Turbo

Eye Lighting Turbo User manual

  • Hello! I've reviewed the Installation Instructions for the EYE Lighting Australia TURBO Remote Driver Box and LED Fixture. This document provides details on the electrical wiring, including 3-Phase high voltage input and DC output connections. I'm ready to assist you with any questions regarding the installation process, specifications, or safety guidelines mentioned in the document.
  • What is the required torque for the M6 screws on the remote driver box?
    What is the maximum weight of the remote driver box?
    What type of cable is used for the AC input to the remote driver box?
    What is the distance between Remote Driver Box and TURBO LED Fixture using 3 x 1.5 mm2 flex cable
    What is the distance between Remote Driver Box and TURBO LED Fixture using 3 x 2.5 mm2 flex cable
For the latest product information visit the EYE Lighting Australia website
EYE Lighting Australia Pty Ltd
15 Industrial Avenue
Wacol QLD 4076
www.eyelighting.com.au
Tel: +61 (0) 7 3335 3555
Fax: +61 (0) 7 3335 3533
TURBO 3PHASE 22.07.22
Standard
Electrical Wiring of the Remote Driver Box
1
TURBO Remote Driver Box (3-Phase)
Installation Instructions
CLASSIIP66
Remote driver box weight: 7.5 Kg Max.
Other Possible 3-Phase AC Input Wiring Congurations:
Standard 3-Phase AC Input Wiring Conguration:
NOTE: The wiring congurations depend on site existing 3-Phase wiring
- Isolate & insulate the L1 (Phase1-Red) & Neutral (N-Black) separately
LED
Open remote driver box: 6× M6 screws (5 Nm torque).
AC Input: ex round cable 5 × 1.5 mm2 or 5 × 2.5 mm2
(Ø10-14mm).
Connect L1 , , L3 terminals (isolate & insulate L2 & Neutral
separately) 277 - 480 Vac 50/60 Hz (for 3-Phase 415 V AC input
& high voltage input LED driver).
DC Input: ex round cable 3× 1.5 mm2 or 3× 2.5 mm2 (Ø9-12mm).
Connect V+, ,V- terminals.
Note: This Vdc output is not xed (90/103/105/112/135) for dierent
wattage variants.
Tighten the cable glands and tighten the cover of the remote driver box:
6 × M6 screws (5 Nm).
IP 66 Remote Gearbox
3Nm
WAGO
WAGO
SPD
LED Driver
LED Driver
SPD
L1 L3
Standard
Standard DC Output Wiring Conguration:
Option
Option
- Isolate & insulate the L3 (Phase3-Blue) & Neutral (N-Black) separately
- Isolate & insulate the L2 (Phase2-White) & Neutral (N-Black) separately
L1 = Live (Phase1) = Red
= GND = Green / Yellow
L3 = Live (Phase3) = Blue
L2 = Live (Phase2) = White
= GND = Green / Yellow
L3 = Live (Phase3) = Blue
V- = Negative DC Output = Black
= GND = Green / Yellow
V+ = Positive DC Output = Red
L1 = Live (Phase1) = Red
= GND = Green / Yellow
L2 = Live (Phase2) = White
3-Phase AC Input: Ø10 - 14mm 1.5 ~ 2.5mm2
5-Core or 4-Core Power Cable
DC Output: Ø9 - 12mm 1.5mm2
3-Core Power Cable
Dimming Wire / OTP Control
Cable Inlet
3-Phase High Voltage Input Connection (refer to exact label for correct termination)
Scan for
PDF Version
From
3-Phase
Power
Source
To the
Junction
Box at
rear of
Turbo
LED
Fixture
IP 66 Remote Gearbox
3Nm
WAGO
WAGO
SPD
LED Driver
LED Driver
SPD
L1 L3
LED DRIVER
3 in 1
Dimming
or DALI
Dimming
Connections
+5 Nm
Important-Safety
This luminaire and remote driver box must be installed by a licensed electrician, following these installation instructions. Before carrying out any installation
or maintenance on this luminaire, ensure that the mains supply is fully isolated. High voltages greater than mains voltage can be present during operation.
Any inadequate installation might cause falling, electric shock, re, or other hazards. Ensure only qualied personnel inspect and maintains the luminaire.
Excessive build-up of foreign material from outer surfaces should be cleaned to maintain the performance of the luminaire. Do not modify the luminaire,
disassemble or replace any component without conrming with supplier rst. Do not touch the power supply when the luminaire is operating.
For the latest product information visit the EYE Lighting Australia website
EYE Lighting Australia Pty Ltd
15 Industrial Avenue
Wacol QLD 4076
www.eyelighting.com.au
Tel: +61 (0) 7 3335 3555
Fax: +61 (0) 7 3335 3533
TURBO 3PHASE 22.07.22
TURBO LED
FIXTURE
Junction Box on the LED Fixture (located at rear)
DC Input from the remote driver box: ex round cable
3 × 1.5 mm2 or 3 × 2.5 mm2 (Ø9 -12mm).
Open the rear junction box: 4 × M4 screws (3 Nm torque).
Connect V+ , V- , terminals.
Tighten the cable gland tightly and tighten the cover of the rear
junction box: 4 × M4 screws (3 Nm).
TURBO LED Fixture and Remote Driver Box Electrical Wiring
2
REMOTE
DRIVER BOX
WARNING:
INPUT DC VOLTAGE SUPPLY
ONLY FROM LED DRIVER
Remote driver box weight: 7.5 Kg Max.
TURBO Remote Driver Box (3-Phase)
Installation Instructions
IP 66 Remote Gearbox
3Nm
WAGO
WAGO
SPD
LED Driver
LED Driver
SPD
L1 L3
V- (Black)
V+ (Red)
GND (Green / Yellow)
IP 66 Remote Gearbox
3Nm
WAGO
WAGO
SPD
LED Driver
LED Driver
SPD
L1 L3
CLASSIIP66LED
+3 Nm
IP 66 Remote Gearbox
3Nm
WAGO
WAGO
SPD
LED Driver
LED Driver
SPD
L1 L3
3-Phase AC Power Cable
(5-Core or 4-Core)
Distance between Remote Driver
Box and TURBO LED Fixture:
30 m g 3 × 1.5 mm2 ex cable
60 m g 3 × 2.5 mm2 ex cable
User access DC input cable
DC input: Ø9 - 12mm cable
Factory Wired
DC Power Cable
/