Honeywell TRUEDRY DH150 User manual

Type
User manual

This manual is also suitable for

TrueDRY™ DH150
Dehumidification System
PROFESSIONAL INSTALLATION GUIDE
1
Assemble
2
Duct
3
Plumb
4
Wire
69-2271EFS-01
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions can
damage the product or cause a hazardous condition.
Installation Guide
69-2271EFS—01 ii
Read and save these instructions.
Need Help?
For assistance with this product please visit http://yourhome.honeywell.com
or call Honeywell Customer Care toll-free at 1-800-468-1502
® U.S. Registered Trademark.
Copyright © 2008 Honeywell International Inc. All rights reserved.
• DonotinstallTrueDRYDH150'sexhaustendwithoutducting.
• TrueDRYDH150isdesignedtobeinstalledindoorsinaspacethatisprotectedfromrainand
flooding.
• Installtheunitwithspacetoaccessthebackorsidepanelsformaintenanceandservice.Donot
installwithservicepanelsinaccessible.
• Avoiddirectingthedischargeairatpeople,oroverthewaterinpoolareas.
• Ifusednearapoolorspa,becertainthereisnochancetheunitcouldfallintothewaterorbe
splashed,andthatitispluggedintoagroundfaultinterrupt(GFI)outlet.
• Donotusethedeviceasabenchortable.
• Toensurequietoperation,donotplacethedevicedirectlyonthestructuralsupportsofthehome.
Providevibrationisolationtominimizenoise.
• Adrainpanmustbeplacedundertheunitifinstalledabovealivingareaoraboveanareawhere
waterleakagecouldcausedamage.
Table of Contents
About your new dehumidifier
Maintaining ideal humidity .................................................................................. 1
Controls ................................................................................................................ 2
Specifications ....................................................................................................... 3
Installation
InstallationChecklist ........................................................................................... 4
IntendedApplication ...........................................................................................4
Ducting:InstalltoFitYourApplication.............................................................. 6
Plumbing ...............................................................................................................7
TerminalDescriptions .......................................................................................... 7
Wiring .................................................................................................................... 8
Checkout ............................................................................................................ 10
Maintenance
Cleaning .............................................................................................................. 11
Troubleshooting ................................................................................................. 12
Parts List ............................................................................................................ 16
Warranty ............................................................................................................. 17
TrueDRY DH150
1 69-2271EFS—01
TheHoneywell TrueDRYDH150ensuresthe homeis maintainedat properhumiditylevels throughitshigh perfor-
mance and efficiency.
Benefits
• Removesupto150pintsofwaterfromtheindoorair.
• Canbeductedforwhole-househumiditycontrol,oroperate
unductedtoaddressmoistureproblemareassuchasanatticor
crawl space.
• Easyaccesspanelsmakesservicequickandsimple.
Maintaining Ideal Humidity
Dewpointsandrelativehumidity(RH)affectthewayyourbodysenses
heat. Higher humidity levels cause the air to feel much hotter than the
actualtemperature.WhenTrueDRYisinstalledproperly,yourcooling
equipmentmaynotrunasmuchbecausedehumidifiedairfeelscooler
than humid air.
About the TrueDRY DH150 Dehumidifier
Idealhumidityisdefinedbyindustry
experts*asbeingbetween40-60%on
anaverageannualbasis.Whenindoor
humidityexceeds60%,thehomeismore
susceptibletomoldandmildewgrowth.
TrueDRYDH150safeguardsagainstexces-
sive humidity in the home year-round.
*American Society of Heating, Refrigerating and Air
Conditioning Engineers (ASHRAE).
MCR24780
0102030405060708090100
OPTIMUM
ZONE
BACTERIA
VIRUSES
FUNGI
MITES
RESPIRATORY
INFECTIONS
ALLERGIC RHINITIS
AND ASTHMA
CHEMICAL
INTERACTIONS
OZONE
PRODUCTION
ASHRAE RECOMMENDED WINTER DESIGN LEVEL
00159095808570756065505540453035202510150
001 4418312316210215110117014011019979593919
59 631031421811411
0117014011018969493919098878
09 221711311901601201001896959391909887868584838
58 801501201997959391909988
878685848382818089787
08 199888786868583828181808979787777767574737
57 0897978787777767675757474737372727
17079696
07 271717171717070707969686867676666656564646
WHAT THE AIR FEELS LIKE
HOW HOT THE HEAT-HUMIDITY COMBINATION MAKES IT FEEL.
EXAMPLE: AIR AT 90ºF WITH 50% RH FEELS LIKE 96ºF TO THE HUMAN BODY!
RELATIVE HUMIDITY (PERCENTAGE)
EXTREME DANGER
EXTREME CAUTION
CAUTION
M27328
DANGER
AIR TEMPERATURE
(DEGREES FAHRENHEIT)
SOURCE: TEMPERATURE - HUMIDIY INDEX WAS DERIVED BY R.G. STEADMAN, JOURNAL OF APPLIED METEOROLOGY, JULY 1979.
Installation Guide
69-2271EFS—01 2
VisionPRO IAQ Total Comfort System (YTH9421C1010)
•Controlsbothheating/coolinganddehumidification.
•Sensorincludedfordisplayingoutdoortemperature.
•Intuitiveuserinterfaceforeasy7-daytemperatureprogramming
•Easy-to-readbacklitdigitaldisplay.
•Maintenanceandservicereminders.
•Controlsotherindoorairqualityequipmentwhenyou’reready.
TheTrueDRYDH150maybeusedwithoneofthefollowingexternalcontrols:
TrueIAQ Digital Control (DG115EZIAQ)
•Automaticadjustmentsmaintainidealhumidity.
•Sensorfordisplayingoutdoortemperatureandhumidity.
•Showsactualanddesiredhumiditysettings.
•Advancedventilationprogrammingincludeseconomizingandextreme
condition shutdown.
•Maintenanceandservicereminders
•Controlsotherindoorairqualityequipmentwhenyou’reready.
Control Options
Manual Dehumidistat (H8908DSPST) and Automatic Ventilation
Controls (W8150A1001)
•Manualhumiditycontrolwithintuitivecomfortsettings.
•Integratedhumiditychartforaccuratecontrolinchangingoutdoorconditions.
•AutomaticW8150ventilationcontroltoASHRAEindustrycode,orfor
continuous operation.
TrueDRY DH150
3 69-2271EFS—01
InstallTrueDRYDH150accordingtoNationalElectricCodes.
Dimensions:
Specifications
Product weight:134lbs
Shipping weight:164lbs
Shipping dimensions:281/4in.Hx42in.Wx24in.D
Media Filter:MERV11,16in.Hx16in.Wx2in.D
Drain connection:3/4-in.threadedfemaleNPT
connection,withattached3/4-in.maleconnection.
Duct connections:Round10in.and6in.inlets.Oval
10in.x4in.outlet.
Cabinet:20gaugegalvanizedsteelpowder-coat
painted.
Input ratings
•Electricalinputvoltage:120VAC—1Phase—60Hz
nominal
•Inputcurrent:6.9amps
Output ratings
•Power transformer to R/C terminals:24VAC,
0.85A
•Energy Performance:3.6pintsperkilowatthour
(KWH).
Standards and approval body requirements
ETLtestedperULstandard474(ducteddehumidifier.)
Dry-Bulb
Temp
Wet-Bulb
Temp
Intake
Humidity
Capacity
(Pints/Day)
80°F 70°F 60%RH 150
70°F 61°F 60%RH 116
60°F 52°F 60%RH 88
Home Size
(square ft)
Dehumidifier Capacity Required to Maintain Desired Indoor RH*
60% RH Indoor (pints/day) 50% RH Indoor (pints/day) 40% RH Indoor (pints/day)
2080 49–54 55–58 71–78
2600 61–68 65–72 90–97
3120 75–82 79–86 95–110
*Basedonextremeclimateswhereoutdoorhumidityis70-90%RH.Forlessextremeclimates,largerhomescanbe
adequatelyservedwithlesscapacity.Actualrequirementsmayvary.
Airflow versus external static pressure
(0–1 in. water pressure) with collars attached
0in.WG 415CFM
0.4inWG. 365CFM
FRONT VIEW
6 DIAMETER
REAR VIEW
SIDE VIEW
37-1/2 (953) WITHOUT COLLARS
39-1/2 (1003) WITH COLLARS
19-15/16
(506)
20-5/8 (524)
10 DIAMETER
M27792
Insulation:Rvalue1
Compressor: Rotary-style
Refrigerant:2lb.,R-410.A
Operating Temp Range (outside cabinet):
56ºF-95ºF(13ºC-35ºC)
Operating Humidity Range: 0-99%RH
Installation Guide
69-2271EFS—01 4
Tools Required
- 3/8-in.hexdrive
- Drillorduct-cuttingtool
- Wirestripper/cutter
- Standard screwdriver
- Ducttape
- 8-in. round duct and starter collar
- 18–22gauge,5-bandthermostatwire
- 1/2-in.diameterdrainline(8ft)
- 1/2-in.drainclamps(quantity2)
Materials Provided
- Sheetmetalscrews(quantity9)
- 6-in. plastic duct collar
- 10-in.plasticductcollar
- 10-in.ovalx4in.plasticductcollar
Options:
- 1/2-in.drainp-trap(mayberequiredbylocalcode)
- Externalhumiditycontrol
•Manualdehumidistat(H8908DSPST),Auto
Ventilation(W8150A1001)
•TrueIAQ(DG115EZIAQ)
•VisionPROIAQ(YTH9421C1010)
Installation Checklist
WARNING:Installationmustbeperformedbyaqualifiedservicetechnicianandmustcomplywithlocal
codes.Removepowertothedevicebeforeinstallingorservicingthedevice.Failuretoconnectthe
device according to these instructions may result in damage to the device or the controls.
Intended Application
Fortheidealinstallation,drawairfromthecentralpartofthehomeandreturnittoisolatedareasofthehomelike
thebedrooms,den,utilityroom,orfamilyroom.Theductworkoftheexistingsystemcanbeusedtosupplyairto
the home.
TrueDRY DH150
5 69-2271EFS—01
M27793
M27794
Door and Collar Assembly
Door Install
Inserttabonthebottomofthedoorbetweenthefoam
installation and the metal side.
Push down on the plastic door latch and swing door shut.
Oncethedoorisshutreleasethedoorlatch.
Collar Install
Removethe2roundducts,1ovalduct,3sealsandsmall
bagofmountinghardwarefrominsidetherectangle
opening.
Adheresealsontothebackofeachductandmountthe
ducts to the front of the dehumidifier using screws pro-
vided.
Installation Guide
69-2271EFS—01 6
FlexductisrecommendedinconnectingtotheTrueDRYDH150collarstoreducevibrationnoise.
M24745
Electrical requirements:
115VACoutlet.Groundfault
interrupter(GFI)recommended.
Duct Sizing:Fortotalductlengths,useroundorrectangularductsizedaccordingly:
- 10-inchforlessthan25-ft
- 12-inchformorethan25-ft
Fortheoptionalfreshairventilationport,useroundinsulatedductsizedaccordingly:
- 6-inchroundforlengthsoflessthan50-ft.
- 8-inchroundforlengthsgreaterthan50-ft,orifmorethan100-cfmisrequired
Ducting: Install to Fit Your Application
Idealwhen…
• RunningTrueDRYDH150withA/Coperation.
• Minimizingdischargeairtemperature(DAT)
increase is preferred.
• Spacedictates.
Idealwhen…
• RunningTrueDRYDH150oppositeA/C
operation.RunningwithA/Coperationrequires
damperontheexhaustporttominimize
backdraftwhenTrueDRYDH150isnotonbut
A/Cis.
• MinimizingDATincreaseispreferred.
• Spacedictates.
Idealwhen…
• Dryingaspecificareaofthehouse.
• RunningwithA/Coperationrequiresbackdraft
damperontheexhaustporttominimize
backdraftwhenTrueDRYDH150isnotonbut
A/Cis.
• MinimizingDATincreaseispreferred.
Idealwhen…
• RunningTrueDRYDH150withA/Coperation.
• Dryingaspecificareaofthehouse.
• MinimizingDATincreaseispreferred.
TrueDRYDH150canbeductedintothecentralforcedairsys-
tem,oroperateasastand-aloneindesignated,high-humidity
zoneswithinthehome,suchasabasementorcrawlspace.
A
Main Return to Main Return
SUPPLY
RETURN
AIR HANDLER
M27965
TrueDRY
B
Main Return to Main Supply
SUPPLY
RETURN
AIR HANDLER
TrueDRY
M27966
BACKDRAFT
DAMPER
C
Dedicated Return to Main Supply
D
Dedicated Return to Main Return
SUPPLY
RETURN
AIR HANDLER
M27968
TrueDRY
SEPERATE
RETURN
TrueDRY DH150
7 69-2271EFS—01
Connect1/2-in.draintubetomaleconnectiondrain
outlet.Securedraintubetoconnectorwithhoseclamp.
Run drain hose continuously downhill to an approved
drain or condensate pump. Route to drain with a trap if
possible.
PlaceTrueDRYDH150onsupportsthatraisethebase
abovethetopflangesonthedrainpanbeneathit.
Raisingitwilloptimizedrainflowbygravity.
Plumbing
Terminal Descriptions
CAUTION: Low-voltage Hazard.
Cancauseequipmentdamage.
DisconnectHVACequipmentbeforebeginning
installation.
Afour-blockwiringterminalislocatedonthesloped
endofTrueDRYDH150.
* Note:OuterscrewssecureblocktoTrueDRY
DH150.Notforwiring.
DHUM: Compressorandfanoperationfordehumidification.
R:  24Vhot
FAN:  Fanactivationonlyforventilation.
C: 24Vcommon
Bend10in.roundflexducttofitovertheDH150ovaloutlet.
Ducting to Oval Outlet
Installation Guide
69-2271EFS—01 8
Wiring
M27941
FAN
C
R
DHUM
M27795
1
2
3
4
DHUM
(COMPRESSOR
AND FAN)
R
FAN
C
1
3
2
GRN
GRN
TrueDRY DH150
9 69-2271EFS—01
Wire the TrueDRY DH150 according to the diagram that applies to your desired operation.
Followthisdiagramforductedoperationwithanexternalhumiditycontrol.
Wiring
TrueDRY
HVAC
MECHANICAL
DEHUMIDISTAT
THERMOSTAT
GYWRRc
GYWR C
M27797
DRY
CONTACTS
+
+
FAN
C
DPDT RELAY,
2.6A
DHUM
R
TrueDRY
HVAC
MECHANICAL
DEHUMIDISTAT
THERMOSTAT
GY
W
R
Rc
GYWR C
M27798
DRY
CONTACTS
DHUM
+
+
R
FAN
C
DPDT
RELAY,
2.6A
EARD-6
AT120
R
C
DAMPER
AUX
REMOTE
W8150A
G
R
C
C
W
G
Forductedoperationwithexternalhumidityandventilationcontrol,followthisdiagram.
Installation Guide
69-2271EFS—01 10
FollowthisdiagramifusingTrueDRYDH150withVisionPROIAQ.
FollowthisdiagramifusingTrueDRYDH150withapowereddehumidistatsuchasTrueIAQ(DG115EZIAQ).
Wiring
HVAC
THERMOSTAT
GYWRRc
M27799
IF A THERMOSTAT OTHER THAN A TH5110, TH5220, TH5320, TH6110, TH6220, TH6320, TH8110,
TH8320, OR TH8321 IS USED, A RELAY MAY BE REQUIRED TO ISOLATE THE G WIRE.
PROGRAM ISU SETTING 60 TO Ø TO FORCE SYSTEM FAN ON WITH DEHUMIDIFICATION CALL.
DHUM
R
FAN
C
+
+
C
68
40
55
1215
:
76
%
%
In
Out
PM
R
C
W
Y
G
R
C
SENSOR
SENSOR
SWITCH
W
G
VENT
VENT
DEHUM
DEHUM
HUM
HUM
OUTDOOR
SENSOR
(PROVIDED)
EARD-6
TrueIAQ
1
1
2
2
TrueDRY
M27800
FAN
FURNACE BOARD
EQUIPMENT INTERFACE MODULE (EIM)
G
C
CONV.HP
1
2
3
C
R
RC
RH
W1
W2
W3
Y
Y2
G
O/B
AUX
AUX2
Y
Y2
G
H1
U
M2
D1
H
M2
V1
N
T2
HEAT 1 RELAY
HEAT 2 RELAY
HEAT 3 RELAY
COOL 1 RELAY
COOL 2 RELAY
FAN RELAY
VISIONPRO IAQ
D-1
R-2
C-3
DHUM
R
FAN
C
+
+
OR
TrueDRY
EARD-6
ApplypowertoTrueDRYDH150.TurnthehumiditycontroltoalowRH%leveltoinitiateahumiditycall.Confirm
thattheTrueDRYDH150compressorandfanturnon.Thefurnaceblowerwillalsoturnontocirculateair.Thiswill
takeuptotwominutes.Besuretoturnthisbackdown(oroff)whencheckoutiscomplete.Turningthehumidity
controltoOffwillturnTrueDRYDH150off.
Checkout
TrueDRY DH150
11 69-2271EFS—01
Onanannualbasis,maintenanceisrequiredtoensureTrueDRYrunsatpeakefficiency.
Cleaning
1 2
3 4
UnplugTrueDRYDH150beforebeginning
service. Push down the door release and
pull.Thefiltercanberemovedfromeither
side.
Gripfiltertabatbottomtoremove.
Replace with new filter.
Usinga1/2-in.hexdriveorstandardscrew-
driver,removetheeightscrewsoneither
sideoftheTrueDRYDH150.Thesideand
toppanelscanthenberemoved.Usinga
dampcloth,wipeexcessdustanddebris
fromblower,refrigerantcoils,andcompres-
sor coils. Reattach panels and collars when
finished.
5
Whenserviceiscomplete,initiateacallfor
dehumidificationandcheckthatthecom-
pressorandfanactivate.Ifusingthedigital
VisionPROIAQorTrueIAQcontrols,reset
maintenance reminders.
Checkthedrainconnectionanddrainline
toensureitisclearofdebrisandsludge.
Ensureallhoseconnectionsaresecureonce
maintenance of the drain lines is complete.
Installation Guide
69-2271EFS—01 12
Problem Recommended Troublshooting Steps
Nodehumidification,neither
impeller fan nor compressor run
with fan switch and ventilation
timerOFF.
1. Unitunpluggedornopowertooutlet.
2. Humidity control set too high or defective.
3. Loose connection in internal or control wiring.
4. DefectiveCompressorrelay.
5. Defectivecontroltransformer.
6. Low pressure Control open.
7. OptionalCondensatePumpSafetySwitchopen.
Nodehumidification,compressor
doesnotrunbutimpellerfanruns
with fan switch and ventilation
timerOFFandhumiditycontrol
turnedtoON.
1. Defectivecompressorruncapacitor.
2. Badconnectionincompressorcircuit.
3. Defectivecompressoroverload.
4. Defectivecompressor.
5. Defrostthermostatopen.
Impellerfanrunswithfanswitch
andventilationtimerOFF,but
compressor cycles on & off.
1. Lowambienttemperatureand/orhumiditycausingunittocyclethrough
defrost mode.
2. Defectivecompressoroverload.
3. Defectivecompressor.
4. Defrostthermostatdefective
5. Dirtyairfilter(s)orairflowrestricted.
6. Lowrefrigerantcharge,causingdefrostcontroltocycle.
7. Badconnectionincompressorcircuit.
CAUTION:ServicingtheTrueDRYDH150withitshighpressurerefrigerantsystemandhighvoltagecir-
cuitrypresentsahealthhazardwhichcouldresultindeath,seriousbodilyinjury,and/orpropertydamage.
Serviceshouldonlybeperformedbyaqualifiedservicetechnician.
Technical Description
Troubleshooting
TrueDRYDH150usesarefrigerationsystemsimilartoanaircondi-
tioner to remove heat and moisture from incoming air and add heat
totheairthatisdischarged.Hot,high-pressurerefrigerantgasis
routedfromthecompressortothecondensercoil.Therefrigerantis
cooledandcondensedbygivingupitsheattotheairthatisabout
tobedischargedfromtheunit.Therefrigerantliquidthenpasses
throughastrainerandcapillarytubingwhichcausestherefrigerant
pressureandtemperaturetodrop.Itnextenterstheevaporatorcoil
whereitabsorbsheatfromtheincomingairandevaporates.The
evaporatoroperatesinafloodedcondition,whichmeansthatallthe
evaporatortubescontainliquidrefrigerantduringnormaloperation.
Afloodedevaporatorshouldmaintainnearlyconstantpressureand
temperatureacrosstheentirecoil,frominlettooutlet.
Themixtureofgasandliquidrefrigerantentertheaccumulatorafter
leavingtheevaporatorcoil.Theaccumulatorpreventsanyliquid
refrigerantfromreachingthecompressor.Thecompressorevacuatesthecoolrefrigerantgasfromtheaccumulator
and compresses it to a high pressure and temperature to repeat the process.
CONDENSER
EVAPORATOR
CAPILLARY
TUBES
ACCUMULATOR
COMPRESSOR
STRAINER/FILTER
DRIER
M27404
TrueDRY DH150
13 69-2271EFS—01
Problem Recommended Troublshooting Steps
Impellerfandoesnotrunwithfan
switchineitherposition.Impeller
fan does not run with ventilation
timer activated. Compressor runs
brieflybutcycleson&offwith
humiditycontrolturnedtoON.
1. Looseconnectioninimpellerfancircuit.
2. Obstructionpreventsimpellerfanrotation.
3. Defectiveimpellerfan.
4. Defectiveimpellerfanrelay.
5. Defectiveimpellerfancapacitor.
Impellerfanrunswithfanswitch
ON.Impellerfandoesnotrunwith
ventilation timer activated.
1. Defectiveventilationtimer.
2. Timenotcorrectonventilationtimer.
3. Ventilationtimersettomanual&switchedOFF.
4. Defectivefanswitch.
Evaporatorcoilfrostedcontinu-
ously,lowdehumidifyingcapacity.
1. Defrostthermostatlooseordefective.
2. Low refrigerant charge.
3. Dirtyairfilter(s)orairflowrestricted.
4. Excessivelyrestrictiveductingconnectedtounit.
Unitnotprovidingventilation.
Ventilationtimernotoperating
correctly.
1. Iftimerisnotfunctioningcorrectlyresettimerandreprogram.
2. Checkcontrolwireconnections(checkconnectionsatfreshairdamper
also).
3. Defectivefreshairdamper.
4. Defectivefanswitch.
Unitremovessomewater,butnot
asmuchasexpected.
1. Airtemperatureand/orhumidityhavedropped.
2. Humiditymeterandorthermometerusedareoutofcalibration.
3. Unithasentereddefrostcycle.
4. Airfilterdirty.
5. Defectivedefrostthermostat.
6. Low refrigerant charge.
7. Airleaksuchasloosecoverorductingleaks.
8. Defectivecompressor.
9. Restrictiveducting.
10.OptionalCondensatePumpSafetySwitchopen.
Troubleshooting
Installation Guide
69-2271EFS—01 14
Refrigerant Charging
Iftherefrigerantchargeislostduetoserviceoraleak,anewchargemustbeaccuratelyweighedin.Ifanyofthe
oldchargeisleftinthesystem,itmustberecoveredbeforeweighinginthenewcharge.Refertotheunitnameplate
for the correct charge weight and refrigerant type.
Impeller Fan Replacement
Themotorizedimpellerfanisaunitaryassemblyconsistingofthemotorandimpellerfan.Ifdefective,thecomplete
assemblymustbereplaced.
1. Unplugthepowercord.
2. Removethecabinetaccesspanel.
3. Removethescrewattachingtheimpellerfansupportbrackettothebase.
4. Disconnecttheimpellerfanleadsinsidetheelectricbox.
5. Removefan/bracketassemblybyremoving3screwsfromthebracketandinletringassembly.
6. Removethedefectiveimpellerfanfromthebracketandreplacewithitwiththenewimpellerfan.
7. Reassemblethenewimpellerfanbyreversingtheaboveprocedure.Note:Therearetwopinsonthebacksideof
thecabinetthatmustalignwiththetwoholesintheimpellerfansupportbracket.
Compressor/Capacitor Replacement
Thiscompressorisequippedwithatwoterminalexternaloverloadandaruncapacitor,butnostartcapacitoror
relay
Checking Compressor Motor Circuits
Performthefollowingtestsiftheimpellerfanrunsbutthecompressordoesnotwiththefanswitchandventilation
timerOFFandthehumiditycontrolON.
1. Unplugtheunit;removethecabinetsideandtheelectricalconnectioncoveronthecompressortop.
2. PlugintheunitandturnthehumiditycontroltoON.Checkfor110voltsfromcompressorterminalRto
overloadterminal3usinganACvoltmeter.Ifvoltageispresent,gotostep3.Ifnovoltage,theremaybealoose
connectioninthecompressorcircuit.Testeachcomponentforcontinuity.Seetheappropriatesectionifadefect
is suspected.
3. Unplugtheunit,andthendisconnecttheredandyellowwiresfromcompressorterminalsR&S.Usingan
ohmmetercheckcontinuitybetweenthepointslistedbelow.
4. CompressorterminalsCandS:Nocontinuityindicatesanopenstartwinding.Thecompressormustbe
replaced.Normalstartwindingresistanceis3to7ohms.
5. CompressorterminalsCandR:Nocontinuityindicatesanopenrunwinding.Thecompressormustbereplaced.
Normalrunwindingresistanceis.5to2ohms.
6. CompressorterminalCandoverloadterminal1:Nocontinuityindicatesadefectiveoverloadlead.
7. Overloadterminals1and3:Ifthereisnocontinuity,theoverloadmaybetripped.Wait10minutesandtryagain.
Ifthereisstillnocontinuity,itisdefectiveandmustbereplaced.
8. CompressorterminalCandcompressorcase:Continuityindicatesagroundedmotor.Thecompressormustbe
replaced.
9. Disconnectthewiresfromtheruncapacitor.SettheohmmetertotheRx1scale.Thecapacitorisshortedand
mustbereplacedifcontinuityexistsacrossitsterminals.Ifthereisnoneedlemovementwiththemeterseton
theRx100000scale,thecapacitorisopenandmustbereplaced.
10.Reconnectthewirestothecompressorandcapacitor.Pluginandturnontheunit.Ifthecompressorfailsto
start,replacetheruncapacitor.
11.Iftheunitstilldoesnotstart,addingahard-startkit(relay&capacitor)willprovidegreaterstartingtorque.Ifthis
doesn'twork,thecompressorhasaninternalmechanicaldefectandmustbereplaced.
Troubleshooting
TrueDRY DH150
15 69-2271EFS—01
Replacing a Burned Out Compressor
Therefrigerantandoilmixtureinacompressorischemicallyverystableundernormaloperatingconditions.
However,whenanelectricalshortoccursinthecompressormotor,theresultinghightemperaturearccausesapor-
tionoftherefrigerantoilmixturetobreakdownintocarbonaceoussludge,averycorrosiveacid,andwater.These
contaminantsmustbecarefullyremovedotherwiseevensmallresidueswillattackreplacementcompressormotors
and cause failures.
Thefollowingprocedureiseffectiveonlyifthesystemismonitoredafterreplacingthecompressortoinsurethatthe
clean up was complete.
1. Thisprocedureassumesthatthepreviouslylistedcompressormotorcircuittestsrevealedashortedoropen
winding.
2. Removeandproperlydisposeofthesystemcharge.DONOTventtherefrigerantorallowittocontactyoureyes
orskin.
3. Removetheburnedoutcompressor.Userubberglovesifthereisanypossibilityofcontactingtheoilorsludge.
4. Tofacilitatesubsequentsteps,determinethetypeofburnoutthatoccurred.Ifthedischargelineshowsno
evidenceofsludgeandthesuctionlineisalsocleanorperhapshassomelightcarbondeposits,theburnout
occurred while the compressor was not rotating. Contaminants are therefore largely confined to the compressor
housing.Asingleinstallationofliquidandsuctionlinefilter/drierswillprobablycleanupthesystem.
Ifsludgeisevidentinthedischargeline,itwilllikelybefoundinthesuctionline.Thisindicatesthecompressor
burnedoutwillrunning.Sludgeandacidhavebeenpumpedthroughoutthesystem.Severalchangesoftheliquid
andsuctionfilter/drierswillprobablybenecessarytocleansethesystem.
5. Correctthesystemfaultthatcausedtheburnout.Consultthefactoryforadvice.
6. Installthereplacementcompressorwithanewcapacitorandanoversizedliquidlinefilter.
Inarunningburnout,installanoversizedsuctionlinefilter/drierbetweentheaccumulatorandcompressor.
Thoroughlyflushtheaccumulatorwithrefrigeranttoremovealltrappedsludgeandtopreventtheoilholefrom
becomingplugged.Astandingburnoutdoesnotrequireasuctionlinefilter/drier.
7. Evacuatethesystemwithagoodvacuumpumpandaccuratevacuumgauge.Leavethepumponthesystem
for at least an hour.
8. Operatethesystemforashortperiodoftime,monitoringthesuctionpressuretodeterminethatthesuction
filterisnotbecomingplugged.Replacethesuctionfilter/drierifpressuredropoccurs.Ifasevererunningburn
outhasoccurred,severalfilter/driersmayhavetobereplacedtoremovealloftheacidandmoisture.
NOTE:NEVERusethecompressortoevacuatethesystemoranypartofit.
Replacing a Compressor, Non-Burnout
Removetherefrigerantfromthesystem.Replacethecompressorandliquidlinefilter/drier.Chargethesystemto50
PSIGandcheckforleaks.Removethechargeandweighintherefrigerantquantitylistedonthenameplate.Operate
the system to verify performance.
Defrost Thermostat
Thedefrostthermostatisattachedtotherefrigerantsuctiontubebetweentheaccumulatorandthecompressor.It
willautomaticallyshutthecompressoroffifthelowsiderefrigeranttemperaturedropsduetoexcessivefrostfor-
mationontheevaporatorcoil.Theimpellerfanwillcontinuetorun,causingairtoflowthroughtheevaporatorcoil
andmelttheice.Whentheicehasmelted,theevaporatortemperaturewillriseandthethermostatwillrestartthe
compressor.
Troubleshooting
Installation Guide
69-2271EFS—01 16
Parts List
Description Part Number
HeatExchanger 50035445-001
Evaporator 50035445-002
CapillaryTubes.050in.x.124in.x59.00in. 50035445-003
Compressor—Toshiba8.1 50035445-004
Accumulator 50035445-005
Filter/Drier 50035445-006
Tube—Cond.toFilter 50035445-007
Tube—DischargeLine 50035445-008
Condensor 50035445-009
Impeller 50035445-010
Relay/Blower 50035445-011
45mFdCapacitor—Compressor 50035445-012
Transformer 50035445-013
Relay/Compressor 50035445-014
15mFdCapacitor—Impeller 50035445-015
Collar—10in. 50035445-016
Collar—Oval10in.x4in. 50035445-017
Collar 6 in. with damper 50035445-018
Leveling Foot 50035445-019
FilterMERVII 50035445-020
TRANSFORMER
RELAY
COMPRESSOR
HEAT
EXCHANGER
CONDENSOR
EVAPORATOR
CAPACITOR
COMPRESSOR
FILTER DRIER
DISCHARGE
TUBE
ACCUMULATOR
CAPILLARY
TUBES
M27801
TUBE COND.
TO FILTER
TUBE
DISCHARGE
LINE
COLLAR OVAL
10 INCH
LEVELING
FOOT
IMPELLER
RELAY/
BLOWER
CAPACITOR
IMPELLER
TrueDRY DH150
17 69-2271EFS—01
Honeywellwarrantsthisproducttobefreefromdefectsintheworkmanshipormaterials,undernormaluseand
service,foraperiodoffive(5)yearsfromthedateofpurchasebytheconsumer.Ifatanytimeduringthewarranty
periodtheproductisdeterminedtobedefectiveormalfunctions,Honeywellshallrepairorreplaceit(atHoneywell’s
option).
Iftheproductisdefective,
(i)returnit,withabillofsaleorotherdatedproofofpurchase,totheplacefromwhichyoupurchasedit;or
(ii)callHoneywellCustomerCareat1-800-468-1502.CustomerCarewillmakethedeterminationwhethertheprod-
uctshouldbereturnedtothefollowingaddress:HoneywellReturnGoods,Dock4MN10-3860,1885DouglasDr.N.,
GoldenValley,MN55422,orwhetherareplacementproductcanbesenttoyou.
Thiswarrantydoesnotcoverremovalorreinstallationcosts.Thiswarrantyshallnotapplyifitisshownby
Honeywellthatthedefectormalfunctionwascausedbydamagewhichoccurredwhiletheproductwasinthepos-
session of a consumer.
Honeywell’ssoleresponsibilityshallbetorepairorreplacetheproductwithinthetermsstatedabove.HONEYWELL
SHALLNOTBELIABLEFORANYLOSSORDAMAGEOFANYKIND,INCLUDINGANYINCIDENTALOR
CONSEQUENTIALDAMAGESRESULTING,DIRECTLYORINDIRECTLY,FROMANYBREACHOFANYWARRANTY,
EXPRESSORIMPLIED,ORANYOTHERFAILUREOFTHISPRODUCT.Somestatesdonotallowtheexclusionor
limitationofincidentalorconsequentialdamages,sothislimitationmaynotapplytoyou.
THISWARRANTYISTHEONLYEXPRESSWARRANTYHONEYWELLMAKESONTHISPRODUCT.THEDURATION
OFANYIMPLIEDWARRANTIES,INCLUDINGTHEWARRANTIESOFMERCHANTABILITYANDFITNESSFORA
PARTICULARPURPOSE,ISHEREBYLIMITEDTOTHEFIVE-YEARDURATIONOFTHISWARRANTY.Somestates
donotallowlimitationsonhowlonganimpliedwarrantylasts,sotheabovelimitationmaynotapplytoyou.
Thiswarrantygivesyouspecificlegalrights,andyoumayhaveotherrightswhichvaryfromstatetostate.
Ifyouhaveanyquestionsconcerningthiswarranty,pleasewriteHoneywellCustomerRelations,1985DouglasDr,
GoldenValley,MN55422orcall1-800-468-1502.InCanada,writeRetailProductsON15-02H,HoneywellLimited/
HoneywellLimitée,35DynamicDrive,Toronto,OntarioM1V4Z9.
5-Year Limited Warranty
HoneywellInternationalInc.
1985DouglasDriveNorth
GoldenValley,MN55422
http://yourhome.honeywell.com
Automation and Control Solutions
®U.S.RegisteredTrademark.
©2008HoneywellInternationalInc.
69-2271EFS—01M.S.12-08
Honeywell Limited-Honeywell Limitée
35DynamicDrive
Toronto,OntarioM1V4Z9
PrintedinU.S.A.onrecycled
papercontainingatleast10%
post-consumerpaperfibers.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Honeywell TRUEDRY DH150 User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI