IXXAT IEM-200 PROFINET Owner's manual

Type
Owner's manual

This manual is also suitable for

Hard- / Software Manual
Industrial Ethernet Module
Modbus-TCP
IXXAT Automation GmbH
Leibnizstr. 15
88250 Weingarten
Germany
Tel.: +49 751 56146-0
Fax: +49 751 56146-29
Internet: www.ixxat.com
E-Mail: info@ixxat.com
Support
In case of unsolvable problems with this product or other IXXAT products
please contact IXXAT in written form:
Fax: +49 751 56146-29
E-Mail: support@ixxat.de
Further international support contacts can be found on our webpage
www.ixxat.com
Copyright
Duplication (copying, printing, microfilm or other forms) and the electronic
distribution of this document is only allowed with explicit permission of
IXXAT Automation GmbH. IXXAT Automation GmbH reserves the right to
change technical data without prior announcement. The general business
conditions and the regulations of the license agreement do apply. All
rights are reserved.
Registered trademarks
All trademarks mentioned in this document and where applicable third
party registered are absolutely subject to the conditions of each valid
label right and the rights of particular registered proprietor. The absence
of identification of a trademark does not automatically mean that it is not
protected by trademark law.
Document number: 4.01.0220.00000
Version: 1.5
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
1 Introduction .................................................................................... 11
1.1 Definitions, acronyms and abbreviations ............................... 11
1.2 References ................................................................................ 13
1.3 Important user information ...................................................... 14
1.4 Conventions Used in This Manual .......................................... 14
1.5 Support ..................................................................................... 14
1.6 Returning hardware ................................................................. 14
1.7 Key features .............................................................................. 15
1.8 Overview ................................................................................... 15
1.8.1 Working principle .......................................................................... 16
1.8.2 Ethernet ports ............................................................................... 16
1.8.3 Board-to-Board Connector ............................................................ 16
1.8.4 Memory interface .......................................................................... 16
1.8.4.1 Communication ...................................................................... 17
1.8.4.2 Process data .......................................................................... 17
1.8.5 Software concept .......................................................................... 20
1.8.5.1 Command channel ................................................................. 20
1.8.5.2 Service channels .................................................................... 20
1.8.5.3 State control ........................................................................... 20
2 Getting started ............................................................................... 23
2.1 Software directory structure .................................................... 23
2.2 EMI Ethernet Module Interface ............................................. 25
2.3 IEM demo application overview .............................................. 26
2.3.1 Startup .......................................................................................... 26
2.3.2 Configuration phase ...................................................................... 27
2.3.3 Service Channel access ............................................................... 28
2.3.4 Creation of variables ..................................................................... 28
2.3.5 Process data exchange ................................................................ 30
2.3.5.1 Data mapping ......................................................................... 30
2.3.5.2 Characteristics ....................................................................... 31
2.3.6 Storing/Restore configuration parameter ...................................... 31
2.3.7 Configuration structure ................................................................. 31
2.3.8 Registering events ........................................................................ 32
2.3.9 Error handling ............................................................................... 32
2.3.10 Generic structure of the demo application .................................... 32
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
2.3.11 First steps in the demo application ............................................... 33
2.3.11.1 Preparation and setup ............................................................ 34
2.3.11.1.1 Selection of the module access ....................................... 34
2.3.11.1.2 Startup .............................................................................. 34
2.3.11.1.3 Mode selection ................................................................. 35
2.3.11.1.4 Initial configuration ........................................................... 36
2.3.11.1.5 Creation of variables ........................................................ 36
2.3.11.1.6 Registering events ........................................................... 39
2.3.11.1.7 Starting the communication .............................................. 40
2.3.11.1.8 DemoMain ........................................................................ 40
3 Porting of the host application ..................................................... 41
3.1 Host system relevant units ...................................................... 41
3.1.1 Adaption of the Board support package (BSP) ............................. 41
3.1.2 Adaption of the memory management (GEO) .............................. 42
3.1.3 Adaption of the SPI driver ............................................................. 42
3.1.3.1 Data packet design ................................................................ 42
3.1.3.2 SPI bus performance ............................................................. 43
3.1.3.3 SPI - Serial Peripheral Interface (SPI.h, SPI.c)...................... 43
3.1.3.3.1 Types and Macros ............................................................ 43
3.1.3.3.2 Functions .......................................................................... 43
3.2 Configuring ............................................................................... 44
3.2.1 Endianess ..................................................................................... 44
3.2.2 Config.h ........................................................................................ 45
3.2.3 Target.h......................................................................................... 48
3.2.4 Integral.h ....................................................................................... 48
3.3 Scaling ...................................................................................... 48
3.3.1 Service channels .......................................................................... 48
3.3.2 Administration queues .................................................................. 49
3.3.3 Memory management ................................................................... 49
4 Ethernet Module Interface (EMI) API Description ..................... 50
4.1 EMI - Ethernet Module Interface .............................................. 50
4.1.1 Types and Macros ........................................................................ 50
4.1.1.1 EMI_k_MAX_FTP_USER_NAME_PASSWORD_LEN .......... 50
4.1.1.2 EMI_t_API_CONFIG .............................................................. 50
4.1.2 Functions ...................................................................................... 51
4.1.2.1 EMI_cmdPowerOnReset() ..................................................... 51
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
4.1.2.2 EMI_cmdBrdReset()............................................................... 51
4.1.2.3 EMI_cmdBrdInit() ................................................................... 52
4.1.2.4 EMI_cmdBrdRelease() ........................................................... 52
4.1.2.5 EMI_cmdBrdInfoReq() ........................................................... 53
4.1.2.6 EMI_cmdBrdInfoQuery() ........................................................ 54
4.1.2.7 EMI_cmdFirmwareVerGet() ................................................... 54
4.1.2.8 EMI_cmdHardwareVerGet() .................................................. 55
4.1.2.9 EMI_cmdProtocolGet() .......................................................... 55
4.1.2.10 EMI_cmdNumExtPortsGet() .................................................. 56
4.1.2.11 EMI_cmdChannelOpen() ....................................................... 56
4.1.2.12 EMI_cmdChannelClose() ....................................................... 57
4.1.2.13 EMI_cmdChannelStart() ........................................................ 58
4.1.2.14 EMI_cmdChannelStop() ......................................................... 58
4.1.2.15 EMI_cmdChannelReset() ....................................................... 59
4.1.2.16 EMI_cmdChannelConfigure() ................................................ 60
4.1.2.17 EMI_cmdCfgStore() ............................................................... 60
4.1.2.18 EMI_cmdCfgRestore() ........................................................... 61
4.1.2.19 EMI_cmdCommandRespQuery() ........................................... 62
4.1.2.20 EMI_cmdNetworkTimeReq() .................................................. 62
4.1.2.21 EMI_cmdNetworkTimeQuery() .............................................. 63
4.1.2.22 EMI_cmdNetworkInfoReq() .................................................... 63
4.1.2.23 EMI_cmdNetworkInfoQuery() ................................................ 64
4.1.2.24 EMI_evtEventRegister() ......................................................... 64
4.1.2.25 EMI_evtEventUnRegister() .................................................... 65
4.1.2.26 EMI_evtEventCheck() ............................................................ 66
4.1.2.27 EMI_srvRemoteConnOpen() ................................................. 66
4.1.2.28 EMI_srvRemoteConnClose() ................................................. 67
4.1.2.29 EMI_srvreqSend() .................................................................. 68
4.1.2.30 EMI_srvrespQuery() ............................................................... 69
4.1.2.31 EMI_srvrespSegmentQuery() ................................................ 70
4.1.2.32 EMI_srvrespServiceCompleted() ........................................... 71
4.1.2.33 EMI_srvconfSend() ................................................................ 71
4.1.2.34 EMI_srvindQuery() ................................................................. 72
4.1.2.35 EMI_srvindSegmentQuery() .................................................. 73
4.1.2.36 EMI_srvServiceHandle() ........................................................ 74
4.1.2.37 EMI_srvTransferContinue() .................................................... 75
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
4.1.2.38 EMI_stsStatusQuery() ............................................................ 75
4.1.2.39 EMI_stsLedQuery() ................................................................ 76
4.1.2.40 EMI_stsLinkQuery() ............................................................... 77
4.1.2.41 EMI_ioCyclDataReadAcquire() .............................................. 77
4.1.2.42 EMI_ioCyclDataReadRelease() ............................................. 78
4.1.2.43 EMI_ioCyclDataWriteAcquire() .............................................. 79
4.1.2.44 EMI_ioCyclDataWriteRelease() ............................................. 79
4.1.2.45 EMI_ioAcyclDataRead() ......................................................... 80
4.1.2.46 EMI_ioAcyclDataWrite() ......................................................... 81
4.1.2.47 EMI_ioCyclWriteImageSizeGet() ........................................... 81
4.1.2.48 EMI_ioCyclReadImageSizeGet() ........................................... 82
4.1.2.49 EMI_ioAcyclImageSizeGet() .................................................. 82
4.1.2.50 EMI_cmdIoctrl() ...................................................................... 83
4.1.2.51 EMI_cmdFtpUserSet() ........................................................... 83
5 Communication Protocols ............................................................ 85
5.1 PROFINET ................................................................................. 85
5.1.1 Device Description File ................................................................. 85
5.1.2 PROFINET device model ............................................................. 85
5.1.3 Variable access ............................................................................ 87
5.1.4 Process data mapping .................................................................. 88
5.1.5 Services ........................................................................................ 89
5.1.5.1 Connection management ....................................................... 89
5.1.5.2 Device structure management ............................................... 89
5.1.5.3 PROFINET specific indications from the IEM ........................ 89
5.1.5.4 Alarms .................................................................................... 90
5.1.5.5 I&M data (Identification and Maintenance) ............................ 90
5.1.6 States and events ......................................................................... 91
5.1.7 Managing persistent data ............................................................. 91
5.1.8 LEDs ............................................................................................. 92
5.2 Ethernet/IP ................................................................................ 93
5.2.1 Device Description File ................................................................. 93
5.2.2 Variable access ............................................................................ 93
5.2.2.1 Object model .......................................................................... 95
5.2.3 Ethernet/IP specific variable mapping ........................................ 100
5.2.3.1 Process data mapping ......................................................... 100
5.2.3.2 Configuration assembly ....................................................... 102
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
5.2.3.3 Signal access ....................................................................... 102
5.2.4 Services ...................................................................................... 102
5.2.4.1 Ethernet/IP Services ............................................................ 102
5.2.4.2 Remote Access .................................................................... 103
5.2.5 States and events ....................................................................... 103
5.2.6 Class 1 and class 3 connection handling ................................... 104
5.2.6.1 ForwardOpen verification ..................................................... 104
5.2.6.2 Connection established ........................................................ 104
5.2.6.3 Connection closed / connection timeout .............................. 105
5.2.7 LEDs ........................................................................................... 105
5.3 EtherCAT ................................................................................. 107
5.3.1 Device Description File ............................................................... 107
5.3.2 Device addressing ...................................................................... 107
5.3.3 E²PROM...................................................................................... 107
5.3.4 Data access ................................................................................ 107
5.3.4.1 Protocol specific addressing ................................................ 107
5.3.4.2 Protocol specific parameters ................................................ 108
5.3.4.3 Protocol specific attributes ................................................... 108
5.3.5 Initialization area ......................................................................... 108
5.3.5.1 Device addressing................................................................ 108
5.3.5.2 Data mapping ....................................................................... 109
5.3.6 Object dictionary ......................................................................... 109
5.3.6.1 Communication profile area ................................................. 109
5.3.6.2 Application profile area ........................................................ 110
5.3.6.3 Data types ............................................................................ 110
5.3.7 Configuration .............................................................................. 111
5.3.7.1 PDO mapping ....................................................................... 111
5.3.7.1.1 Configuration by tool (TwinCAT) .................................... 111
5.3.7.1.2 Configuration by application ........................................... 112
5.3.7.2 Detecting mapping errors ..................................................... 114
5.3.7.3 Store PDO configuration ...................................................... 115
5.3.8 Process data exchange .............................................................. 115
5.3.8.1 Static mapping ..................................................................... 115
5.3.8.2 Dynamic mapping ................................................................ 115
5.3.8.3 Synchronization.................................................................... 116
5.3.8.4 Safe output values ............................................................... 116
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
5.3.9 Service Data Object (SDO) ......................................................... 116
5.3.10 Protocol specific state handling .................................................. 117
5.3.11 Protocol specific events .............................................................. 117
5.3.12 Protocol specific commands ....................................................... 119
5.3.13 Protocol specific services ........................................................... 119
5.3.14 Bus cycle time ............................................................................. 120
5.3.15 Operating system load (minor fault) ............................................ 120
5.3.16 Parameter service ....................................................................... 120
5.3.16.1 Open a remote SDO connection .......................................... 120
5.3.16.2 Close a remote SDO connection ......................................... 120
5.3.16.3 Read a remote SDO connection .......................................... 121
5.3.16.4 Write remote data................................................................. 121
5.3.17 Mailbox service ........................................................................... 121
5.3.18 LEDs ........................................................................................... 121
5.4 Ethernet Powerlink ................................................................. 123
5.4.1 Device Description File ............................................................... 123
5.4.2 Process data mapping ................................................................ 125
5.4.3 Synchronization to IEM ............................................................... 125
5.4.4 LEDs ........................................................................................... 125
6 Error handling .............................................................................. 127
6.1 Error classes (priorities) ........................................................ 127
6.2 Assignment between errors and units .................................. 127
6.3 Assignment between errors and files ................................... 128
6.4 Extended error bit .................................................................. 129
6.5 Error Codes ............................................................................ 129
6.5.1 COM_k_UNIT_ID_HC_ABM (unit id 1) ....................................... 129
6.5.2 COM_k_UNIT_ID_HC_SHM (unit id 2) ...................................... 129
6.5.3 COM_k_UNIT_ID_HC_BCC (unit id 3) ....................................... 129
6.5.4 COM_k_UNIT_ID_HC_DCI (unit id 4) ........................................ 130
6.5.5 COM_k_UNIT_ID_HC_SPI (unit id 5) ......................................... 130
6.5.6 COM_k_UNIT_ID_HC_EMI (unit id 6) ........................................ 130
6.5.7 COM_k_UNIT_ID_HC_FUPH (unit id 7) ..................................... 133
6.5.8 COM_k_UNIT_ID_MC_ABM (unit id 50) .................................... 134
6.5.9 COM_k_UNIT_ID_MC_SHM (unit id 51) .................................... 135
6.5.10 COM_k_UNIT_ID_MC_BCC (unit id 52) .................................... 135
6.5.11 COM_k_UNIT_ID_MC_BSP (unit id 53) ..................................... 135
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
6.5.12 COM_k_UNIT_ID_MC_CRM (unit id 54) .................................... 135
6.5.13 COM_k_UNIT_ID_MC_BPW_GEN (unit id 108) ........................ 135
6.5.14 COM_k_UNIT_ID_MC_BPW_PNIO (unit id 109) ....................... 139
6.5.15 COM_k_UNIT_ID_MC_BPW_ETC (unit id 110) ........................ 146
6.5.16 COM_k_UNIT_ID_MC_BPW_EPL (unit id 111) ......................... 146
6.5.17 COM_k_UNIT_ID_MC_BPW_EIP (unit id 112) .......................... 147
6.5.18 COM_k_UNIT_ID_MC_OS (unit id 120) ..................................... 151
6.5.19 COM_k_UNIT_ID_MC_TCPIP (unit id 121) ............................... 151
6.5.20 COM_k_UNIT_ID_MC_TSE (unit id 122) ................................... 151
6.5.21 COM_k_UNIT_ID_MC_PNIO (unit id 128) ................................. 151
6.5.22 COM_k_UNIT_ID_MC_ETC (unit id 129) ................................... 151
6.5.23 COM_k_UNIT_ID_MC_EPL (unit id 130) ................................... 152
6.5.24 COM_k_UNIT_ID_MC_EIP (unit id 131) .................................... 152
6.5.25 COM_k_UNIT_ID_MC_DHSI (unit id 140) ................................. 152
6.5.26 COM_k_UNIT_ID_MC_EMHI (unit id 141) ................................. 152
6.5.27 COM_k_UNIT_ID_MC_HTH (unit id 142) ................................... 152
6.5.28 COM_k_UNIT_ID_MC_FUPM (unit id 150) ................................ 152
6.5.29 COM_k_UNIT_ID_MC_FUPMv2 (unit id 151) ............................ 154
7 Hardware ...................................................................................... 161
7.1 Connectors and LEDs ............................................................ 161
7.1.1 Board-to-Board Connector .......................................................... 161
7.1.1.1 Connector pin out ................................................................. 161
7.1.1.2 Signal description ................................................................. 162
7.1.1.2.1 Address inputs (ADDR1 ADDR13) ............................. 162
7.1.1.2.2 Byte enable lines (BE0# and BE1#) ............................... 163
7.1.1.2.3 Data input/output (D0 D15) ......................................... 163
7.1.1.2.4 Chip select (CS#) ........................................................... 164
7.1.1.2.5 Read (RD#) .................................................................... 164
7.1.1.2.6 Write (WR#) ................................................................... 164
7.1.1.2.7 7.2.7 SPI (SPI_CLK, SPI_CS#, SPI_MOSI, SPI_MISO) 164
7.1.1.2.8 GPIOs from application processor ................................. 164
7.1.1.2.9 GPIOs to application processor ..................................... 165
7.1.1.2.10 Reset (RESET#) ............................................................ 165
7.1.1.3 Pin location ........................................................................... 166
7.1.2 RJ45 connectors ......................................................................... 166
7.1.3 LED labeling ............................................................................... 166
7.1.4 PE and shielding recommendations ........................................... 167
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
7.2 Hardware interface ................................................................. 167
7.2.1 Parallel interface access ............................................................. 168
7.2.2 SPI interface access ................................................................... 168
7.3 Electrical specification........................................................... 169
7.3.1 Power supply .............................................................................. 169
7.3.2 I/O 3.3V LVTTL ........................................................................ 169
7.3.3 Timings for memory mapped access (MCI) ................................ 169
7.3.3.1 Timings on accessing parallel interface ............................... 169
7.3.3.2 Data read access ................................................................. 169
7.3.3.3 Data write access ................................................................. 169
7.3.3.4 Timing diagram .................................................................... 170
7.3.4 Timing for SPI based access ...................................................... 170
7.3.4.1 SPI settings .......................................................................... 171
7.3.4.2 Timing CS# .......................................................................... 171
7.4 Mechanical specification ....................................................... 172
7.4.1 PCB measurements .................................................................... 172
7.4.2 Mounting holes ........................................................................... 172
7.4.3 Board-to-Board connector .......................................................... 173
7.4.4 Ethernet Connector ..................................................................... 174
7.4.5 Height restrictions ....................................................................... 174
7.5 Environmental Specification ................................................. 175
7.5.1 Temperature ............................................................................... 175
7.5.2 Relative humidity ........................................................................ 175
8 Appendix ...................................................................................... 176
8.1 Shared Memory Layout .......................................................... 176
8.2 FCC Compliance ..................................................................... 177
8.3 EC Declaration of Conformity ................................................ 178
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
1 Introduction
1.1 Definitions, acronyms and abbreviations
API
Application Programming Interface
Application Process Identifier (PROFINET)
Application
Customer specific software implementation
BCC
Basic Communication Channel
BSP
Board Support Package
BPW
Bus Protocol Wrapper. Software part on the IEM that in-
terfaces a certain communication protocol stack.
CCI
Controller Communication Interface. Provides structures
and mechanisms to transfer data and messages between
host and module through the SHM (see description below)
CIP
Common Industrial Protocol
CLNK
command link
CoE
CAN application layer over EtherCAT
CRC
cyclic redundancy check
EDS
Electronic Data Sheet (EtherNet/IP)
EIP
EtherNet/IP
EMI
Ethernet Module Interface: API of the Industrial Ethernet
Module
Firmware
Throughout this document: The part of the Industrial
Ethernet Module API running on the Module.
GEO
Generic operating system
GSDML
General Station Description Markup Language
(PROFINET)
HC
Host Controller
Host
Target system including application and EMI
I&M
Identification and Maintenance Profile (PROFINET)
IEM
Industrial Ethernet Module
IOPS
IO Provider Status (PROFINET)
IOCS
IO Consumer Status (PROFINET)
IOXS
IO Provider/Consumer Status (PROFINET)
MC
Module Controller
MCI
Memory Controller Interface
Module
IEM containing BPW, CCI and protocol specific implemen-
tations
MN
Managing Node (POWERLINK)
MSM
Module State Machine: state machine on host controller
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
and IEM
Network variables
Other word for Process Image.
PE
protective earth
PDO
Process Data Object
PNIO
PROFINET I/O
Process Image
Data area where all input and output data of a system
(compare PLC) are combined.
RMA
return material authorization
RWWB
read while write buffer
SD
Service Data
SDO
Service Data Object
SHM
Shared Memory interface
SoC
Start of Cycle
Software
Throughout this document: The part of the Industrial
Ethernet Module API running on the Host Controller.
SPI
Synchronous Peripheral Interface
Unit
Functional block of the software
XDD
XML Device Description (POWERLINK)
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
1.2 References
[EIP1]
THE CIP NETWORKS LIBRARY
Volume 1
Common Industrial Protocol
Edition 3.15, November 2013
[EIP2]
THE CIP NETWORKS LIBRARY
Volume 2
EtherNet/IP Adaptation of CIP
Edition 1.15, April 2013
[EPL1]
Ethernet POWERLINK Communication Profile Specification
Version 1.1.0, 2008
[PNIO1]
GSDML Specification for PROFINET IO Draft in PI Review.
Version 2.16, June 2008
[PNIO2]
GSDML-Getting started
http://support.automation.siemens.com/WW/view/en/31410371
[PNIO3]
Application Layer services for decentralized periphery and distribut-
ed automation.
Specification for PROFINET IO
Version 2.2, October 2007 (Order No.: 2.712)
[PNIO4]
Application Layer protocol for decentralized periphery and distributed
automation.
Specification for PROFINET IO
Version 2.2, October 2007 (Order No.: 2.722)
[ETC1]
EtherCAT1 Specification Part 5: Application layer service definition
ETG.1000.5 S (R)
V1.0 of July 2008
[ETC2]
EtherCAT Specification Indicator and Labeling
ETG.1300 S (R)
V1.0.1
July 02, 2009
[ETC3]
EtherCAT Specification - Slave Information
ETG.2000 S (R)
V1.0.4
June 19, 2012
[HW1]
Altera Application Note AN447
Interfacing Cyclone III and Cyclone IV Devices with 3.3/3.0/2.5-V
LVTTL/LVCMOS I/O Systems
November 2009 AN-447-2.0
http://www.altera.com/literature/an/an447.pdf
1
EtherCAT® is registered trademark and patented technology, licensed by
Beckhoff Automation GmbH, Germany.
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
1.3 Important user information
This manual is intended to provide a good understanding of IXXAT’s Industrial
Ethernet Module (furthermore referenced as IEM).
As there are many applications of the IEM, those responsible for the use of
this device must ensure that all the necessary steps have been taken to verify
that the application meets all performance and safety requirements including
any applicable laws, regulations, codes, and standards.
1.4 Conventions Used in This Manual
The following conventions are used throughout this manual:
Numbered lists provide sequential steps
Bulleted lists provide information, not procedural or sequential steps
Hexadecimal values are written in the format NNNNh, where NNNN is the
hexadecimal value
All measurements expressed in this document have a tolerance of ±0.1mm
unless stated otherwise
16/32 bit values are generally stored in Intel (little-endian) format unless
stated otherwise
1.5 Support
For more information on our products, FAQ lists and installation tips please
refer to the support area on our homepage (http://www.ixxat.de). There you
will also find information on current product versions and available updates.
If you have any further questions after studying the information on our homep-
age and the manuals, please contact our support department. In the support
area on our homepage you will find the relevant forms for your support re-
quest. In order to facilitate our support work and enable a fast response,
please provide precise information on the individual points and describe your
question or problem in detail.
If you would prefer to contact our support department by phone, please also
send a support request via our homepage first, so that our support department
has the relevant information available.
1.6 Returning hardware
If it is necessary to return hardware to us, please download the relevant RMA
form from our homepage and follow the instructions on this form. In the case of
repairs, please also describe the problem or fault in detail on the RMA form.
This will enable us to carry out the repair quickly.
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
1.7 Key features
The IEM implements
One single software API supporting all implemented standards of industrial
Ethernet protocols
FPGA with NIOS II processor, covering all Ethernet communication proto-
col stack tasks (and thus reduction load on application processor to a min-
imum)
Supported protocols
o EtherCAT
o Ethernet/IP
o POWERLINK
o PROFINET
Pre-certification available (where applicable)
DPRAM interface guarantees data consistency
Optional SPI interface
On board LEDs
Galvanic isolated Ethernet interface
Certified components
Synthesis of all major design recommendations of the relevant industrial
Ethernet specifications
CE certified
1.8 Overview
Below you will find a schematic overview of the IEM, the application interface,
the internal data path and the Ethernet interface.
IEM
* depends on the used protocol
FPGA
DPRAM
RAM SPI Flash
PHY PHY
Ethernet
Port 1
Ethernet
Port 2
2x Duo LED
Switch / Hub
Optional*
Power Supply
2,5V/1,2V
3,3V Host Interface
Board-to-Board Connector
Figure 1-1: Schematic overview about the IEM
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
1.8.1 Working principle
The IEM is mechanically and electrically connected to the host application pro-
cessor by the Board-to-Board Connector. The FPGA design incorporates
amongst other components a dual ported memory (DPRAM) and a NIOS II
soft-core processor. This DPRAM serves as a shared memory over which the
communication between the IEM’s NIOS II processor and the host application
processor is handled.
1.8.2 Ethernet ports
The IEM provides two galvanic isolated RJ45 female connectors. The con-
nectors are designed to fulfill all mandatory requirements from the various in-
dustrial Ethernet specifications (PE, Shield, PHY, etc.). All Ethernet communi-
cation is handled completely by the IEM itself.
1.8.3 Board-to-Board Connector
The IEM is connected through a 50-pin 1.27 mm Board-to-Board Connector
which carries all control signals, address/data bus signals as well as the power
supply for the IEM.
The Board-to-Board Connector contains all signals to connect to the host CPU
either using an address and data bus (16 bit wide on IEM, 16/32 bit wide for
design-in) or SPI. Additionally, a reset pin as well as two general purpose pins
from and to the IEM, which can be used e.g. for IRQ are provided on the con-
nector.
1.8.4 Memory interface
Seen from the application CPU’s point of view the application interface is a
block of (dual ported) memory which contains a command channel, process
data interface and several data queues.
The DPRAM can be either accessed directly (memory mapped access) or via
SPI (indirect access). To realize consistency with SPI communication, a mirror
buffer on the host is used for the communication interface.
The software running on the IEM and the library provided for the host proces-
sor separate this memory into dedicated parts used for specific communication
tasks. The main differentiation is made between exchange of process data and
all other communication. The latter is thus in the following just referred to as
“communication” (see Figure 1-2).
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
1.8.4.1 Communication
Figure 1-2 shows an overview of the part of the DPRAM responsible for the
communication (command, event, service and status).
CMD Buffer
(CLNK)
Status Buffer
(RWWB)
Event (Cbk)
queue
Event queue
(FIFO)
SD queue
HC à MC
(FIFO)
SD queue
HC à MC
(FIFO)
SD queue
MC à HC
(FIFO)
SD queue
MC à HC
(FIFO)
Shared
Memory
SHM
IEM
Host
request response
request response
callback request response
request response
command
channel
event service channels (optional) status
Communication
SD queue
HC à MC
(FIFO)
SD queue
MC à HC
(FIFO)
indication
indication
SD queue
HC à MC
(FIFO)
SD queue
HC à MC
(FIFO)
confirmation
confirmation
(trigger from host) (trigger from module)
Figure 1-2: Schematic overview of communication area at DPRAM
1.8.4.2 Process data
The main concept is that all process data is read/written from/to buffers in the
DPRAM, which are additionally protected by a set of semaphores to ensure
data consistency on large memory blocks. When the buffers are released by
the application processor, the IEM handles all communication standalone
without any interaction from the application processor required.
Cyclic process data
Variables can be readable or writeable, but not read-/writeable. For each
data direction, three buffers are used and swapped after access.
Acyclic process data
Acyclic process data share one buffer; variables can be readable, writeable
and read-/writeable.
Status Buffer
(RWWB)
Status Buffer
(RWWB)
Output Data Status Buffer
(RWWB)
Status Buffer
(RWWB)
Input Data Acyclic Data
Shared
Memory
SHM
IEM
Host
Communication
Figure 1-3: Schematic overview of process area at DPRAM
What Figure 1-2 and Figure 1-3 depicted is displayed in the following figure in
more detail. Additionally it shows which API functions of the Ethernet Module
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
Interface (EMI) software are involved in the data flow. Please refer to Figure 1
4 later, when studying the functional interface (EMI) of the IEM.
What Figure 1-2 and Figure 1-3 depicted is displayed in Figure 1-4 in more
detail. Additionally it shows which API functions of the Ethernet Module Inter-
face (EMI) software are involved in the data flow. Please refer to Figure 1-4
later, when studying the functional interface (EMI) of the IEM.
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
CCI
CMD Buffer
(CLNK)
Status Buffer
(RWWB)
Event (Cbk)
queue
Event queue
(FIFO)
SD queue
HC à MC
(FIFO)
SD queue
HC à MC
(FIFO)
SD queue
MC à HC
(FIFO)
SD queue
MC à HC
(FIFO)
request response response
response
request
request
Shared Memory SHM
SD queue
HC à MC
(FIFO)
SD queue
MC à HC
(FIFO)
indication
indication
SD queue
HC à MC
(FIFO)
SD queue
HC à MC
(FIFO)
confirmation
confirmation
(trigger from host) (trigger from module)
Status Buffer
(RWWB)
Status Buffer
(RWWB)
Output Data Status Buffer
(RWWB)
Status Buffer
(RWWB)
Input Data Acyclic Data
request response
BCC
BCC_RequestSend()
BCC_ResponseTest()
BCC_ResponseRead()
CMD Buffer
request
request response
response
CCI_ClinkSendRequest()
CCI_ClinkTestResponse()
CCI_ClinkReadResponse()
CCI_FifoAcquireRead()
CCI_FifoReleaseRead()
CCI_FifoAcquireRead()
CCI_FifoReleaseRead()
CCI_FifoAcquireRead()
CCI_FifoReleaseRead()
CCI_FifoAcquireWrite()
CCI_FifoReleaseWrite()
CCI_FifoAcquireWrite()
CCI_FifoReleaseWrite()
CCI_RwwbAcquireRead()
CCI_RwwbReleaseRead()
EMI
EMI_cmdBrdInit()
EMI_cmdBrdRelease()
EMI_cmdBrdInfoReq()
EMI_cmdChannelOpen()
EMI_cmdChannelClose()
EMI_cmdChannelStart()
EMI_cmdChannelStop()
EMI_cmdChannelConfigure()
EMI_evtEventRegister()
EMI_evtEventUnRegister()
EMI_evtEventCheck()
EMI_srvreqSend()
EMI_srvServiceHandle()
EMI_srvRemoteConnOpen()
EMI_srvRemoteConnClose()
EMI_srvrespQuery() EMI_srvindQuery() EMI_srvconfSend() EMI_stsStatusQuery() EMI_ioCyclDataWriteAquire()
EMI_ioCyclDataWriteRelease()
EMI_ioCyclDataReadAquire()
EMI_ioCyclDataReadRelease()
EMI_ioAcyclDataRead()
EMI_ioAcyclDataWrite()
Callback
SD Data
Figure 1-4: Functional overview of the logical DPRAM layout
Introduction
Copyright IXXAT Automation GmbH
IEM Manual, 1.5
1.8.5 Software concept
1.8.5.1 Command channel
For basic interaction with immediate response between host and module, a
command channel is provided (see Figure 1-2 for an overview of the commu-
nication area in the DPRAM).
Commands are used for board initialization and channel access. The interface
functions of the command channel can be used either in blocking or non-
blocking mode. Blocking means that the function will return after the command
was executed and a result is available. Non-blocking means that the applica-
tion is responsible for receiving a result by polling with a corresponding query
function.
1.8.5.2 Service channels
Services provide a timeout controlled handshake messaging with request/
response and indication/confirmation mechanism between host and module.
A request is performed by the host and answered by the module by means of
a response. An indication is initiated from the module and answered by the
host by means of a confirmation. Size and layout of the transmitted data are
depending on the service. To avoid blocking, queues are used.
Services can be used depending on the protocol to access data. For example,
getting a value may be used from host to retrieve configuration data from the
module, in case of network access, the module may need host located data.
1.8.5.3 State control
The current state of the communication channel is represented by the MSM
(module state machine). The MSM is separated in a generic and a protocol
specific part. Access from command or service channel may be restricted by
the current state. State transitions between PROTOCOL_OFFLINE and PRO-
TOCOL_ONLINE are handled by protocol specific implementation. For better
readability, error states and sub states in case of a remote access are not
shown in Figure 1-5.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178

IXXAT IEM-200 PROFINET Owner's manual