  • Hello! I have analyzed the installation guide for KMC Controls room temperature sensors STE-6010, STE-6011, STE-6013, and STE-6015. This document provides detailed instructions on mounting the sensors on various surfaces, including hollow walls and handy boxes. It also describes how to remove the cover, connect the wires, and includes wiring diagrams. I'm ready to answer any questions you might have about your new sensor based on this guide.
  • Where should the sensor be installed?
    How is the cover removed?
    Can the sensor be mounted on a hollow wall?
    What type of backplate is needed for a handy box installation?
STE-6010/6011/6013/6015 Room Temperature Sensors 1 Installation Guide
2.438
2.250
R 3.094
R .187
.643 .450
STE-6013 STE-6011
.475
max.
STE-6010/6015
Modular
RJ-45
Jack
Four-pin
EIA-485
PC Data
Port
Clamp
(Screw-type)
Terminals
Clamp
(Screw-type)
Terminals
.149
Installation Guide
Room Temperature Sensors
STE-6010/6011/6013/6015
Mounting 1
Location and Cover Removal 1
STE-6010/6013/6015 Only 1
STE-6011 Only 1
Controller Connection 2
STE-6010/6015 2
STE-6011 2
STE-6013 2
Maintenance 2
More Information 2
Mounting
4. Aachthecabletotheterminalblockorjack
accordingtotheappropriatewiringdiagramon
thenextpage.
5. Replacethecover.
STE-6011 Only
Handy Box Installation (Recommended)
1. MountauniversalbackplateHMO-6036tothe
handyboxusingthetwoscrewsprovided.
2. Removethecoverfromthebackpanel.
3. AachwiresaccordingtotheSTE-6011wiring
diagramonthenextpage.
4. Aachthebackpaneltothebackplateusingtwo
screws.
5. Checkthatleadstothethermistorarestraight
andthethermistoriscompletelyextended.
6. Replacethecover.
Hollow Wall Installation
1. Removethecoverfromthebackpanel.
2. Usethebackpanelasatemplatetodrilltwo
holesformountingscrews(7/64inchesor3mm
indiameterand1.4inches,1-13/32inches,or35.6
mmapart)andtocutacenterhole(7/8inchor20
mm)fortheterminalblockorjack.
3. AachwiresaccordingtotheSTE-6011wiring
diagramonthenextpage.
4. Aachthebackpaneltothewallusingtwo
#6self-threadingscrews.(Plasticanchorsare
recommended,andthesizeoftheholeswillthen
needadjusting.)
5. Checkthatleadstothethermistorarestraight
andthethermistoriscompletelyextended.
6. Replacethecover.
All dimensions
are in inches
Location and Cover Removal
Installthesensoronaninsidewallwhereitcansense
theaverageroomtemperatureandbeawayfrom
directsunlight,heatsources,windows,airvents,
andaircirculationobstructions(curtains,furniture,
etc.).Itcanbemountedonahollowwallor(with
auniversalbackplateHMO-6036/6036W)toa2x4
inchhandybox.
Thecoverisheldtotheblack,backpanelbythree,
small,roundpegsthattintheholesofthecover.
Theboompegisonatabandsnapsintothecenter
boomhole.
1. WithasmallPhillipsscrewdriverorhexwrench,
press in and hold the tab buon that snaps into
the center hole on the boom cover.
2. Carefullypullorprythebackpanelfromthe
frontcover.
STE-6010/6013/6015 Only
Handy Box Installation (Recommended)
1. Mountauniversalbackplate
HMO-6036orHMO-6036Wtothe
handyboxusingthetwoscrews
provided.
2. Removethecoverfromthebackpanel.
3. Aachthebackpaneltothebackplateusingthe
twoscrewsprovided.
4. Aachthecabletotheterminalblockorjack
accordingtotheappropriatewiringdiagramon
thenextpage.
5. Replacethecover.
Hollow Wall Installation
1. Removethecoverfromthebackpanel.
2. Usingthebackpanelasatemplate,drilltwoholesfor
mountingscrews(7/64inchesor3mmindiameter
and1.4inches,1-13/32inches,or35.6mmapart)and
cutacenterhole(sizeneededisdependentonmodel)
fortheterminalblockorjack.
3. Aachthebackpaneltothewallusingtwo
#6self-threadingscrews.(Plasticanchorsare
recommended,andthesizeoftheholeswillthen
needadjusting.)
STE-6010/6011/6013/6015 Room Temperature Sensors 2 Installation Guide
STE-6013
STE-6011
Controller Connection
Connectwiresasshownfortherelevantmodel.
Thermistor (10K Ohms)
(Wires are
interchangeable)
ConnectinganSTE-6010/6015toaKMCcontroller
requiresaspecialcablewith(onthesensorend)an
RJ-45modularconnectorand(onthecontrollerend)
anRJ-11modularconnectorwithadditionalwiresfor
KMCcontrollerinputs.Purchasingpre-assembled
cablesfromKMCismorecost-eectiveandreliable
thancreatingcustomcablesintheeld.Useoneof
thefollowingcables:
• KMD-5693=25feet
• KMD-5694=50feet
• KMD-5695=75feet
Theadditionalwireconnectionstothecontrollerare:
Orangeisthethermistorsignaltothecontrollers
appropriateinput
Greenistheoptional10 VDC supply voltage
fromanoutputofacontrollertotheSTE-6015
LED(fortheSTE-6010,cliportapetheunused
wire)
Orange/whiteshouldbeclippedortapedback
sinceasetpointsignalisnotusedwithanSTE-
6010/6015
STE-6010/6015
KMD–5693 = 25 feet; KMD–5694 = 50 feet; KMD–5695 = 75 feet
1 8
Orange Wire = Thermistor Input to Controller
Orange/White Wire = Setpoint Signal Input to Controller
(for STE-6014/6016/6017/6018 only; clip or tape when not used)
12 inches
52
RJ-11 and
Wire Leads
to Controller
RJ-45
to STE
Sensor
Green Wire = Aux. Supply Voltage to STE-6015/6018
(10 VDC) or STE-6016 (7.5/12 VDC) (clip or tape when not used)
RJ-11 RJ-45 Color
(Lead) 8 Orange
7 N.C.
(Lead) 6 Green
3 5 Blue
4 4 Blue/White
5 3 Green/White
2 N.C.
(Lead) 1 Orange/White
(Cables crossed, 20 AWG)
Common (“Ground”)
Thermistor (10K Ohms)
D
B
C
10 VDC LED Supply (from Controller)
(Override
Button)
Up (Toward Ceiling at Installation)
Maintenance
Carefulinstallationwillalsoensurelong-term
reliabilityandperformance.Removedustasneces-
saryfromholesintopandboom.Cleanwithaso,
dampclothandmildsoap.
© 2012 KMC Controls, Inc. 866-019-03C
KMC Controls, Inc.
19476IndustrialDrive
NewParis,IN46553
574.831.5250
www.kmccontrols.com;[email protected]
More Information
Model
Number
Interface
Features
Cable
Connections
Override
Button
LED
Status
Indicator
Screw
Clamp
Terminals
RJ-45
Connector
EIA-485
Data
Port
STE-6010-10 X X
STE-6011-10 X
STE-6013-10 X X X
STE-6015-10 X X X X
STE-6010/6011 STE-6013/6015
Formountingconsiderations,net-
workconnection,controllercon-
guration,programming,trouble-
shooting,andotherinformation,
seetheSTE-6010/6011/6013/6015
Application Guide.
Forgeneralproductinformation,
seetheSTE-6000 Series Room
Temperature Sensors/Transmit-
ters Data SheetontheKMC
Controlswebsite.
/