INSTALLATION OF 125mm SINGLE SKIN FLUE SYSTEM WITH AN AGA
APPROVED GAS COWL
This Flue and Cowl system shall be installed only by an authorised person and in accordance
with the manufacturers installations below, local gas fitting regulations, municipal building
codes, AS 5601 Gas Installations and any other statutory regulations.
1. Inspect Flue Cowl components
for any obvious damage.
2. Position heater in final position
and prepare ceiling and roof
cutout positions using a string
line from heater flue outlet.
See figure 1.
3. Fit flue adaptor into heater
flue outlet.
4. Install flue lengths in turn, fitting
upper flue length inside the
lower flue length. Secure each
join with (3 off) rivets supplied.
5. Fit ceiling ring over flue at
appropriate time, secure to
ceiling by bending tabs over
ceiling material.
6. Slide the Flue Cowl over the
outside of a 125mm diameter
flue. Do not insert Flue Cowl
past the swage point. Ensure a
min of 500mm distance from
cowl to roof surface.
See figure 2.
7. Check flue system for alignment
and that the Flue Cowl is
venting normally.
125mm Cowl
Swage
(Insert flue pipe to
this point only)
Rivet or Tek screw
(3 places,
NOT supplied)
125mm DIA Flue pipe
125mm FLUE COWL
APPROVED TO AG 604
IF THE COUPLING IS ABOVE
ROOF LEVEL SEAL JOINT WITH
SILICON TO PREVENT WATER
INGRESSION
FLASHING TO PROVIDE A
WATERTIGHT SEAL
25mm MINIMUM CLEARANCE
TO COMBUSTIBLE MATERIAL
CEILING RING
UPPER LENGTH FITS INSIDE
LOWER LENGTH. RIVET
FLUE JOINS. RIVETS (6 OFF)
SUPPLIED WITH FLUE KIT
FLUE SPIGOT ADAPTOR
REAR SPACER
Note: Fit a minimum of two
lengths (1.8 m).of vertical flue
before fitting any 45° bends. If
bends are used, they must fit
inside the flue on. downwards
ends. Use no more than two 45°
bends in the total flue run and
maintain at least 250 mm of
straight flue pipe between the
bends.
FIGURE 1.
Shows Flue system in position. For more detail, refer
to heater installation booklet supplied with heater
or contact IXL Home on the phone number below.
125mm DIA
FLUE PIPE
315mm
TO C/L OF
FLUE FROM
FRONT OF
HEATER
MAINTAIN 25mm
MINIMUM
CLEARANCE
BETWEEN FLUE AND
COMBUSTIBLE
MATERIALS
500mm
MINIMUM
1K Marine Parade, Abbotsford, VIC 3067
FREE CALL: 1300 727 421
FIGURE 2.
Cowl installation.
  • Page 1 1

Cannon FLUERO-B User and Installation Guide

Type
User and Installation Guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI