÷113 5÷95%
without condensate
protect from sun-light and rain.
transport
5÷45 41÷113 5÷95%
without condensate
protect from sun-light and rain.
installation
5÷45 41÷113 5÷95%
without condensate
protect from sun-light and rain.
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 4 of 21
fcd-dp_mi-r2.doc –
r.2
2. Principles of working
FC/D and FAC/D series filters are used for water treatment for residential and industrial
applications as well. All the materials are food grade and approved for drinking water.
2.1. Quartz-sand filters FC/D
The filtration through a sand media is a mechanical process that allows to remove suspended solids
(even of small dimensions) from water.
The slower is the linear flow (speed of water trough the filtering bed), the better is the filtration action.
During the process, as the filtering bed traps the suspended particles, as filtration action increases,
since the trapped solids works the same way of a filtering bed!
But it also increases the resistance of the filtering bed against the water flow; so the pressure drop
between inlet and outlet increases as well.
The maximum allowed pressure drop is 1 bar (100 kPa), after that it is required to backwash the
filtering bed.
The purpose of the backwashing is to re-built the filtering bed efficiency, by removing the solids
trapped during service; it is featured by a counter-flow of water through the filtering bed.
The programmer allows to set the regeneration according to the max allowable pressure drop across
the filter and/or at pre-set time and days.
For the best working of the filter, the backwashing must be featured before the pressure drop
reaches the threshold level (1 bar - 100 kPa).
During regeneration the water supplying is completely inhibited by means of a membrane valve
mounted on the outlet line.
2.2. Activated-carbon filters FAC/D
Filtration through a bed of activated carbon is the process that allows to remove organic matters and
chlorine from water.
The lower is the flow rate, the better is the filtration action.
FAC/D series filters are designed and sized for chlorine removal. The expected life of activated-
carbon used as de-chlorination (chlorine removal) is very long; it works as chemical reduction of chlorine
to chloride ion.
Activated carbon action is not selective in removing the substances contained in water and crossing
the filtering bed: hence, it removes also the organics the water contains, if any.
Therefore, it could happen that the filtering bed is exhausted or clogged by the trapping of substances
contained in water, even if the purpose of treatment was not the removal of these substances, but just the
de-chlorination.
Furthermore, it could happen that the filtering bed releases some of the substances previously trapped
in higher concentration than before.
Since it is quite impossible to forecast the exhaustion of the activated carbon bed, or to monitor the
exhaustion itself, with current instrumentation, the utilization of an activated carbon filter must be strictly
avoided without adequate pre-treatments, like quartz-sand filtration, chlorination, etc.
Whether raw water contains organics and/or is biologically polluted, FAC/D series filters CANNOT be
used without written authorization by NOBEL Technical Department.
The activated-carbon bed also works as a mechanic filter same way of quartz-sand bed.
Although this working should be avoided, it can happen that the pressure drop of activated-carbon bed
reaches a value of 1 bar (100 kPa); in this case the backwashing of the filtering bed is required.
The programmer allows to set the regeneration according to the max allowable pressure drop across
the filter and/or at pre-set time and days.
For the best working of the filter, the backwashing must be featured before the pressure drop
reaches the threshold level (1 bar - 100 kPa).
It is recommended to run the regeneration only when it is strictly required: the backwashing causes
the mixing of the bed and could displace the higher layers of activated carbon (most polluted) from the
top to the bottom of the column.
During regeneration the water supplying is completely inhibited by means of a membrane valve
mounted on the outlet line.
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 5 of 21
fcd-dp_mi-r2.doc –
r.2
3. Technical characteristics
3.1. Assumed raw water characteristics
water temperature (min÷max)
ºC (ºF) 5÷40 (41÷104)
water pressure (min÷max)
bar (kPa) 1.5÷8.0 (150÷800)
3.2. Technical characteristics (general)
power supply
V ph/Hz W 110÷240 1/50÷60 30
regeneration time
min. 20÷30
p min/max
bar (kPa) 0.2÷1.0 (20÷100)
3.3. Characteristics for each model
MODEL
connections
flow m³/h
backwashing water consumption
IN/OUT drain
operating max
backwash
liters
FC05/D
1¼" 1" 3.2 6.5 4.8 1600
FC08/D
1½" 1¼" 4.0 8.0 6.0 2000
FC11/D
1½" 1¼" 5.7 11.0 8.5 2850
FC15/D
2" 1½" 7.8 15.0 11.0 3900
FC20/D
2" 1½" 10.0 20.0 15.0 5000
FC25/D
2½" 2" 13.0 26.0 20.0 6500
FC30/D
DN80 2½" 16.0 32.0 24.0 8000
FC40/D
DN80 2½" 20.0 40.0 30.0 10000
FC45/D
DN80 2½" 23.0 46.0 35.0 11500
FC50/D
DN100 DN80 27.0 53.0 40.0 13500
FC60/D
DN100 DN80 31.0 62.0 46.0 15500
FC70/D
DN100 DN80 35.0 70.0 53.0 17500
FC80/D
DN100 DN80 40.0 80.0 60.0 20000
MODEL
connections
flow m³/h
backwashing water consumption
IN/OUT drain
max
backwash
liters
FAC05/D
1¼" 1" 5.0 3.0 500
FAC08/D
1½" 1¼" 8.0 4.8 800
FAC11/D
1½" 1¼" 11.0 6.6 1100
FAC15/D
2" 1½" 15.0 9.0 1500
FAC20/D
2½" 2" 20.0 12.0 2000
FAC25/D
2½" 2" 24.0 14.4 2400
FAC30/D
DN80 2½" 30.0 18.0 3000
FAC40/D
DN80 2½" 40.0 24.0 4000
FAC50/D
DN100 DN80 48.0 28.8 4800
FAC60/D
DN100 DN80 61.0 36.6 6100
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 6 of 21
fcd-dp_mi-r2.doc –
r.2
3.4. Dimensions
See DRAWING 1 dimensions
3.5. Weights
WEIGHT
MODEL vessel quartz-sand kg
anthracyte shipping on service
kg 04÷07 mm 1÷2 mm 2÷3 mm l (kg) approx. kg approx. kg
FC05/D
135 100 50 35 40(28) 380 600
FC08/D
150 120 60 50 50(35) 460 700
FC11/D
180 200 80 50 70(49) 600 1000
FC15/D
300 250 100 100 100(70) 900 1400
FC20/D
340 300 150 100 130(91) 1050 170
FC25/D
390 400 200 150 150(105) 1350 2100
FC30/D
435 500 200 200 200(140) 1600 2600
FC40/D
550 600 300 200 250(175) 2000 3100
FC45/D
610 700 350 250 300(210) 2300 3600
FC50/D
670 800 400 300 350(245) 2600 4200
FC60/D
740 900 450 350 400(280) 2900 4800
FC70/D
870 1100 500 400 450(315) 3400 5500
FC80/D
1100 1250 600 450 500(350) 4000 6400
WEIGHT
MODEL vessel
quartz-sand
1÷2 mm
activated
carbon
shipping on service
kg kg l (kg) approx. kg approx. kg
FAC05/D
150 30 200(96) 300 500
FAC08/D
180 50 280(134) 400 700
FAC11/D
300 50 350(168) 560 900
FAC15/D
340 75 500(240) 700 1300
FAC20/D
390 100 650(312) 900 1600
FAC25/D
435 100 800(463) 1000 1900
FAC30/D
550 150 1000(480) 1300 2400
FAC40/D
670 200 1350(648) 1700 3200
FAC50/D
740 250 1600(768) 2000 3700
FAC60/D
1100 300 2000(960) 2600 4800
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 7 of 21
fcd-dp_mi-r2.doc –
r.2
4. Installation
4.1. How to remove packaging
The vessels are shipped wrapped in a plastic foil; remove it with care before starting-up.
Keep the cards and everything contained inside the packaging.
The media filter are shipped as separated:
in bags of 25 kg (35 liters approx) each or fraction anthracite
in bags of 25 kg each or fraction quartz sand
in bags of 25 kg (50 liters approx) each or fraction activated carbon
4.2. How to move and lift the unit
The vessels can be displaced when they are empty, hooking and lifting by the special rings
mounted on the upper part of the vessels (see fig. 1). It is recommended to use proper sized
hooks and ropes, according to the weight. It is also possible to hook and lift the vessel by the
bearing legs.
4.3. Placing & commissioning
Place the unit according to the available room of the site and the required room for current
maintenance and service of the equipment. See the dimensional drawing.
Place the column of media filter on a perfectly flat surface. See the dimensional drawing
concerning the placing of the unit according to the walls of the site and required room for
maintenance and service. The shown scheme is only suggested; the column can be placed
in different positions; according to the inlet/outlet connections on the valve groups.
Fix the valves manifold to the vessel (see installation drawing)
Fix the control board to the valves manifold
DUAL arrangement only :
Repeat the same operations for both columns; yet, the control panel is only one for both
columns and must be fixed on column A (see installation drawing).
GOLFARI
H
OO
KIN
G
GAMBE DI SOSTEGNO
LE
GS
CAUTION : DO NOT LIFT OR MOVE THE UNIT HOOKING OR
CATCHING BY THE PRE-ASSEMBLED PARTS.
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 8 of 21
fcd-dp_mi-r2.doc –
r.2
4.4. Hydraulic connections
(see DRAWINGS installation and components)
In order to avoid shut-off during maintenance operations, an emergency by-pass line
should be provided
Complete the line from inlet fittings to the raw water line.
Complete the line from outlet fittings (valve V2) to the treated water line.
Connect the drain valves (V1 and V5) to a floor drain. The gate valve mounted downstream
of the valve V5 will be used to adjust the backwash flow rate.
A common flexible pipe made in plastic or rubber can be used for the drain line; its diameter
must be of at least one size larger of the one mentioned on “CHARACTERISTICS FOR
EACH MODEL” table.
It is suggested the drain line could be inspected in order to check quantity and quality of
drain water, as well as any leakage of media filter from the unit.
Connect the inlet air fitting, placed on the base manifold of the solenoid valves, to a
compressed air-mains, complete with pressure reducer, dehumidifier filter and shut-off valve.
The air pressure must be kept at value equal or higher of the pressure of water to be treated,
with max value of 8.0 bar.
Whether water is used to pilot the valves, the inlet fitting of the base manifold of the solenoid
valves must be connected to the pilot water fitting (¼"), pre-arranged on the inlet manifold of
the column; run to the drain a pipe from the drain fitting (¼") of the base manifold of the
solenoid valves.
Complete the line between the outlet fitting of each solenoid valve to the correspondent
membrane valve:
SOLENOID VALVE MEMBRANE VALVES
Solenoid
v. no.
TYPE no. TYPE
1NC V1 NC
2NC V2 NA
3 NC V3-V4-V5 NC-NA-NC
All the solenoid valves can be hand-driven by the lever placed at the base of each of them; the
turning of the lever simulate the action of the coil. Then, for valves NC type, the valve is closed
when the lever is on parallel to the base; it is opened when the lever is on perpendicular to the
base itself.
DUAL arrangement only :
the hydraulic connections must be made for both columns
each group of pilot solenoid valves (E1A-E2A-E3A / E1B-E2B-E3B) is coupled to its own
filtering columns (A/B)
put in the 2 pressure sensors on the inlet and outlet manifolds of the 2 columns (see
transducers drawing)
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 9 of 21
fcd-dp_mi-r2.doc –
r.2
4.5. How to load the media filter
The media filter must be loaded inside the vessel afterthat the placing of the filter is
completed or in the case the media have to be replaced.
Open both the side man-holes
Check that the filter nozzles are correctly fixed and not damaged.
Load the supplied quartz-sand (2-3 mm size for FC/D filters, 1-2 mm size for FAC/D filters)
into the vessel, through the lower man-hole, until the sand covers completely the filter-
nozzles. Make a flat surface of the sand using a wooden tool, in order to avoid any damage
to the coating of the vessel.
Close the man-hole, after checking the integrity and correct position of the gasket, by
tightening the nuts.
Load the rest of supplied media filter into the vessel, through the upper man-hole (or through
the upper head, see components drawing). The media filter are shipped separately; check
that the shipped and available quantity complies exactly with the quantity listed in the Weight
Table (see § 3.5 pag. 6).
Filtering media must be loaded, one after the other one, and according to the following order:
quartz sand 2÷3 mm (only for filters FC)
quartz sand 1÷2 mm
quartz sand 0.4÷0.7 mm (only for filters FC)
anthracite (only for filters FC)
activated carbon (only for filters FAC)
Take care to make a flat surface of each layer of sand, before load the next one.
After completed the loading, close the upper man-hole (or upper head), after checking the
integrity and correct position of the gasket, by tightening the nuts
4.6. Electrical wiring connections
Make the electrical wiring connections inside the control panel, as below explained (see also
WIRING DIAGRAM).
o o Power supply 110÷240V, 50÷60 Hz directly to the clamps of the main switch
ooGND
o + o pressure inlet trasducer P-IN
o - o " " "
o 6 o " " "
o + o pressure outlet trasducer P-OUT
o - o " " "
o 7 o " " "
A free voltage contact for remote segnalation of running regeneration (max 1 A, max 24 V) is
also available, directly on the output Q4 of the programmer.
DUAL arrangement only :
the free voltage contact of output Q4 of the programmer reports the running regeneration of
column A, while the running regeneration of column B is reported by free voltage contact of
output Q4 of expansion card
It is also possible to inhibit the starting of regeneration by mean of a free voltage external
contact. It will be connected to one of any clamp + and the input I2 of the programmer.
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 10 of 21
fcd-dp_mi-r2.doc –
r.2
5. End cycle and regeneration
5.1. End cycle
The unit is equipped with 2 pressure sensors plumbed on inlet and outlet line of the filters;
the sensors gauge the correspondent pressure (IN/OUT) and therefore also the differential
pressure; when the pressure drop across the filtering bed reaches the value of 0.8 bar (80 kPa),
the end-cycle is driven.
During normal service, possible peaks of pressure could cause a wrong indication of reached
max allowable pressure drop; in order to avoid that, the end-cycle driving is delayed of an
adjustable time. Hence the max pressure drop must remain for all the time of adjusted delay, to
drive the end-cycle.
The electronic micro-processor programmer allows also to run the regeneration according to
time schedule, at pre-set time and day (max 3 regeneration per day).
To set the regeneration by time only (regardless of pressure drop), proceed as follows :
- set at least 1 regeneration by time schedule
- enter as max allowable pressure drop (end-cycle) the value 10000.
To set the regeneration by pressure drop only (regardless of time), proceed as follows :
- delete any programmed regeneration by time control
- enter as max allowable pressure drop (end-cycle) the desired value (standard =80)
5.2. Regeneration
The regeneration is automatically controlled by the electronic programmer according to time
schedule or pressure drop.
The regeneration can also be started manually at any time, out of any automatic
programme, by keeping pushed for 3 consecutive seconds the button function of the
programmer.
For the correct use of the buttons function of the programmer, proceed as follows (see also
the chapter “How to use the buttons function of the programmer”):
push several times the button until ESC+C… appears on the display
push and keep pushed the button
ESC
and immediately afterthat the desired button funtion
(), keeping both pushed for 3 consecutive seconds.
Warning :
by pushing the button
ESC
without pushing the button functions within 2
seconds, the display skips visualization to menu; release and then push
again the button
ESC
to go back to visualization ESC+C…
The pushing of manual start of the regeneration, while the regeneration is
already running, has not any effect.
An undesirable regeneration can be interrupted, in any moment, by
keeping pushed the button RESET for 3 consecutive seconds.
When the manually started regeneration is completed, the unit will continue to work
according to previous programming.
DUAL arrangement only :
Regeneration can also be started manually for each column independent way :
press and keep pressed for 3 consecutive seconds the function button of the programmer, the
regeneration of column A is started; while pressing and keeping pressed for 3 consecutive
seconds the function button of the programmer, the regeneration of column B is started.
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 11 of 21
fcd-dp_mi-r2.doc –
r.2
The regeneration can also run in case of power failure, by hand-driving the lever of the pilot
solenoid valves: the solenoid valve is closed when the lever is on parallel to the base and it is
open when it is on perpendicular to the base itself. Naturally, the compressed air supplying (air
controlled valves) or pilot water supplying (water controlled valves) must be assured.
The correspondent membrane valves (controlled by the pilot solenoid ones), if NC type is
open when the solenoid valve is open, and viceversa if the membrane valve is NO type.
PHASE SOLENOID VALVES
EXCITED (=OPEN)
OPEN VALVES
SERVICE // V2 - V4
BACKWASHING E2 - E3 V3 - V5
RINSE E1 - E2 V1 - V4
The regeneration phases run one after another, as follows :
1. Backwash : during this phase, the water flushes from the bottom to the top of the column,
lifting the filtering media and releasing the solids trapped on its surface during the service.
The backwashing water flows to drain from the top of the column. This is the only phase,
during which the water crosses through the column from the bottom to the top.
2. Rinse : it is the phase during which the filtering media are rinsed; at the end of this phase
the column is ready to start again a new service cycle.
NOTE: During regeneration the water supplying is completely inhibited.
NOTE : For DUAL arrangement, when regeneration is required, column A starts it
immediately, while in the same time column B enters in “regeneration
required”state, although it continues to feed water.
At the end of regeneration of column A, with an adjustable delay (see
following how to adjust time of delay), column B starts regeneration.
5.3. Inhibit of the regeneration
It is possibile to inhibit the automatic starting of regeneration by mean of an external contact,
using the input I2 of the programmer as described at paragraph "Electrical wiring connection".
Hence, when the end-cycle is reached, the filter will remain on REGENERATION
REQUIRED until the inhibit signal is switched off.
Even if the inhibit signal is still on, it is also possible to start manually the regeneration, as
above explained.
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 12 of 21
fcd-dp_mi-r2.doc –
r.2
6. CONTROL PANEL
6.1. Functions of the logical programmer
The logical programmer Siemens serie LOGO handles the logical working of the whole unit.
Its display allow the visualization of the status of the logical inputs (marked as I), the logical
outputs (marked as Q), current time and date, the several messages enabled by the
programme.
It is also possible to modify the settings of the entered numerical parameters (marked as B).
The numbering of the inputs and outputs is arranged on several rows, each of them
correspond to a ten (I1÷I9, I10÷I19 ecc.).
By pushing the buttons or the display shows, alternatively, the visualizations of the
service : current time and date, inputs, outputs, (M, to be ignored), function buttons (ESC+C..).
By pushing the buttons and the messages enabled by the programme are visualized.
The used functions are the following :
MARK DESCRIPTION
I2 input available for regeneration inhibit
I3 button RESET
I7 (AI1) pressure sensor INLET (P-IN)
I8 (AI2) pressure sensor OUTLET (P-OUT)
Q1 output of the solenoid valve E1 (E1A for DUAL arrangement)
Q2 output of the solenoid valve E2 (E2A for DUAL arrangement)
Q3 output of the solenoid valve E3 (E3A for DUAL arrangement)
Q4 output of running regeneration (column A for DUAL arrangement)
Q5 output related to solenoid valve E1B (for DUAL arrangement only)
Q6 output related to solenoid valve E2B (for DUAL arrangement only)
Q7 output related to solenoid valve E3B (for DUAL arrangement only)
Q8 output related to report of running regeneration column B (for DUAL arrangement
only
)
B1 time of BACKWASHING
B2 time of RINSING
B3-1 setting time and days of regeneration
B4 delay of driving of end-cycle
B5 max allowable pressure drop
B6 time of delay starting regeneration of column B after conclusion of regeneration
column A (for DUAL arrangement only)
All settings of automatic working are factory-made at the shipment.
See the chapter “SETTINGS” to check the factory-set.
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 13 of 21
fcd-dp_mi-r2.doc –
r.2
6.2. Signals on the display of the programmer
The report messages enabled by the programmer are visualized on the display one at a time,
with a determinate priority.
The buttons and are used to scroll the messages.
The button is used to turn back to service visualizations.
The messages that can be visualized are :
"P IN"
"P OUT"
"DP"
"SET"
These visualizations are always available.
They show, respectively, (values are expressed in bar) :
current inlet pressure
current outlet pressure
current differential pressure value
max differential pressure value to drive end-cycle
"BACKWASH"
This visualization is available only when the filter is running the
backwash phase.
The pre-set time and the elapsed time from the starting of the
phase are also shown.
"RINSE"
This visualization is available only when the filter is running the
rinse phase.
The pre-set time and the elapsed time from the starting of the
phase are also shown.
"WAITING FOR
REGENERATION"
This visualization appears only when the filter reaches the end-
cycle, but the regeneration cannot run due to the inhibit signal
(input I2).
For DUAL arrangement, the visualization is available for each
column
"RIGENERATION BACKWASH
FILTER A"
"…… B"
This visualization is available for DUAL arrangement only.
The signal indicates which column in on backwashing
"RIGENERATION RINSE
FILTER A"
"…… B"
This visualization is available for DUAL arrangement only.
The signal indicates which column in on rinse
6.3. How to use the
buttons function
of the programmer
The 4 buttons can have special functions whether enabled by the software.
For their utilization, proceed as follows :
push several times the button until the display shows ESC+C…
push and keep pushed the button
ESC
and immediately afterthat the desired button function
()
Warning :
by pushing the button
ESC
without pushing the button functions within 2
seconds, the display skips visualization to menu; release and then push
again the button
ESC
to go back to visualization ESC+C…
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 14 of 21
fcd-dp_mi-r2.doc –
r.2
7. SETTINGS
7.1. How to set current time and day of the week
The programmer is equipped with internal clock, keeping exact time for 80 hours in case of
power failure. To set the current time and day, proceed as follows :
1. push the button
ESC
2. push the button until the pointer > indicates "Set …"
3. push the button
OK
4. the pointer indicates “Clock..”, push the button
OK
5. the pointer indicates “Set Clock..”, push the button
OK
6. push the button to point the day or the number to be modified
7. when the pointer blinks on the day or the number to be modified, push the buttonor
until the new desired day or value is shown (symbols related to days of week are
explained at following chapter)
8. repeat the same operation with other values, if required
9. push the button
OK
to confirm (save) the modifications
10. push twice the button
ESC
to go back to the visualization of service.
The programmer is already factory set for automatic updating with european summer time
(S/W Time ON = EU)
7.2. How to set day and time of regeneration
The days of the week can be set one by one; they appear on the display in the weekly row: it
is possible to select (visualized the initial letter of the day) or not (visualized the symbol -).
The row and explanation of the symbols that appear on the display are :
M / -T / -W / -T / -F / -S / -S / -
M
onday
T
uesday
W
ednesday
T
hursday
F
riday
S
aturday
S
unday
The available digits to set the time are between 00:00 and 23:59; the symbol --:-- indicate
not any ON and/or not any OFF.
The regeneration starts at the time set on the line ON.
The time on the line OFF
MUST BE NECESSARILY SET
one minute later than the time
on the line ON.
The programmer allows to set up to 3 regeneration per day (B3-1, B3-2, B3-3).
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 15 of 21
fcd-dp_mi-r2.doc –
r.2
Proceed as follows to modify :
1. push the button
ESC
2. push several times the button until the pointer > points "set param"
3. push the button
OK
.
4. push several times the button until the display shows the parameter where to make the
modification (B3 - 1 or other)
5. push the button
OK
, the blinking cursor will take place on the line of the days (D)
6. by pushing the button the cursor moves on the positions correspondent to the days of
the week
7. push the button to enable/disable
8. by pushing the button the cursor moves on the several digits of the hours (lines ON and
OFF)
9. when the cursor blinks on the digit to modify, push several times the until the desired
number appears
10. repeat the same operations with other digits, whether required.
11. push the button
OK
to confirm the modifications
12. push the button to visualize other parameters which must be modified, and operate as
explained at above points 5 ÷11, or push the button
ESC
to leave the modification menu
13. push the button
ESC
to go back to visualization of service.
7.3. How to set time of phases, delay, pressure drop value
Proceed as follows to modify :
1. push the button
ESC
2. push several times the button until the pointed > points "set param"
3. push the button
OK
.
4. push several times the button until the parameter to modify is shown (B1 or other)
5. push the button
OK
.
6. by pushing the button , move the cursor on the digit to modify
7. when the cursor blinks on the digit to modify, push the button until thge desired digit
appears
8. repeat the same operations with other digits, whether required
9. push the button
OK
to confirm the modifications
10. proceed as explained for other modifications of other parameter or push the
ESC
per to
leave the modification menu
11. push the button
ESC
to go back to visualization of service
NOTE:
during the modifications, the normal service is NOT interrupted.
In modification menù, ref. to the timers, the digits visualized on the line (marked
as Ta) underneath the line of the time setting (marked as T), indicate the status
of the present counting of the time related to the selected timer
time basis are :
s = seconds (00,00 ÷ 99,95)
m = minutes (00:00 ÷ 99m:59s)
h = hours (00:00 ÷ 99h:59m)
although the programmer allows to set values up to 19999, in the field of the
max allowable pressure drop (B5), let us remind that the real max allowable
value is 100, correspondent to a pressure drop of 1 bar (=100 kPa = max
allowable value pressure drop across the filter).
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 16 of 21
fcd-dp_mi-r2.doc –
r.2
7.4. Factory set
Parameter utilization set value
B1
time BACKWASH
15.00 m
B2
time RINSE
05.00 m
B4
delay of the max differential pressure driving
60.00 s
B5-ON
max differential pressure
80 (equal to 0.8 bar)
B5-OFF
Must be necessarly the same of B5-ON
80
B6
time of delay starting regeneration of column B after
conclusion of regeneration column A (for DUAL
arrangement only)
10.00 s
Parameter utilization Day of
regeneration
time ON time OFF
B3 - 1
Start of regeneration by time
M 00 : 01 00 : 02
B3 - 2
"
- -- : -- -- : --
B3 - 3
"
- -- : -- -- : --
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 17 of 21
fcd-dp_mi-r2.doc –
r.2
8. Starting-up
The starting-up of the unit consists of running a first regeneration cycle, during which the
filtering media column will be filled of water, all automatic features will be checked and the unit
will be prepared to start the service.
At the beginning, it is suggested to operate manually, and to hand-driven the valves, by
hand-driving the lever of the pilot solenoid valves:
the solenoid valve is closed when the lever is on parallel to the base and it is open
when it is on perpendicular to the base itself.
This way will allow to stop, to run for longer time or to repeat each phase as desired, and to
adjust the flow rates according to the attached table.
To start-up the unit, proceed as follows (for DUAL arrangement, operate on column A only):
DISCONNECT ELECTRIC POWER
shut off the inlet, outlet and by-pass gate valves.
close quite completely the gate valve along the backwash drain line
hand-drive the solenoid valves E3 to open the backwashing membrane valves
open slowly and only partially the gate valve on inlet line. The water will enter inside the
vessel from the bottom and, during filling, will expel the air inside it.
when only water will come out from the drain, open completely the inlet gate valve and adjust
the backwash drain gate valve in order that the flow rate will be the highest allowable without
any leakage of media filter through the drain line; when the proper flow rate of backwash has
been stated, adjust the gate valve definitely. The backwashing phase must run until all the
water coming out the drain is perfectly clear.
Hand-drive the solenoid valves E3 to close the backwashing membrane valves.
Hand-drive the solenoid valve E1 to open the membrane valve V1 (RINSE); the rinse phase
must run until all the water coming out the drain is perfectly clear.
Hand-drive the solenoid valves E1 to close the valve V1 and to conclude the regeneration.
Switch ON the control panel.
Open the outlet valve .
Starting now the unit is on service and feeds treated water.
For DUAL arrangement : repeat all listed operation on column B
It is suggested to check, during the running of the first automatic regenerations, that the
adjusted flow rates and times are correct.
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 18 of 21
fcd-dp_mi-r2.doc –
r.2
9. SERVICE & MAINTENANCE
Normally, these units do not require any regular maintenance operation and there is not any
consumption material to be currently replaced.
The only parts that can be aged are the electrical components and moving parts, as listed :
the membrane of the automatic valves; after years, they can be aged and crack.
the solenoid valves can break down (electric) or can get dirty if the pilot fluid is not
perfectly clean.
The average life of the media filter is approx 5÷8 years, according to the chemical-phisical
characteristics of the water and how often the regeneration is featured.
The correct handling of the equipment requires :
check monthly the values of pressure and flow rate of water, which have to comply with
stated ones.
check that the air and/or water pressure are within the stated values.
check that the values of pressure shown by the programmer meet the ones gauged by the
manometers.
Not any further special maintenance operations are required.
Not any consumption material is required .
9.1. Media filter, nozzles
Whether the filtering bed is clogged and “packed” in order that it is impossible to backwash it
properly, the replacing of the media filter is required.
Proceed as follows for the emptying :
Switch OFF the control panel
Close the shut-off valves upstream and downstream of .
Empty the column of water, by opening the bottom drain valve
Open the upper-side man-hole (or upper head)
Open the lower-side man-hole, leaving one nut inserted in. It will allow to control the flow
of the media filter outside.
Then open completely the lower and side man-hole. Keep the nuts and gaskets of the
man-holes.
Flush water to take out the media filter still laying along the internal walls of the column
and on the internal nozzles.
Complete the emptying of the column, using an aspirator, if necessary.
During the last part of the operation, take care not to damage the nozzles mounted on the
holding plate.
Replace the damaged nozzles, if any.
Proceed as explained at § 4.5 to load the new media filter.
Proceed as explained at § 8 to start-up the unit, after replacing of media filter.
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 19 of 20
fcd-dp_mi-r2.doc –
r.2
9.2. Disposal
In case of disposal of the unit or parts of it, it must be made according to local laws
concerning the waste of the materials.
Concerning media filter, they are natural products that, at origin state, can be disposed of as
natural products. Whether the activated carbon had trapped special and particular substances,
the carbon will be classified as same class of the trapped substances.
10. MAIN COMPONENTS
Quantity
DESCRIPTION
1 (2) coated steel vessel (see table DIMENSIONS)
1 (2) internal distribution system (see next table)
# (x2) media filter (see table WEIGHTS)
5 (10) diaphragm valves in cast-iron (see next table)
3 (6) pilot solenoid valves type 6012-24Vcc/MAN/PA
1 (1) control panel NOBEL made
2 (2) pressure transducers stainless steel, range 0÷10 bar, output 0-10 V, connection ¼"
# galvanized steel piping/fittings, several diameters
The quantities indicates between brackets () are the ones related to DUAL arrangement.
diaphragm valves
distributor
MODEL V1 V2 V3 V4 V5
number/type
FC05/D
1"NC 1¼"NO 1"NC 1¼"NO 1"NC 12 short
FC08/D
1"NC 1½"NO 1¼"NC 1½"NO 1¼"NC 12 short
FC11/D
1"NC 1½"NO 1¼"NC 1½"NO 1¼"NC 18 short
FC15/D
1"NC 2"NO 1½"NC 2"NO 1½"NC 30 plate
FC20/D
1"NC 2"NO 1½"NC 2"NO 1½"NC 36 plate
FC25/D
1"NC 2½"NO 2"NC 2½"NO 2"NC 42 plate
FC30/D
1¼"NC DN80NO 2½"NC DN80NO 2½"NC 56 plate
FC40/D
1¼"NC DN80NO 2½"NC DN80NO 2½"NC 68 plate
FC45/D
1¼"NC DN80NO 2½"NC DN80NO 2½"NC 84 plate
FC50/D
1½"NC DN100NO DN80NC DN100NO DN80NC 87 plate
FC60/D
1½"NC DN100NO DN80NC DN100NO DN80NC 104 plate
FC70/D
1½"NC DN100NO DN80NC DN100NO DN80NC 118 plate
FC80/D
1½"NC DN100NO DN80NC DN100NO DN80NC 142 plate
diaphragm valves
distributor
MODELLO
V1 V2 V3 V4 V5 number/type
FAC05/D
1"NC 1¼"NO 1"NC 1¼"NO 1"NC 12 short
FAC08/D
1"NC 1½"NO 1¼"NC 1½"NO 1¼"NC 18 short
FAC11/D
1"NC 1½"NO 1¼"NC 1½"NO 1¼"NC 30 plate
FAC15/D
1"NC 2"NO 1½"NC 2"NO 1½"NC 36 plate
FAC20/D
1"NC 2½"NO 2"NC 2½"NO 2"NC 42 plate
FAC25/D
1"NC 2½"NO 2"NC 2½"NO 2"NC 56 plate
FAC30/D
1¼"NC DN80NO 2½"NC DN80NO 2½"NC 68 plate
FAC40/D
1¼"NC DN80NO 2½"NC DN80NO 2½"NC 87 plate
FAC50/D
1½"NC DN100NO DN80NC DN100NO DN80NC 104 plate
FAC60/D
1½"NC DN100NO DN80NC DN100NO DN80NC 142 plate
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
FC/D-DP -FAC/D-DP
s.r.l.Milano - ITALY
Page 20 of 20
fcd-dp_mi-r2.doc –
r.2
11. TROUBLE-SHOOTING GUIDE
PROBLEM CAUSE HOW TO SOLVE
The electronic
programmer does not
switch ON
electrical power is
disconnected
the programmer is defected
connect electrical power
replace the programmer
The regeneration does not
run
electrical power is
disconnected
the programmer is not correctly
adjusted
the programmer is defected
connect electrical power
adjust correctly the
programmer
replace the programmer
Regeneration is
electrically started but it
does not run hydraulically
there is not supplying of pilot
fluid (air or water)
one or more solenoid valves
are defected
connect properly the supplying
of pilot water or compressed air
replace the defected solenoid
valves
There is a leakage of
water to drain during
service
one among (or both)
membrane valves no. 1 and 5
does not close properly.
check the proper working of
the pilot solenoid valves
check and clean the seat of
the plate of the membrane
valve
The unit does not feed
water
the membrane valve no. 2 does
not open
check the proper working of
the pilot solenoid valve
There is a leakage of
filtering media to the drain
or to the outlet line
one nozzle of distribution
system is damaged or broken
replace the nozzle
The values of pressure
shown on the display of
the programmer are by far
different than the ones
gauged by manometers
the manometers are not quite
calibrated
the pressure transducers are
not quite calibrated i sensori di
pressione sono starati
check the real pressure values
by using a standard instrument;
then replace the instrument
(manometer or transducer)
which gauge the uncorrect
value *
* Normally, a difference of approx 3 % between the values gauged by the two different
measurement systems is acceptable.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30

NobelCom FAC/D-DP User manual

Type
User manual

The NobelCom FAC/D-DP is an automatic filter designed to treat raw water from municipalities or wells. It effectively removes impurities, chlorine, and organic substances, providing clean and safe water for various applications. Here is a brief overview of its capabilities:

  • Filtration: The filter utilizes quartz sand and activated carbon to effectively remove suspended solids, dirt, and other impurities from the water.

  • Activated Carbon: The activated carbon in the filter adsorbs chlorine, organic substances, and other contaminants, improving the taste, smell, and overall quality of the water.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI