Hilti CFS-M BAS User guide

Type
User guide
2119193 A1-04.2015
CFS-M BAS
www.hilti.in
70 mm
3d
Fire Rated Assembly / Assemblage Homolugué
Product:
Produt:
Location:
Endroit:
System #:
Système #:
Tel:
Installed by: Installation Date:
Date d’installation:
Repenetrated by:
Date:
4. Add 2 ½ parts mortar to 1 part water and stir thoroughly.
5. Apply mortar to a depth of 70 mm on top of mineral wool shuttering. 6. Fasten identification plate visibly and ensure seal complies with approval.
Do not apply loads to seal for at least 3 days.
3. Clean penetration and pre-moisten surfaces.
2. Tightly fit mineral wool board of 60 mm thickness and 160 kg/m3 density into
opening, leaving 70 mm to top of opening for mortar. Seal gaps around cables
with FS-One sealant.
1. Provide rebar and wire mesh support arrangement for assembly.
1 2
3 4
5 6
Printed: 14.04.2015 | Doc-Nr: PUB / 5225835 / 000 / 00