Mitsubishi Electric SUZ-KA18NA2 Owner's manual

Category
Split-system air conditioners
Type
Owner's manual

This manual is also suitable for

SERVICE MANUAL
R410A
Outdoor unit
[Model Name]
SUZ-KA18NA2
SUZ-KA18NAH2
SUZ-KA24NA
SUZ-KA24NAH2
SUZ-KA30NA
SUZ-KA30NAH2
SUZ-KA36NA
SUZ-KA36NAH2
[Service Ref.]
SUZ-KA18NA(H)2.TH
SUZ-KA24NA(H)2.TH
SUZ-KA30NA(H)2.TH
SUZ-KA36NA(H)2.TH
PARTS CATALOG (OCB688)
CONTENTS
1.
COMBINATION OF INDOOR AND OUTDOOR UNITS
...
2
2. PART NAMES AND FUNCTIONS
......................
2
3. SPECIFICATION
.................................................
3
4. OUTLINES AND DIMENSIONS
..........................
4
5. WIRING DIAGRAM
............................................
5
6. REFRIGERANT SYSTEM DIAGRAM
................
9
7. DATA
..................................................................
11
8. ACTUATOR CONTROL
.....................................
14
9. SERVICE FUNCTIONS
......................................
15
10. TROUBLESHOOTING
.......................................
15
11. FUNCTION SETTING
........................................
32
12. DISASSEMBLY INSTRUCTIONS
......................
35
Note:
This manual describes service
data of the outdoor units only.
No. OCH688
November 2018
SPLIT-TYPE, AIR CONDITIONERS
SUZ-KA18NA(H)2.TH
2
OCH688
1
COMBINATION OF INDOOR AND OUTDOOR UNITS
OUTDOOR UNIT
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
PART NAMES AND FUNCTIONS
2
SUZ-KA18NA(H)2.TH SUZ-KA24NA(H)2.TH SUZ-KA30NA(H)2.TH SUZ-KA36NA(H)2.TH
Heat pump type
Outdoor unit
SUZ-
Indoor unit
Service
Manual No.
Service Ref.
Heat pump without
electric heater
OCH669
OCB669
KA18NA(H)2.TH
PEAD-A18AA7.MX
PEAD-A24AA7.MX
PEAD-A30AA7.MX
PEAD-A36AA7.MX
SVZ-KP18NA.MX
SVZ-KP24NA.MX
SVZ-KP30NA.MX
SVZ-KP36NA.MX
MLZ-KP18NA
MD-1404-K019
MD-1404-K018
KA24NA(H)2.TH KA30NA(H)2.TH KA36NA(H)2.TH
HWE08020
BWE10180
OBH802
OBB802
HWE16080
BWE016290
SEZ-KD18NA4.TH
SLZ-KF18NA.TH
3
OCH688
Outdoor unit model
SUZ-KA18
NA(H)2
SUZ-KA24
NA(H)2
SUZ-KA30
NA(H)2
SUZ-KA36
NA(H)2
Power supply V , phase , Hz 208/230 , 1 , 60
Max. fuse size (time delay) A 15 20
Min. circuit ampacity A 14 17
Fan motor F.L.A 0.67 1.00
Compressor
Model
SNB130FQBMT SNB220FQGM1T
R.L.A 10.0 13.0
L.R.A 12.5 16.0
Refrigeration oil oz. (Model) 11.8(FV50S) 15.6(FV50S)
Refrigerant control Linear expansion valve
Sound level
*
1
Cooling dB(A) 54 55
Heating dB(A) 55
Defrost method Reverse cycle
Dimensions
W in 34-5/8
D in 33-1/16
H in 13
Weight Ib 127 129
External nish Munsell 3Y 7.8/1.1
Control voltage
(by built-in transformer)
VDC 12 - 24
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in 1/4 (0.0265) 3/8(0.0285)
Gas in 1/2 (0.0285) 5/8(0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor &
outdoor units
Height difference ft 50 100
Piping length ft 100
Refrigerant charge (R410A) 3 lb. 9 oz. 4 lb. 14 oz.
Note: Test conditions are based on AHRI 210/240.
Rating conditions (Cooling) Indoor: 80˚F D.B., 67˚F W.B., Outdoor: 95˚F D.B., (75˚F W.B.)
(Heating) — Indoor: 70˚F D.B., 60˚F W.B., Outdoor: 47˚F D.B., 43˚F W.B.
3
SPECIFICATION
OPERATING RANGE
(1) POWER SUPPLY
Rated voltage Guaranteed voltage (V)
Outdoor unit
208/230 V
1 phase
60 Hz
Min. 187
208 230 Max. 253
4
OCH688
Unit: inch
SUZ-KA18NA(H)2.TH SUZ-KA24NA(H)2.TH SUZ-KA30NA(H)2.TH SUZ-KA36NA(H)2.TH
4
OUTLINES AND DIMENSIONS
16-7/16
1-9/16
1-5/8
Drain hole
6-7/8
19-11/16
13
2
Air in
Air in
Air out
2-holes 13/32 13/16
14-3/16
33-1/16
4-5/16
3-3/16
34-5/8
17-25/32
Service panel
3-29/32
6-1/2
7-11/16
35
44
Liquid refrigerant pipe joint
Refrigerant pipe (flared)
Ø 1/4 (KA18)
Refrigerant pipe (flared)
Ø 3/8 (KA24/30/36)
Gas refrigerant pipe joint
Refrigerant pipe (flared)
Ø 1/2 (KA18)
Refrigerant pipe (flared)
Ø 5/8 (KA24/30/36)
*1 20 in. (500 mm) or more when front
and sides of the unit are clear
14 in. (350 mm)
or more
4 in. (100 mm)
or more
REQUIRED SPACE
Clear *1
4 in. (100 mm)
or more
20 in. (500 mm)
or more *2
*2 When any 2 sides of left, right
and rear of the unit are clear
5
OCH688
SUZ-KA18NA2.TH
5
WIRING DIAGRAM
4
W
W
W
4
6
OCH688
SUZ-KA18NAH2.TH
4
W
W
W
4
7
OCH688
SUZ-KA24NA2.TH   SUZ-KA30NA2.TH  SUZ-KA36NA2.TH
2
1
MS
MS
3~
BN
TAB61
TAB62
TABS3
LED
YE
BU
1
34
L
2
43
PTC65
DB41A
DB41B
X64
TAB3B
TAB3A
PTC64
WHRD
F601
Q3B
BU
CIRCUIT
BREAKER
GNYE
Q3A
D3B
D3A
208/230V
AC
60Hz
TB1
MF
BK
WH
RD
33
11
MC
U
W
V
BK
RD
WH
CB3
N
P
W
V
U
IC700
TAB9 TAB8 TAB7
CB2
CB1
TAB4A
TAB4B
POWER
SUPPLY
21S4
S1
S3
S2
MS
3~
26H
H
RT61
1 2
CN601
X601
5
LEV
1
CN724
6
RT65
CN672
21
LD9
BK
RD
TABS3
LED
INVERTER
P.C.
BOARD
T801
1
2
CN602
LDE1
LDE2
BK
BK
X602
F601
RT64
RT68RT62
5 1
CN931
21
CN673
1 6
CN671
GNYE
TO
INDOOR
UNIT
208/230V
AC
24V
DC-12
TB2
MF
8
F880 F901
TAB9
IC932
CN932
13
WH
BU
2 2
RD
22
11
1 1
YE
BK BK
BK BK
BKBK
BK
NAME
SWITCHING
POWER
TRANSISTOR
DEFROST
THERMISTOR
DISCHARGE
TEMP.THERMISTOR
AMBIENT
TEMP.THERMISTOR
FIN
TEMP.THERMISTOR
OUTDOOR
HEAT
EXCHANGER
TEMP.THERMISTOR
SYMBOL
Q3A,Q3B
RT61
RT62
RT64
RT65
RT68
TERMINAL
BLOCK
TRANSFORMER
TB1,TB2
T801
X64
RELAY
X601,X602
RELAY
21S4
26H
HEATER
PROTECTOR
OPTION
PARTS
REVERSING
VALVE
COIL
SYMBOL
NAME
F901
F880
F601
FUSE
T3.15AL250V
FUSE
T3.15AL250V
H
DEFROST
HEATER
OPTION
PARTS
IC700,IC932
L
REACTOR
POWER
MODULE
PTC64,PTC65
CIRCUIT
PROTECTION
MF
MC
LEV
LED
LED
EXPANSION
VALVE
COIL
COMPRESSOR
FAN
MOTOR
DIODE
OPTION
PARTS
SYMBOL
NAMENAME
DIODE
MODULE
SMOOTHING
CAPACITOR
FUSE
T3.15AL250V
SYMBOL
DB41A,DB41B
D3A,D3B
CB1,CB2,CB3
NOTES
1.About
the
indoor
side
electric
wiring,
refer
to
the
indoor
unit electric
wiring
diagram
for
servicing.
2.Use
copper
supply
wires. 3.Symbols
indicate, :Terminal
block :Connector
8
OCH688
SUZ-KA24NAH2.TH SUZ-KA30NAH2.TH SUZ-KA36NAH2.TH
RELAY
X601,X602
DEFROST
HEATER
BU
WH
POWER
SUPPLY
3 1
CN932
IC932
TAB4B
TAB4A
CB1
CB2
TAB7TAB8TAB9
IC700
U
V
W
P
N
CB3
WH
RD
BK
V
W
U
MC
1 1
3 3
RD
WH
BK
F901F880
8
MF
TB2
12 - 24V
DC
208/230V
AC
TB1
208/230V
AC
60Hz
TO
INDOOR
UNIT
D3A
D3B
Q3A
GNYE
CIRCUIT
BREAKER
BU
Q3B
CN671
61
CN673
1 2
CN931
15
RT62 RT68
RT64
F601
X602
BK
BK
LDE2
LDE1
CN602
21
T801
INVERTER
P.C.
BOARD
RD WH
PTC64
TAB3A
TAB3B
X64
DB41B
DB41A
PTC65
3 4
2
L
4 3
1
BU YE
LED
TABS3
RD
TAB62
TAB61
BK
LD9
1 2
CN672
RT65
6
CN724
1
LEV
5
X601
CN601
21
RT61
BN
3~
MS
3~
MS
S2
S3
S1
1
2
21S4
3.Symbols
indicate,
:Terminal
block
:Connector2. Use
copper
supply
wires.
1. About
the
indoor
side
electric
wiring,
refer
to
the
indoor
unit
electric
wiring
diagram
for
servicing.
NOTES
RELAY
NAME
F601
F880
F901
CB1,CB2,CB3
D3A,D3B
DB41A,DB41B
SYMBOL
FUSE
T3.15AL250V
FUSE
T3.15AL250V
FUSE
T3.15AL250V
SMOOTHING
CAPACITOR
REACTOR
CIRCUIT
PROTECTION
FAN
MOTOR
MF
COMPRESSOR
MC
EXPANSION
VALVE
COIL
LEV
LED
LED
DISCHARGE
TEMP.THERMISTOR
RT62
TRANSFORMER
T801
TERMINAL
BLOCK
RT68
TEMP.THERMISTOR
OUTDOOR
HEAT
EXCHANGER
TB1,TB2
SWITCHING
POWER
TRANSISTOR
Q3A,Q3B
DIODE
MODULE
NAME NAME NAME
SYMBOL SYMBOL
DIODE
RT64
FIN
TEMP.THERMISTOR
POWER
MODULE
PTC64,PTC65
X64
IC700,IC932
L
H
RT61
DEFROST
THERMISTOR
RT65
AMBIENT
TEMP.THERMISTOR
21S4
26H
HEATER
PROTECTOR
REVERSING
VALVE
COIL
SYMBOL
YE
RD
BKBKBK
BK
BK
BK
BK
11
1 1
22
2 2
H
26H
9
OCH688
Unit: inch (mm)
SUZ-KA18NA(H)2.TH
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
Capillary tube
O.D. 0.157×
I.D. 0.094×
3-15/16
4.0
×
ø
2.4
×
100)
Capillary tube
O.D. 0.157×
I.D. 0.094×7-7/8
4.0
×
ø
2.4
×
200)
Refrigerant flow in cooling
Compressor
4-way
valve
Refrigerant flow in heating
Refrigerant pipe
ø1/2
(
ø
12.7)
(with heat insulator)
Refrigerant pipe
ø1/4
(
ø
6.35)
(with heat insulator)
LEV
R.V. coil
heating ON
cooling OFF
Strainer
#100
Outdoor heat
exchanger
temperature
thermistor
RT68
Strainer
#100
Muffler
Capillary tube
O.D. 0.118×
I.D. 0.079× 7-7/8
(ø3.0×ø2.0×200(×4))
Stop valve
(with service port)
Service
port
Service port
Muffler
Strainer
#100
6
REFRIGERANT SYSTEM DIAGRAM
SUZ-KA24NA(H)2.TH SUZ-KA30NA(H)2.TH SUZ-KA36NA(H)2.TH
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
(with strainar)
Stop valve
(with service port)
Capillary tube
O.D. 0.142 × I.D. 0.094
× 1-31/32
3.6
×
ø
2.4
×
50)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
5/8
(with heat insulator)
Refrigerant pipe
ø
3/8
(with heat insulator)
LEV
R.V. coil
heating ON
cooling OFF
Muffler
#100
Receiver
Outdoor heat
exchanger
temperature
thermistor
RT68
Ambient
temperature
thermistor
RT65
Strainer
#100
Service port
Service port
Unit: inch (mm)
10
OCH688
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft. Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas Liquid
SUZ-KA18/NA(H)2
100
50 1/2 1/4
SUZ-KA24/30/36
NA(H)2
100 5/8 3/8
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 70 80 90 100
SUZ-KA18NA2
SUZ-KA18NAH2
3 lb. 9 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 70 80 90 100
SUZ-KA24/30/36
NA(H)2
4 lb. 14 oz. 0 2.69 8.07 13.45 18.83 24.21 29.59 34.97 40.35
Calculation: X oz. = 2.65/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
11
OCH688
7 DATA
STANDARD OPERATION DATA
Representative matching SEZ-KD18NA4 SLZ-KF18NA PEAD-A18AA7 PEAD-A24AA7
Item Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Total
Capacity BTU/h 18000 21600 17700 19700 18000 21600 24000 25000
SHF 0.82 0.71 0.80 0.77
Input kW 1.31 1.58 1.41 1.85 1.27 1.6 1.92 1.99
Electrical circuit
Indoor unit SEZ-KD18NA4 SLZ-KF18NA PEAD-A18AA7 PEAD-A24AA7
Power supply (V, phase, Hz) 230, 1, 60 230, 1, 60 230, 1, 60
Input kW 0.09 0.07 0.04 0.04 0.11 0.09 0.12 0.1
Current A 0.74 0.63 0.43 0.38 0.95 0.84 1.03 0.92
Outdoor unit
SUZ-KA18
NA(H)2
SUZ-KA18
NA(H)2
SUZ-KA18
NA(H)2
SUZ-KA24
NA(H)2
Power supply (V, phase, Hz) 230, 1, 60 230, 1, 60 230, 1, 60
Input kW 1.22 1.51 1.37 1.81 1.16 1.51 1.8 1.89
Current A 4.96 6.24 5.70 7.66 4.57 6.12 7.32 7.73
Refrigerant circuit
Condensing pressure
PSIG
369 366 372 492 371 365 411 418
Suction pressure
PSIG
141 100 125 105 135 100 140 108
Discharge temperature °F 158 167 155 174 158 167 161 162
Condensing temperature °F 111 110 111 128 111 110 119 120
Suction temperature °F 56 41 46 34 57 41 51 35
Ref. pipe length ft. 25 25 25
Refrigerant charge (R410A) 1.6 1.6 1.6 2.2
Indoor
unit
Intake air temperature
DB °F 80 70 80 70 80 70 80 70
WB °F 67 60 67 60 67 60 67 60
Discharge air temperature DB °F 57 101 56 108 56 103 56 101
Outdoor
unit
Intake air temperature
DB °F 95 47 95 47 95 47 95 47
WB °F 75 43 75 43 75 43 75 43
12
OCH688
Representative matching PEAD-A30AA7 PEAD-A36AA7 SVZ-KP18NA SVZ-KP24NA
Item Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Total
Capacity BTU/h 27000 30000 33000 33500 18000 21600 24000 25000
SHF 0.84 0.84 0.85 0.81
Input kW 2.16 2.41 3.51 3.17 1.36 1.6 1.92 1.91
Electrical circuit
Indoor unit PEAD-A30AA7 PEAD-A36AA7 SVZ-KP18NA SVZ-KP24NA
Power supply (V, phase, Hz) 230, 1, 60 230, 1, 60
Input kW 0.17 0.15 0.25 0.23 0.16 0.18
Current A 1.31 1.2 1.71 1.6 1.44 1.6
Outdoor unit
SUZ-KA30
NA(H)2
SUZ-KA36
NA(H)2
SUZ-KA18
NA(H)2
SUZ-KA24
NA(H)2
Power supply (V, phase, Hz) 230, 1, 60 230, 1, 60
Input kW 1.99 2.26 3.26 2.94 1.2 1.44 1.74 1.73
Current A 8.08 9.28 13.55 12.18 4.47 5.52 6.75 6.70
Refrigerant circuit
Condensing pressure
PSIG
419 417 456 356 369 349 411 415
Suction pressure
PSIG
147 105 142 97 144 100 145 108
Discharge temperature °F 164 162 176 176 158 158 156 167
Condensing temperature °F 120 120 127 108 111 108 116 119
Suction temperature °F 53 34 50 30 58 37 59 35
Ref. pipe length ft. 25 25
Refrigerant charge (R410A) 2.2 1.6 2.2
Indoor
unit
Intake air temperature
DB °F 80 70 80 70 80 70 80 70
WB °F 67 60 67 60 67 60 67 60
Discharge air temperature DB °F 58 98 57 95 58 100 59 96
Outdoor
unit
Intake air temperature
DB °F 95 47 95 47 95 47 95 47
WB °F 75 43 75 43 75 43 75 43
13
OCH688
Representative matching SVZ-KP30NA SVZ-KP36NA MLZ-KP18NA
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total
Capacity BTU/h 27000 30000 33000 33500 18000 20000
SHF 0.9 0.84 0.67
Input kW 2.16 2.06 3.72 3.03 1.44 1.77
Electrical circuit
Indoor unit SVZ-KP30NA SVZ-KP36NA MLZ-KP18NA
Power supply (V, phase, Hz) 230, 1, 60 230, 1, 60
Input kW 0.21 0.34 0.04
Current A 2.0 3.0 0.4
Outdoor unit
SUZ-KA30
NA(H)2
SUZ-KA36
NA(H)2
SUZ-KA18
NA(H)2
Power supply (V, phase, Hz) 230, 1, 60 230, 1, 60
Input kW 1.95 1.85 3.38 2.69 1.4 1.73
Current A 7.39 6.96 13.17 10.17 5.86 7.30
Refrigerant circuit
Condensing pressure
PSIG
414 322 453 336 368 453
Suction pressure
PSIG
155 87 139 95 123 105
Discharge temperature °F 160 159 174 175 164 175
Condensing temperature °F 116 102 124 109 110 118
Suction temperature °F 61 39 55 36 56 34
Ref. pipe length ft. 25 25
Refrigerant charge (R410A) 2.2 1.6
11Indoor
unit
Intake air temperature
DB °F 80 70 80 70 80 70
WB °F 67 60 67 60 67 60
Discharge air temperature DB °F 60 93 59 99 52 117
Outdoor
unit
Intake air temperature
DB °F 95 47 95 47 95 47
WB °F 75 43 75 43 75 43
14
OCH688
8-2. R.V. COIL CONTROL
Heating
.................
ON
Cooling
.................
OFF
Dry
....................
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds 15 seconds
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Discharge temperature
thermistor
Protection
Indoor coil temperature
thermistor
Cooling: Coil frost prevention
Heating: High pressure protec-
tion
Defrost thermistor Heating: Defrosting
Fin temperature thermistor Protection
Ambient temperature
thermistor
Cooling: Low ambient tempera-
ture operation
Outdoor heat exchanger tem-
perature thermistor
Cooling: Low ambient tempera-
ture operation
Cooling: High pressure protec-
tion
8
ACTUATOR CONTROL
15
OCH688
9-1. CHANGE IN DEFROST SETTING
Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board.
(Refer to "10-6. TEST POINT DIAGRAM AND VOLTAGE".)
Jumper
Defrost nish temperature
SUZ-KA18NA(H)2
SUZ-KA24/30/36NA(H)2
JS
Soldered
(Initial setting)
48°F (9°C) 50°F (10°C)
None
(Cut)
64°F (18°C) 64°F (18°C)
9-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature.
The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 68°F (20°C)
or below. When pre-heat control is turned ON, compressor is energized. (About 50 W)
<JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to "10-6. TEST POINT
DIAGRAM AND VOLTAGE".)
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
10
TROUBLESHOOTING
10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and turn off the
breaker.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp is blinking ON and OFF to indicate an abnormality.
2) Before servicing check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to "10-2. TROUBLESHOOTING CHECK TABLE" and "10-3. HOW TO PROCEED "SELF-DIAGNOSIS"".
Lead wiring
Housing point
9
SERVICE FUNCTIONS
16
OCH688
temperature thermistor, outdoor heat exchanger temperature
No. Symptoms
Abnormal point/ Condition
RemedyCondition
Outdoor unit
does not op-
erate.
1-time blink
every
2.5 seconds
Outdoor power sys-
tem
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started.
Reconnect connector of compressor.
Refer to “10-5. How to check in-
verter/compressor".
Check stop valve.
Outdoor thermistors Discharge temperature thermistor shorts, or opens during
  compressor running.
defrost thermistor, P.C. board
thermistor or ambient temperature thermistor shorts, or opens
during compressor running.
Refer to “10-5.F Check of outdoor
thermistors".
Outdoor control system
Nonvolatile memory data cannot be read properly.
Replace inverter P.C. board.
6-time blink
2.5 seconds
OFF
Serial signal The communication fails between the indoor and outdoor unit
for 3 minutes.
11-time blink
2.5 seconds OFF
Stop valve/
Closed valve
Closed valve is detected by compressor current. Check stop valve.
'Outdoor unit
stops and
restarts 3
minutes later'
is repeated.
2-time blink
2.5 seconds OFF
Overcurrent protec-
tion
Large current flows into intelligent power module.
Reconnect connector of compressor.
Refer to “10-5. How to check in-
verter/compressor".
Check stop valve.
3-time blink
2.5 seconds OFF
Discharge tempera-
ture overheat pro-
tection
Temperature of discharge temperature thermistor exceeds
116°C, compressor stops. Compressor can restart if discharge
temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrig-
erant amount.
Refer to “10-5.
k
Check of LEV".
4-time blink
2.5 seconds OFF
Fin temperature
/P.C. board tem-
perature thermistor
overheat protection
Temperature of fin temperature thermistor on the heat sink
exceeds 72 to 86°C or temperature of P.C. board temperature
thermistor on the inverter P.C.board exceeds 72 to 85°C.
Check around outdoor unit.
Check outdoor unit air passage.
Refer to “10-5.  Check of outdoor
fan motor".
5-time blink
2.5 seconds OFF
High pressure pro-
tection
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost
thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrig-
erant amount.
Check stop valve.
8-time blink
2.5 seconds OFF
Compressor syn-
chronous abnormal-
ity
The waveform of compressor current is distorted.
Reconnect connector of compressor.
Refer to “10-5. How to check in-
verter/compressor".
10-time blink
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to “10-5. Check of outdoor
fan motor.
Refer to “10-5. Check of inverter
P.C. board.
12-time blink
2.5 seconds OFF
Each phase current
of compressor
Each phase current of compressor cannot be detected nor-
mally.
Refer to “10-5
. L
verter/compressor".
13-time blink
2.5 seconds OFF
DC voltage DC voltage of inverter cannot be detected normally. Refer to “10-5
. How to check in-
verter/compressor".
Outdoor unit
operates.
1-time blink
2.5 seconds OFF
Frequency drop by
current protection
When the input current exceeds approximately 12A(KA18)
16A(KA24)/16A(KA30)/16A(KA36), compressor
The unit is normal, but check the
following.
Check if indoor filters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air
circulation is short cycled.
3-time blink
2.5 seconds OFF
Frequency drop by
high pressure pro-
tection
Temperature of indoor coil thermistor exceeds 131 °F [55 °C]
in HEAT
mode, compressor frequency lowers.
Frequency drop by
defrosting in COOL
mode
Indoor coil thermistor reads 46 °F [8 °C] or less in COOL
mode, com
pressor frequency lowers.
4-time blink
2.5 seconds OFF
Frequency drop by
discharge tempera-
ture protection
Temperature of discharge temperature thermistor exceeds
232 °F [111 °C], compressor frequency lowers.
Check refrigerant circuit and refrig-
erant amount.
Refer to “10-5. Check of LEV".
Refer to “10-5. Check of outdoor
thermistors".
7-time blink
2.5 seconds OFF
Low discharge tem-
perature protection
Temperature of discharge temperature thermistor has been
122 °F [50 °C] or less for 20 minutes.
Refer to “10-5. Check of LEV".
Check refrigerant circuit and refrig-
erant amount.
8-time blink
2.5 seconds OFF
PAM protection
PAM: Pulse Ampli-
tude Modulation
The overcurrent flows into IGBT (Insulated Gate Biopolar tran-
sistor: TR821) or the bus-bar voltage reaches 320 V or more,
PAM
stops and restarts.
This is not malfunction. PAM pro-
tection will be activated in the fol-
lowing cases:
1. Instantaneous power voltage
drop. (Short time power failure)
2. When the power supply voltage
is high.
9-time blink
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the com-
pressor is correctly connected.
Refer to “10-5. How to check
inverter/compressor".
NOTE: 1. The location of LED is illustrated at the right figure. Refer to "10-6. TEST POINT DIAGRAM".
2. LED is lighted during normal operation.
The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the blinking frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED
Blinking
Inverter P.C. board
I
I
L
K
G
K
Check indoor/outdoor connecting wire.
Replace indoor or outdoor P.C.
board if abnormality is displayed
again.
Zero cross detecting
circuit
Zero cross signal for PAM control cannot be detected.
LED
indication
check
code
UP
U3
U4
FC
E8
E9
UE
Fin temperature thermistor,
/
frequency lowers.
How to check in-
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
A
10-2. TROUBLE SHOOTING CHECK TABLE
No. Symptoms
LED
indication
check
code
Abnormal point/ Condition
Condition Remedy
1
Outdoor
unit does
not
operate.
1-time blink
every
2.5 seconds
UP
Outdoor power system Overcurrent protection cut-out operates 3 consecutive times within 1
minute after the compressor gets started.
Reconnect connector of compressor.
Refer to “10-5.
A
How to check
inverter/compressor".
Check stop valve.
2
U3
Outdoor thermistors Discharge temperature thermistor shorts, or opens during
compressor
running.
Refer to “10-5.
F
Check of outdoor
thermistors".
U4
Fin temperature thermistor, defrost thermistor, P.C. board temperature
thermistor, outdoor heat exchanger temperature thermistor or ambient
temperature thermistor shorts, or opens during compressor running.
3
6-time blink
2.5 seconds
OFF
FC
Outdoor control system Nonvolatile memory data cannot be read properly. Replace inverter P.C. board.
4
E8
/
E9
Serial signal The communication fails between the indoor and outdoor unit for 3
minutes.
Check indoor/outdoor connecting
wire.
Replace indoor or outdoor P.C.board
if abnormality is displayed again.
5
11-time blink
2.5 seconds
OFF
UE
Stop valve/
Closed valve
Closed valve is detected by compressor current. Check stop valve.
6
16-time ash
2.5 seconds
OFF
PL
Outdoor refrigerant
system abnormality
A closed valve and air trapped in the refrigerant circuit are detected
based on the temperature sensed by the indoor and outdoor
thermistors and the current of the compressor.
Check for a gas leak in a connecting
piping, etc.
Check stop valve.
Refer to “10-5.
O
Check of outdoor
fan motor".
7
'Outdoor
unit stops
and
restarts 3
minutes
later' is
repeated.
2-time blink
2.5 seconds OFF
Overcurrent protection Large current ows into intelligent power module. Reconnect connector of compressor.
Refer to “10-5.
A
How to check
inverter/compressor".
Check stop valve.
8
3-time blink
2.5 seconds OFF
Discharge temperature
overheat protection
Temperature of discharge temperature thermistor exceeds 116°C,
compressor stops. Compressor can restart if discharge temperature
thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refriger-
ant amount.
Refer to “10-5.
k
Check of LEV".
9
4-time blink
2.5 seconds OFF
Fin temperature/P.C.
board temperature
thermistor overheat
protection
Temperature of n temperature thermistor on the heat sink exceeds
72 to 86°C or temperature of P.C. board temperature thermistor on the
inverter P.C.board exceeds 72 to 85°C.
Check around outdoor unit.
Check outdoor unit air passage.
Refer to “10-5.
I
Check of outdoor
fan motor".
10
5-time blink
2.5 seconds OFF
High pressure protec-
tion
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost thermistor
exceeds 70°C in COOL mode.
Check refrigerant circuit and refriger-
ant amount.
Check stop valve.
11
8-time blink
2.5 seconds OFF
Compressor synchro-
nous abnormality
The waveform of compressor current is distorted. Reconnect connector of compressor.
Refer to “10-5.
A
How to check
inverter/compressor".
12
10-time blink
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds after
outdoor fan start-up.
Refer to “10-5.
I
Check of outdoor
fan motor.
Refer to “10-5.
L
Check of inverter
P.C. board.
13
12-time blink
2.5 seconds OFF
Each phase current of
compressor
Each phase current of compressor cannot be detected normally. Refer to “10-5.
L
How to check
inverter/compressor".
14
13-time blink
2.5 seconds OFF
DC voltage DC voltage of inverter cannot be detected normally. Refer to “10-5.
A
How to check
inverter/compressor".
15
Outdoor
unit
operates.
1-time blink
2.5 seconds OFF
Frequency drop by cur-
rent protection
When the input current exceeds approximately 12A(KA18)/16A(KA24)
/16A(KA30)/16A(KA36), compressor frequency lowers.
The unit is normal, but check the fol-
lowing.
Check if indoor lters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air circu-
lation is short cycled.
16
3-time blink
2.5 seconds OFF
Frequency drop by high
pressure protection
Temperature of indoor coil thermistor exceeds 131 °F [55 °C] in HEAT
mode, compressor frequency lowers.
Frequency drop by de-
frosting in COOL mode
Indoor coil thermistor reads 46 °F [8 °C] or less in COOL mode, com-
pressor frequency lowers.
17
4-time blink
2.5 seconds OFF
Frequency drop by
discharge temperature
protection
Temperature of discharge temperature thermistor exceeds 232 °F [111
°C], compressor frequency lowers.
Check refrigerant circuit and refriger-
ant amount.
Refer to “10-5.
k
Check of LEV".
Refer to “10-5.
G
Check of outdoor
thermistors".
18
7-time blink
2.5 seconds OFF
Low discharge tempera-
ture protection
Temperature of discharge temperature thermistor has been 122 °F [50
°C] or less for 20 minutes.
Refer to “10-5.
k
Check of LEV".
Check refrigerant circuit and refriger-
ant amount.
19
8-time blink
2.5 seconds OFF
PAM protection
PAM: Pulse Amplitude
Modulation
The overcurrent ows into IGBT (Insulated Gate Biopolar transistor:
TR821) or the bus-bar voltage reaches 320 V or more, PAM stops and
restarts.
This is not malfunction. PAM protection
will be activated in the following cases:
1. Instantaneous power voltage drop.
(Short time power failure)
2. When the power supply voltage is
high.
Zero cross detecting
circuit
Zero cross signal for PAM control cannot be detected.
20
9-time blink
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check mode
starts.
Check if the connector of the com-
pressor is correctly connected.
Refer to “10-5.
A
How to check
inverter/compressor".
17
OCH688
10-3. HOW TO PROCEED "SELF-DIAGNOSIS"
As this air conditioner has a function to memorize all the failures that had occurred, the latest failure detail can be recalled by
following the procedure below. Use this function when the check code is not displayed with wired remote controller or the re-
mote controller at use is wireless type.
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Test run
Input maintenance info.
Function setting
Check
Self check
F1 F2 F3 F4
kcehc fleS
:tceleS
Ref. address
sserddA
F1 F2 F3 F4
kcehc fleS
Ref. address
Return:
teseR
Error Unt # CI.prG
F1 F2 F3 F4
Self check
Return:
Reset
Ref. address
Error
--
Unt #
Grp.
-- --
When there is no error history
F1 F2 F3 F4
Self check
Delete error history?
Ref. address
Cancel OK
F1 F2 F3 F4
Self check
Return:
Ref. address
Error history deleted
2
With the
F1
or
F2
button, enter the refrigerant address, and press the button.
Select "Self check" with the F1 or F2 button, and press the button.
1
Select "Service" from the Main menu, and press the button.
3
Check code, unit number, attribute will appear.
"-" will appear if no error history is available.
4
Resetting the error history.
Press the
F4
button (Reset) on the screen that shows the error history.
A conrmation screen will appear asking if you want to delete the error history.
Press the
F4
button (OK) to delete the error history.
If deletion fails, "Request rejected" will appear.
"Unit not exist" will appear if no indoor units that are correspond to the entered
address are found.
Navigating through the screens
• To go back to the Service menu ..........
button
• To return to the previous screen .......
button
10-3-1. Self-diagnosis <PAR-3xMAA ("x" represents 0 or later)>
18
OCH688
If operations cannot be completed with the remote controller, diagnose the remote controller with this function.
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Maintenance password
Remote controller check
F1 F2 F3 F4
Remote controller check
:nigeB
Start checking?
Remote controller check
:nigeB
Start checking?
1
Select "Service" from the Main menu, and press the button.
Select "Remote controller check" with the F1
or F2 button, and press
the
button.
2
Select "Remote controller check" from the Service menu, and press the but-
ton to start the remote controller check and see the check results.
To cancel the remote controller check and exit the Remote controller check
menu screen, press the
or the button.
The remote controller will not reboot itself.
Check the remote controller display and see if anything is displayed
(including lines). Nothing will appear on the remote controller display if
the correct voltage (8.52 V DC) is not supplied to the remote controller.
If this is the case, check the remote controller wiring and indoor units.
OK: No problems are found with the remote controller. Check other
parts for problems.
E3, 6832: There is noise on the transmission line, or the indoor unit or another
remote controller is faulty. Check the transmission line and the
other remote controllers.
NG (ALL0, ALL1):
Send-receive circuit fault. Remote controller needs replacing.
ERC:
The number of data errors is the discrepancy between the number of
bits in the data transmitted from the remote controller and that of the
data that was actually transmitted over the transmission line. If data
errors are found, check the transmission line for external noise inter
-
ference.
Remote controller check results screen
If the button is pressed after the remote controller check results are dis-
played, remote controller check will end, and the remote controller will automati-
cally reboot itself.
10-3-2. Remote controller check <PAR-3xMAA ("x" represents 0 or later)>
3
19
OCH688
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and refrigerant address "00" blinks.
• Check that the remote controller's display has stopped before continuing.
2. Press the temperature buttons.
• Select the refrigerant address of the indoor unit for the self-diagnosis.
Note: Set refrigerant address using the outdoor unit’s DIP switch (SW1).
(For more information, see the outdoor unit installation manual.)
3. Point the remote controller at the sensor on the indoor unit and press the
HOUR button.
• If an air conditioner error occurs, the indoor unit's sensor emits an intermittent
buzzer sound, the operation light blinks, and the check code is output.
(It takes 3 seconds at most for check code to appear.)
4. Point the remote controller at the sensor on the indoor unit and press the ON/
OFF button.
• The check mode is cancelled.
<Malfunction-diagnosis method at maintenance service>
10-3-3. Self-diagnosis <Wireless remote controller>
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK
display
Temperature
button
CHECK
button
Refrigerant
address
display
HOUR
button
ON/OFF
button
20
OCH688
[Output pattern A] Errors detected by indoor unit
[Output pattern B]
E9
1. If the beeper does not sound again after the initial
2 beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION
INDICATOR
lamp
blink
pattern
Beep Beep Beep Beep Beep
Beep Beep
Off
Approx. 2.5 sec.
On
Approx. 3 sec.
On
0.5 sec.
On
0.5 sec.
On
0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.
On
Approx. 3 sec.
On
0.5 sec.
On
0.5 sec.
··· Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1
st
2
nd
3
rd
1
st
2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
[Output pattern B]
OPERATION
INDICATOR
lamp
blink
pattern
Beep
Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sec.
On
0.5 sec.
On
0.5 sec.
On
0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.
On
0.5 sec.
On
0.5 sec.
··· Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1
st
2
nd
3
rd
1
st
2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
Refer to the following tables for details on the check codes.
[Output pattern A]
Notes:
*The check code in the parenthesis indicates PAR-30MAA model.
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
Symptom Remark
(Number of times)
Wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
(Number of times)
Wireless remote controller
Wired remote controller
1 P1
Intake sensor error
P9 Pipe (TH5) sensor error
2
P2 Pipe (TH2) sensor error
3 E6,E7
Indoor/outdoor unit communication error
4 P4 Drain sensor error/Float switch connector (CN4F) open
5
P5 Drain pump error
PA Forced compressor stop (due to water leakage abnormality)
6 P6 Freezing/Overheating protection operation
7 EE Communication error between indoor and outdoor units
9 E4, E5 Remote controller signal receiving error
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Symptom
1
Indoor/outdoor unit communication error
2
(Transmitting error) (Outdoor unit)
3
Open/short of outdoor unit thermistors
UP
U3,U4
Others
14
Other errors (Refer to the technical manual for the outdoor unit.)
12
14
Fb (FB)*
PL
Indoor unit control system error (memory error, etc.)
E0, E3
E1, E2 Remote controller control board error
Remote controller transmission error
Abnormality of refrigerant circuit
Compressor overcurrent interruption
As for indoor
unit, refer to
indoor unit's
service manual.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38

Mitsubishi Electric SUZ-KA18NA2 Owner's manual

Category
Split-system air conditioners
Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI