Mitsubishi Electric PAC-SG96HR-E User manual

Category
Split-system air conditioners
Type
User manual

Mitsubishi Electric PAC-SG96HR-E is a power supply terminal kit designed for A-Control indoor units, enabling separate power supplies for the indoor and outdoor units in PUHZ applications. It features a terminal block with a capacity of 30A/330V, made from denatured melamine, and comes with lead wires already connected. The kit includes a screw for attaching the terminal block, a fastener for binding lead wires, and a label to indicate the separate power supply configuration.

Mitsubishi Electric PAC-SG96HR-E is a power supply terminal kit designed for A-Control indoor units, enabling separate power supplies for the indoor and outdoor units in PUHZ applications. It features a terminal block with a capacity of 30A/330V, made from denatured melamine, and comes with lead wires already connected. The kit includes a screw for attaching the terminal block, a fastener for binding lead wires, and a label to indicate the separate power supply configuration.

E-101
OPTIONAL
PARTS
This kit (L/N/Earth) is used when the power supply of
the indoor unit and the outdoor unit is separated.
(For PUHZ applications only)
Photo
Specications
PSA-RP·KA series
PCA-M·KA series
Power Supply Terminal Kit
PAC-SG96HR-E
Unit : mm
Descriptions
Applicable Models
Dimensions
for new A-Control indoor units
(L/N/Earth)
NL
53.824
39.2 120
Connector 2P (Blue)
Denatured melamine
Terminal block material
30A/330V
Terminal block capacity
Terminal block (with lead wires connect-
ed) x 1, Screw x 1, Fastener (for binding
lead wires)
Parts composition
E-102
OPTIONAL
PARTS
This kit (L/N) is used when the power supply of the
indoor unit and the outdoor unit is separated.
(For PUHZ applications only)
Photo
Specications
PCA-RP71HAQ
PEAD-M·JA series
Power Supply Terminal Kit
PAC-SG97HR-E
Unit : mm
Descriptions
Applicable Models
Dimensions
for new A-Control
indoor units (L/N)
L N
3618.5
38 80
Connector 2P (Blue)
Denatured melamine
Terminal block material
15A/264V
Terminal block capacity
Terminal block (with lead wires connect-
ed) x 1, Screw x 1, Fastener (for binding
lead wires)
Parts composition
E-103
OPTIONAL
PARTS
Power Supply Terminal Kit for new A-Control Indoor units PAC-SG96,97HR-E
How to Use / How to Install
1. Overview
This kit is used when the power supply of the indoor unit and the outdoor unit is separated.
(for PUHZ applications only)
Refer to the installation manual of the indoor unit as well.
2. Provided parts
Comfirm the following parts are included.
Terminal block (lead wires already wired) x 1
Screw (to attach terminal block) x 1
Screw (to secure ground wire) x 1
Fastener (to tie lead wires) x 1
For PAC-SG96HR-E For PAC-SG97HR-E For PAC-SG96HR-E only
1:1 System
Simultaneous twin/triple/four system
L
N
S1
S2
S3
S1
S2
S3
1
2
L
N
<For models without heater>
•The indoor power supply
terminal kit is required.
•Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
•Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
AOutdoor unit power supply
BEarth leakage breaker
CWiring circuit breaker or isolating switch
DOutdoor unit
EIndoor unit / outdoor unit connecting cords
FRemote controller
GIndoor unit
HOption
JIndoor unit power supply
<For models without heater>
•The indoor power supply
terminal kits are required.
AOutdoor unit power supply
BEarth leakage breaker
CWiring circuit breaker or isolating switch
DOutdoor unit
EIndoor unit / outdoor unit connecting cords
FRemote controller
GIndoor unit
HOption
JIndoor unit power supply
KIndoor unit earth
A B C B C H
J
E
E
F
F
D
D G
K K K
H
G
G
H
G
H
G
H
L
N
L
N
S1
S2
S3
S1
S2
S3
1
2
L
N
S1
S2
S3
1
2
L
N
S1
S2
S3
1
2
L
N
S1
S2
S3
1
2
A B C B CJ
N
LN
LNN
1
22 1
3
3
Change the yellow and
blue relay connectors.
Terminal block
attachment hole
Terminal block
attachment hole
Relay connector
(blue)
Relay connector
(blue)
Relay connector (yellow)
Relay connector (yellow)
4
4
3. Attachment method
■ PAC-SG96HR
1.Remove the cover of electric parts
box. 2. Attach terminal block 1 using screw
2 in the direction shown in the figure.
3. Change the relay connectors of blue and yellow
lead wires, secure the ground wire using screw
4 at the position shown in the figure, and then
bundle the lead wires using fastener 3.
Ceiling suspended, PCA-MKA type:
E-104
OPTIONAL
PARTS
Terminal block
attachment hole
Terminal block
attachment hole
Relay connector
(yellow)
Relay connector
(yellow)
Relay connector
(blue)
Relay connector
(blue)
Change the yellow and
blue relay connectors.
1
12
2
3
3
122
1
Relay connector
(blue)
Relay connector
(blue)
Relay connector
(yellow)
Relay connector
(yellow)
Change the yellow and
blue relay connectors.
1.Remove the terminal block cover of
electric parts box.
■ PAC-SG97HR
Ceiling suspended for kitchens, PCA-RP71HAQ type:
2. Attach terminal block 1 using screw
2 in the direction shown in the figure.
3. Change the relay connectors of blue
and yellow lead wires, and then bundle
the lead wires using fastener 3.
3.Change the relay connectors of blue
and yellow lead wires.
TTerminal block attachment holeerminal block attachment hole
Ceiling concealed, PEAD-M.JA type
1.Remove the cover of electric parts
box. 2. Attach terminal block 1 using screw
2 in the direction shown in the figure.
Power Supply Terminal Kit for new A-Control Indoor units PAC-SG96,97HR-E
E-105
OPTIONAL
PARTS
4. Electric wiring
Be sure to do the electric wiring following the steps in each indoor unit installation manual.
6. DIP switch settings of the outdoor unit control board
It is necessary to change the settings of DIP switch on the outdoor unit control board.
7. Test run
Perform a test run following the steps in the installation manual
of the outdoor unit.
5. Paste the labels enveloped in the instruction document of indoor unit near the
electric wiring diagrams of both indoor and outdoor units.
Three types of labels (labels A-C) are provided: Paste the label B.
(Separate indoor unit/outdoor unit power supplies... Label B)
ON
OFF 1 2 3
<SW8>
Outdoor unit DIP switch settings
(when using separate indoor unit /
outdoor unit power supplies only)
Change of connectors
(except PCA-M·KA type)
(PCA-M·KA type)
Indoor unit
control board
Connectors (connections of initial setting are
for indoor unit power supplied from outdoor unit)
Connectors
Indoor unit power supplied from outdoor unit
(initial setting)
BLACK
CN01
L
BLUE
YELOW
YELOW
BLUE
CN01
Option
S1
S2
S3
N
L
S1
S2
S3
N
Indoor unit
control board
Separate indoor unit / outdoor unit power supplies
BLACK
CN01
BLUE
YELOW
BLUE
YELOW
CN01
Option
If the indoor and
outdoor units have
separate power
supplies, change
the connections of
the connectors as
shown in the
following figure.
Indoor unit
control board
Connectors
Indoor unit power supplied from outdoor unit
(initial setting)
ORANGE
CND
L
BLUE
YELOW
YELOW
BLUE
CND
S1
S2
S3
N
L
S1
S2
S3
N
Indoor unit
control board
Separate indoor unit / outdoor unit power supplies
ORANGE
CND
BLUE
YELOW
BLUE
YELOW
CND
Connectors (connections of initial setting are
for indoor unit power supplied from outdoor unit)
Option If the indoor and
outdoor units have
separate power
supplies, change
the connections of
the connectors as
shown in the
following figure.
Power Supply Terminal Kit for new A-Control Indoor units PAC-SG96/97HR-E
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5

Mitsubishi Electric PAC-SG96HR-E User manual

Category
Split-system air conditioners
Type
User manual

Mitsubishi Electric PAC-SG96HR-E is a power supply terminal kit designed for A-Control indoor units, enabling separate power supplies for the indoor and outdoor units in PUHZ applications. It features a terminal block with a capacity of 30A/330V, made from denatured melamine, and comes with lead wires already connected. The kit includes a screw for attaching the terminal block, a fastener for binding lead wires, and a label to indicate the separate power supply configuration.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI