Mitsubishi Electric MUZ-HM15NA2 Owner's manual

Category
Split-system air conditioners
Type
Owner's manual

This manual is also suitable for

Models
MUZ-HM09NA
-
U1
,
U8
MUZ-HM18NA
-
U1
MUZ-HM09NA2
-
U1
,
U8
MUZ-HM18NA2
-
U1
MUZ-HM12NA
-
U1
,
U8
MUZ-HM24NA
-
U1
MUZ-HM12NA2
-
U1
,
U8
MUZ-HM24NA2
-
U1
MUZ-HM15NA
-
U1
MUZ-HM15NA2
-
U1
HFC
utilized
R410A
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
MUZ-HM24NA
PARTS CATALOG (OBB747)
SERVICE MANUAL
No. OBH747
REVISED EDITION-D
Indoor unit service manual
MSZ-HM•NA Series (OBH746)
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. OUTLINES AND DIMENSIONS ······················ 10
5. WIRING DIAGRAM ·········································· 12
6. REFRIGERANT SYSTEM DIAGRAM ············· 15
7. DATA ································································ 19
8. ACTUATOR CONTROL ··································· 32
9. SERVICE FUNCTIONS ··································· 33
10. TROUBLESHOOTING ····································· 34
11. DISASSEMBLY INSTRUCTIONS ···················· 59
OBH747 REVISED EDITION-C is void.
Revision D:
• Capacity corrections have been corrected [7-1. 2), 3)].
OUTDOOR UNIT
2
Use the speci ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.
Revision A:
• MUZ-HM09/12NA-
U8
, MUZ-HM09/12NA2-
U8
, MUZ-HM15/18NA-
U1
, MUZ-HM15/18NA2-
U1
and MUZ-HM24NA2-
U1
have
been added.
Revision B:
• 3. SPECIFICATION has been modified.
Revision C:
• MUZ-HM09/12NA
-
U1
, MUZ-HM09/12NA2
-
U1
have been added.
Revision D:
• Capacity corrections have been corrected [7-1. 2), 3)].
OBH747D
3
1
TECHNICAL CHANGES
MUZ-HM24NA
-
U1
1. New model
MUZ-HM09NA
-
U8
MUZ-HM09NA2
-
U8
MUZ-HM12NA
-
U8
MUZ-HM12NA2
-
U8
MUZ-HM15NA
-
U1
MUZ-HM15NA2
-
U1
MUZ-HM18NA
-
U1
MUZ-HM18NA2
-
U1
MUZ-HM24NA2
-
U1
1. New model
MUZ-HM09NA
-
U1
MUZ-HM09NA2
-
U1
MUZ-HM12NA
-
U1
MUZ-HM12NA2
-
U1
1. New model
OBH747D
4
MUZ-HM24NA MUZ-HM24NA2
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
PART NAMES AND FUNCTIONS
2
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
OBH747D
5
3
SPECIFICATION
Outdoor unit model
MUZ-HM09NA
-
U1
MUZ-HM09NA2
-
U1
MUZ-HM09NA
-
U8
MUZ-HM09NA2
-
U8
Capacity
Rated (Minimum~Maximum)
Cooling 1
Btu/h 9,000 ( 3,800 ~ 10,000 )
Heating 47 1
Btu/h 10,900 ( 4,500 ~ 11,800 )
Capacity
Rated (Maximum)
Heating 17 2
Btu/h 6,700 (7,200)
Power consumption
Rated (Minimum~Maximum)
Cooling 1
W 750 (240 - 850) 750 (205 - 850)
Heating 47 1
W 900 (240 - 1,000) 900 (255 - 1,000)
Power consumption
Rated (Maximum)
Heating 17 2
W 700 (780)
EER
1
[SEER]
3
Cooling 12.0 [ 18.0 ]
HSPF IV
4
Heating 10.0 [NA] / 8.5 [NA2]
COP Heating
1
3.55
Power factor
Cooling (208/230) % 87/87 84/84
Heating (208/230) % 90/90 90/89
Power supply V , phase , Hz 208/230 , 1 , 60
Max. fuse size (time delay) A 15
Min. circuit ampacity A 9 12
Fan motor F.L.A A 0.50
Compressor
Model KNB073FRVMC KNB073FQDHC
R.L.A A 6.2 6.6
L.R.A A 7.7 8.2
Refrigeration oil
oz. (L) (Model)
9.1 (0.27) (FV50S) 10.8 (0.32) (NEO22)
Refrigerant control Linear expansion valve
Sound level
1
Cooling dB(A) 46
Heating
dB(A) 50
Air ow
High - Med. - Low
Cooling CFM 1,063
Heating
CFM 1,282 - 1,105 1,240 - 1,105
Fan speed
High - Med. - Low
Cooling rpm 740
Heating rpm 890 - 770 860 - 770
Defrost method Reverse cycle
Dimensions
W in. 31-1/2
D in. 11-1/4
H in. 21-5/8
Weight Ib. 73
External nish Munsell 3Y 7.8/1.1
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in. 1/4 (0.0315)
Gas in. 3/8 (0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor &
outdoor units
Height difference ft. 40
Piping length ft. 65
Refrigerant charge (R410A)
1 lb. 12 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB)
(Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB
2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
3: Test condition (Refer to page 9.)
4: Test condition (Refer to page 9.)
OBH747D
6
Outdoor unit model
MUZ-HM12NA
-
U1
MUZ-HM12NA2
-
U1
MUZ-HM12NA
-
U8
MUZ-HM12NA2
-
U8
Capacity
Rated (Minimum~Maximum)
Cooling 1
Btu/h 12,000 ( 3,800 ~ 12,200 )
Heating 47 1
Btu/h 12,200 ( 4,500 ~ 14,500 ) 12,200 ( 5,500 ~ 14,500 )
Capacity
Rated (Maximum)
Heating 17 2
Btu/h 7,600 (9,000)
Power consumption
Rated (Minimum~Maximum)
Cooling 1
W 1,210 (240 - 1,300) 1,210 (205 - 1,300)
Heating 47 1
W 990 (240 - 1,220) 990 (340 - 1,660)
Power consumption
Rated (Maximum)
Heating 17 2
W 800 (990)
EER
1
[SEER]
3
Cooling 9.9 [ 18.0 ]
HSPF IV
4
Heating 10.0 [NA] / 8.5 [NA2]
COP Heating
1
3.61
Power factor
Cooling (208/230) % 95/95 94/94
Heating (208/230) % 93/93 95/96
Power supply V , phase , Hz 208/230 , 1 , 60
Max. fuse size (time delay) A 15
Min. circuit ampacity A 9 12
Fan motor F.L.A A 0.50
Compressor
Model
KNB073FRVMC KNB092FQAHC
R.L.A A 6.2 6.6
L.R.A A 7.7 8.2
Refrigeration oil
oz. (L) (Model)
9.1 (0.27) (FV50S) 10.8 (0.32) (NEO22)
Refrigerant control Linear expansion valve
Sound level
1
Cooling dB(A) 49
Heating
dB(A) 51
Air ow
High - Med. - Low
Cooling CFM 1,063 1,102 - 639
Heating
CFM 1,282 - 1,105 1,186 - 1,116 - 1,045
Fan speed
High - Med. - Low
Cooling rpm 740 810 - 490
Heating rpm 890 - 770 870 - 820 - 770
Defrost method Reverse cycle
Dimensions
W in. 31-1/2
D in. 11-1/4
H in. 21-5/8
Weight Ib. 73
External nish Munsell 3Y 7.8/1.1
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in. 1/4 (0.0315)
Gas in. 3/8 (0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor &
outdoor units
Height difference ft. 40
Piping length ft. 65
Refrigerant charge (R410A)
1 lb. 12 oz. 2 lb. 9 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB)
(Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB
2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
3: Test condition (Refer to page 9.)
4: Test condition (Refer to page 9.)
OBH747D
7
Outdoor unit model
MUZ-HM15NA
MUZ-HM15NA2
MUZ-HM18NA
MUZ-HM18NA2
Capacity
Rated (Minimum~Maximum)
Cooling 1
Btu/h 14,000 (3,100 - 16,000) 17,200 (5,800 - 18,000)
Heating 47 1
Btu/h 18,000 (4,800 - 18,500) 18,000 (5,400 - 20,900)
Capacity
Rated (Maximum)
Heating 17 2
Btu/h 11,500 (14,000) 11,500 (15,000)
Power consumption
Rated (Minimum~Maximum)
Cooling 1
W 1,127 (187 - 1,957) 1,598 (308 - 2,028)
Heating 47 1
W 1,570 (190 - 1,980) 1,548 (288 - 2,208)
Power consumption
Rated (Maximum)
Heating 17 2
W 1,290 (1,820) 1,258 (1,908)
EER
1
[SEER]
3
Cooling 12.0 [18.0] 10.5 [18.0]
HSPF IV
4
Heating 10.0 [NA] / 8.5 [NA2] 10.0 [NA] / 8.5 [NA2]
COP Heating
1
3.30 3.32
Power factor
Cooling (208/230) % 98/98 98/98
Heating (208/230) % 98/98 97/97
Power supply V , phase , Hz 208/230, 1 , 60 208/230, 1 , 60
Max. fuse size (time delay) A 15 15
Min. circuit ampacity A 10 10
Fan motor F.L.A A 0.50 0.50
Compressor
Model SNB130FQBMT SNB130FQBMT
R.L.A A 7.4 7.4
L.R.A A 9.3 9.3
Refrigeration oil
oz. (L) (Model)
11.8 (0.35) (FV50S) 11.8 (0.35) (FV50S)
Refrigerant control Linear expansion valve
Sound level
1
Cooling dB(A) 49 49
Heating
dB(A) 51 51
Air ow
High - Med. - Low
Cooling CFM 1,102 - 639 1,102 - 639
Heating
CFM 1,186 - 1,045 - 1,045 1,186 - 1,045 - 1,045
Fan speed
High - Med. - Low
Cooling rpm 810 - 490 810 - 490
Heating rpm 870 - 770 - 770 870 - 770 - 770
Defrost method Reverse cycle
Dimensions
W in. 31-1/2 31-1/2
D in. 11-1/4 11-1/4
H in. 21-5/8 21-5/8
Weight Ib. 81 81
External nish Munsell 3Y 7.8/1.1
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in. 1/4 (0.0315) 1/4 (0.0315)
Gas in. 1/2 (0.0315) 1/2 (0.0315)
Connection method
Indoor Flared Flared
Outdoor Flared Flared
Between the indoor &
outdoor units
Height difference ft. 40 40
Piping length ft. 65 65
Refrigerant charge (R410A) 2 lb. 9 oz. 2 lb. 10 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB)
(Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB
2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
3: Test condition (Refer to page 9.)
4: Test condition (Refer to page 9.)
OBH747D
8
Outdoor unit model
MUZ-HM24NA
MUZ-HM24NA2
Capacity
Rated (Minimum~Maximum)
Cooling 1 Btu/h 22,500 (5,800 ~ 22,500)
Heating 47
1 Btu/h 26,000 (5,400 ~ 26,000)
Capacity
Rated (Maximum)
Heating 17 2 Btu/h 18,500 (18,500)
Power consumption
Rated (Minimum~Maximum)
Cooling 1 W 2,575 (275 ~ 2,575)
Heating 47
1 W 2,445 (265 ~ 2,445)
Power consumption
Rated (Maximum)
Heating 17 2 W 2,245 (2,245)
EER
1 [SEER] 3 Cooling 8.6 [18.0]
HSPF IV
4 Heating 9.5 [NA] / 8.5 [NA2]
COP Heating
1 3.05
Power factor
Cooling (208/230) % 99/99
Heating (208/230) % 99/99
Power supply V , phase , Hz 208/230, 1 , 60
Max. fuse size (time delay) A 15
Min. circuit ampacity A 14
Fan motor F.L.A 0.93
Compressor
Model SNB130FQBMT
R.L.A 10
L.R.A 12.5
Refrigeration oil
oz. (L) (Model)
11.8 (0.35) (FV50S)
Refrigerant control Linear expansion valve
Sound level
1
Cooling dB(A) 54
Heating dB(A) 55
Air ow
High - Med. - Low
COOL CFM 1,742 - 922
HEAT CFM 1,691 - 1,691 - 1,372
Fan speed
High - Med. - Low
Cooling rpm 840 - 450
Heating rpm 810 - 810 - 650
Defrost method Reverse cycle
Dimensions
W in. 33-1/16
D in. 13
H in. 34-5/8
Weight Ib. 121
External nish Munsell 3Y 7.8/1.1
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in. 3/8 (0.0315)
Gas in. 5/8 (0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor &
outdoor units
Height difference ft. 50
Piping length ft. 100
Refrigerant charge (R410A) 3 lb. 9 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB)
(Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB
2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
OBH747D
9
Test condition
ARI
Mode Test
Indoor air condition (°F) Outdoor air condition (°F)
Dry bulb Wet bulb Dry bulb Wet bulb
SEER
(Cooling)
"A-2" Cooling Steady State
at rated compressor Speed
80 67 95 (75)
"B-2" Cooling Steady State
at rated compressor Speed
80 67 82 (65)
"B-1" Cooling Steady State
at minimum compressor Speed
80 67 82 (65)
"F-1" Cooling Steady State
at minimum compressor Speed
80 67 67 (53.5)
"E-V" Cooling Steady State
at Intermediate compressor Speed
5
80 67 87 (69)
HSPF
(Heating)
"H1-2" Heating Steady State
at rated compressor Speed
70 60 47 43
"H3-2" Heating
at rated compressor Speed
70 60 17 15
"H0-1" Heating Steady State
at minimum compressor Speed
70 60 62 56.5
"H1-1" Heating Steady State
at minimum compressor Speed
70 60 47 43
"H2-V" Heating
at Intermediate compressor Speed
5
70 60 35 33
5
: At Intermediate compressor Speed
= ("Rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".
3, 4
(2) OPERATION
Mode Condition
Intake air temperature (°F)
Indoor Outdoor
DB WB DB WB
Cooling
Standard temperature 80 67 95
Maximum temperature 90 73 115
Minimum temperature 67 57 14
Maximum humidity 78 %
Heating
Standard temperature 70 60 47 43
Maximum temperature 80 67 75 65
Minimum temperature 70 60 -4 (NA), 5(NA2) -5 (NA), 4 (NA2)
OPERATING RANGE
(1) POWER SUPPLY
Rated voltage Guaranteed voltage (V)
Outdoor unit
208/230 V
1 phase
60 Hz
Min. 187
208 230 Max. 253
OBH747D
10
OUTLINES AND DIMENSIONS
4
Unit: inch
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
4 in. (100 mm)
or more
14 in. (350 mm)
or more
8 in. (200 mm)
or more *2
4 in. (100 mm)
or more
Liquid refrigerant pipe joint
Refrigerant pipe (flared)
Ø 1/4
Gas refrigerant pipe joint
Refrigerant pipe (flared)
Ø 3/8 (HM09/12)
Ø 1/2 (HM15/18)
REQUIRED SPACE
clear *1
*1
4 in. (100 mm) or more when
front and sides of the unit are clear
*2
When any 2 sides of left, right
and rear of the unit are clear
holes
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
OBH747D
11
MUZ-HM24NA MUZ-HM24NA2
Unit: inch
16-7/16
1-9/16
1-5/8
Drain hole
6-7/8
19-11/16
13
2
Air in
Air in
Air out
2-holes 13/32 13/16
14-3/16
33-1/16
4-5/16
3-3/16
34-5/8
17-25/32
Service panel
3-29/32
6-1/2
7-11/16
35
44
Liquid refrigerant pipe joint
Refrigerant pipe (flared)
Ø 3/8
Gas refrigerant pipe joint
Refrigerant pipe (flared)
Ø 5/8
*1 20 in. (500 mm) or more when front
and sides of the unit are clear
14 in. (350 mm)
or more
4 in. (100 mm)
or more
REQUIRED SPACE
Clear *1
4 in. (100 mm)
or more
20 in. (500 mm)
or more *2
*2 When any 2 sides of left, right
and rear of the unit are clear
OBH747D
12
5
WIRING DIAGRAM
MUZ-HM09NA
-
U8
MUZ-HM09NA2
-
U8
MUZ-HM12NA
-
U8
MUZ-HM12NA2
-
U8
MUZ-HM09NA
-
U1
MUZ-HM09NA2
-
U1
MUZ-HM12NA
-
U1
MUZ-HM12NA2
-
U1
OBH747D
13
MUZ-HM15NA
-
U1
MUZ-HM15NA2
-
U1
MUZ-HM18NA
-
U1
MUZ-HM18NA2
-
U1
OBH747D
14
MUZ-HM24NA
-
U1
MUZ-HM24NA2
-
U1
OBH747D
15
6
REFRIGERANT SYSTEM DIAGRAM
MUZ-HM09NA
-
U8
MUZ-HM09NA2
-
U8
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
(with strainer)
Stop valve
(with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø3/8 (ø9.52)
(with heat insulator)
Refrigerant pipe ø1/4 (ø6.35)
(with heat insulator)
R.V. coil
heating ON
cooling OFF
Strainer
#100
LEV
Ambient
temperature
thermistor
RT65
Muffler
Capillary tube
O.D. 0.118 × I.D. 0.079
× 9-7/16
(ø3.0 × ø2.0
×
240)
Outdoor heat
exchanger
temperature
thermistor
RT68
Service port
Service port
Muffler
Unit: Inch (mm)
Flared connection
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
(with strainer)
Stop valve
(with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø3/8 (ø9.52)
(with heat insulator)
Refrigerant pipe ø1/4 (ø6.35)
(with heat insulator)
R.V. coil
heating ON
cooling OFF
Strainer
#100
LEV
Muffler
Capillary tube
O.D. 0.118 × I.D. 0.055
× 10-1/4
(ø3.0 × ø1.4
×
260)
Muffler
Service port
Service port
Outdoor
heat
exchanger
Defrost
thermistor
RT61
Ambient
temperature
thermistor
RT65
Outdoor heat
exchanger
temperature
thermistor
RT68
MUZ-HM09NA
-
U1
MUZ-HM09NA2
-
U1
MUZ-HM12NA
-
U1
MUZ-HM12NA2
-
U1
OBH747D
16
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
(with strainer)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø1/4 (ø6.35)
(with heat insulator)
R.V. coil
heating ON
cooling OFF
Strainer
#100
LEV
Ambient
temperature
thermistor
RT65
Muffler
Capillary tube
O.D. 0.157 ×
I.D. 0.094 × 9-7/16
(
ø4.0 × ø2.4 × 240
)
Outdoor heat
exchanger
temperature
thermistor
RT68
Capillary tube
O.D. 0.118 ×
I.D. 0.079 × 8-9/32
(ø3.0 × ø2.0 × 210)
Service
port
Service
port
Refrigerant pipe ø1/2 (ø12.7)
(with heat insulator)
Stop valve
(with service port)
Muffler
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
MUZ-HM12NA
-
U8
MUZ-HM12NA2
-
U8
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
(with strainer)
Stop valve
(with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø3/8 (ø9.52)
(with heat insulator)
Refrigerant pipe ø1/4 (ø6.35)
(with heat insulator)
R.V. coil
heating ON
cooling OFF
Strainer
#100
Capillary tube
O.D. 0.118 × I.D. 0.071
× 23-5/8
3.0
× ø
1.8
×
600
)
(×2)
LEV
Ambient
temperature
thermistor
RT65
Muffler
Capillary tube
O.D. 0.118 × I.D. 0.079
× 9-7/16
(ø3.0 × ø2.0
×
240)
Outdoor heat
exchanger
temperature
thermistor
RT68
Muffler
Service port
Service port
Unit: Inch (mm)
OBH747D
17
Unit: Inch (mm)
MUZ-HM24NA MUZ-HM24NA2
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
Capillary tube
O.D. 0.157×
I.D. 0.094×
3-15/16
4.0
×
ø
2.4
×
100)
Capillary tube
O.D. 0.157×
I.D. 0.094×7-7/8
4.0
×
ø
2.4
×
200)
Refrigerant flow in cooling
Compressor
4-way
valve
Refrigerant flow in heating
Refrigerant pipe
ø5/8
(
ø
15.88)
(with heat insulator)
Refrigerant pipe
ø3/8
(
ø
9.52)
(with heat insulator)
LEV
R.V. coil
heating ON
cooling OFF
Muffler
with #100 mesh strainer
Strainer
#100
Outdoor heat
exchanger
temperature
thermistor
RT68
Strainer
#100
Muffler
Capillary tube
O.D. 0.118×
I.D. 0.079× 7-7/8
(ø3.0×ø2.0×200(×4))
Stop valve
(with service port)
Service
port
Service port
OBH747D
18
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft. Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas Liquid
MUZ-HM09NA
MUZ-HM09NA2
MUZ-HM12NA
MUZ-HM12NA2
65 40
3/8
1/4
MUZ-HM15NA
MUZ-HM15NA2
MUZ-HM18NA
MUZ-HM18NA2
1/2
MUZ-HM24NA
MUZ-HM24NA2
100 50 5/8 3/8
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 65
MUZ-HM09NA
MUZ-HM09NA2
MUZ-HM12NA
-
U1
MUZ-HM12NA2
-
U1
1 lb. 12 oz.
0 1.08 3.24 5.40 7.56 8.64
MUZ-HM12NA
-
U8
MUZ-HM12NA2
-
U8
MUZ-HM15NA
MUZ-HM15NA2
2 lb. 9 oz.
MUZ-HM18NA
MUZ-HM18NA2
2 lb. 10 oz.
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 70 80 90 100
MUZ-HM24NA
MUZ-HM24NA2
3 lb. 9 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
OBH747D
19
DATA7
7-1. PERFORMANCE DATA
1) COOLING CAPACITY
Model
Indoor air Outdoor intake air DB temperature (˚F)
IWB (˚F)
75 85 95 105 115
TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
MUZ-HM09NA
MUZ-HM09NA2
71 11.0 7.6 0.67 10.3 7.1 0.73 9.7 6.6 0.79 9.0 6.2 0.83 8.3 5.7 0.86
67 10.4 8.6 0.63 9.7 8.0 0.69 9.0 7.4 0.75 8.4 6.9 0.80 7.7 6.3 0.83
63 9.8 9.4 0.60 9.1 8.7 0.66 8.5 8.1 0.72 7.7 7.3 0.77 7.0 6.7 0.80
MUZ-HM12NA
MUZ-HM12NA2
71 14.7 9.4 1.08 13.7 8.7 1.18 12.9 8.2 1.27 12.0 7.6 1.34 11.0 7.0 1.39
67 13.9 10.7 1.02 13.0 10.0 1.12 12.0 9.2 1.21 11.2 8.6 1.28 10.3 7.9 1.34
63 13.1 11.8 0.97 12.1 10.9 1.07 11.3 10.2 1.16 10.3 9.3 1.23 9.4 8.5 1.28
MUZ-HM15NA
MUZ-HM15NA2
71 17.2 11.1 1.04 16.0 10.4 1.14 15.1 9.7 1.23 14.0 9.1 1.29 12.9 8.3 1.35
67 16.2 12.7 0.98 15.1 11.8 1.08 14.0 10.9 1.17 13.0 10.2 1.24 12.0 9.3 1.30
63 15.3 13.9 0.94 14.1 12.9 1.04 13.2 12.0 1.12 12.0 10.9 1.19 10.9 10.0 1.24
MUZ-HM18NA
MUZ-HM18NA2
71 21.1 15.3 1.46 19.7 14.3 1.60 18.5 13.4 1.72 17.2 12.5 1.81 15.8 11.5 1.89
67 20.0 17.2 1.38 18.6 16.0 1.52 17.2 14.8 1.64 16.0 13.8 1.74 14.7 12.6 1.82
63 18.7 18.6 1.31 17.4 17.3 1.45 16.2 16.1 1.57 14.7 14.6 1.67 13.4 13.3 1.74
MUZ-HM24NA
MUZ-HM24NA2
71 27.6 20.9 2.34 25.8 19.5 2.56 24.2 18.3 2.76 22.5 17.0 2.91 20.7 15.7 3.02
67 26.1 23.2 2.21 24.3 21.6 2.43 22.5 20.0 2.63 20.9 18.6 2.79 19.2 17.1 2.92
63 24.5 25.1 2.10 22.7 23.3 2.33 21.2 21.6 2.51 19.2 19.7 2.68 17.6 18.0 2.79
NOTE: 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x10
3
Btu/h)
SHC : Sensible Heat Capacity (x10
3
Btu/h) TPC : Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor Intake air DB temperature.
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
MUZ-HM24NA MUZ-HM24NA2
2) COOLING CAPACITY CORRECTIONS
Refrigerant piping length (one way: ft.)
Model 25 (std.) 40 65 100
MUZ-HM09NA
MUZ-HM09NA2
MUZ-HM12NA
MUZ-HM12NA2
MUZ-HM15NA
MUZ-HM15NA2
1.0 0.988 0.967
MUZ-HM18NA
MUZ-HM18NA2
1.0 0.985 0.963 0.933
MUZ-HM24NA
MUZ-HM24NA2
1.0 0.983 0.956 0.921
OBH747D
20
4) HEATING CAPACITY
Model
Indoor air Outdoor intake air WB temperature (˚F)
IDB (˚F)
5 152535434555
TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
MUZ-HM09NA
MUZ-HM09NA2
75 4.8 0.53 6.3 0.67 7.9 0.79 9.4 0.88 10.6 0.92 11.0 0.94 12.4 0.97
70 5.2 0.51 6.7 0.65 8.2 0.77 9.6 0.86 10.9 0.90 11.2 0.92 12.7 0.95
65 5.5 0.49 6.9 0.62 8.6 0.74 10.0 0.83 11.2 0.88 11.6 0.89 13.0 0.94
MUZ-HM12NA
MUZ-HM12NA2
75 5.4 0.58 7.1 0.74 8.8 0.87 10.6 0.97 11.9 1.01 12.3 1.03 13.9 1.07
70 5.8 0.56 7.5 0.71 9.2 0.85 10.8 0.94 12.2 0.99 12.6 1.01 14.2 1.05
65 6.1 0.53 7.7 0.68 9.6 0.82 11.2 0.92 12.6 0.97 12.9 0.98 14.5 1.03
MUZ-HM15NA
MUZ-HM15NA2
75 7.9 0.94 10.4 1.19 13.1 1.40 15.6 1.56 17.6 1.64 18.1 1.66 20.5 1.73
70 8.6 0.90 11.1 1.15 13.5 1.37 15.9 1.52 18.0 1.60 18.5 1.63 21.0 1.70
65 9.0 0.86 11.3 1.10 14.1 1.32 16.5 1.48 18.5 1.56 19.1 1.58 21.4 1.66
MUZ-HM18NA
MUZ-HM18NA2
75 7.9 0.94 10.4 1.18 13.1 1.39 15.6 1.55 17.6 1.63 18.1 1.65 20.5 1.72
70 8.6 0.90 11.1 1.14 13.5 1.36 15.9 1.51 18.0 1.59 18.5 1.62 21.0 1.69
65 9.0 0.86 11.3 1.10 14.1 1.31 16.5 1.47 18.5 1.55 19.1 1.57 21.4 1.65
MUZ-HM24NA
MUZ-HM24NA2
75 11.4 1.48 15.1 1.86 18.9 2.19 22.5 2.44 25.4 2.56 26.1 2.60 29.6 2.70
70 12.4 1.41 16.0 1.80 19.5 2.14 23.0 2.38 26.0 2.50 26.8 2.55 30.3 2.65
65 13.0 1.35 16.4 1.73 20.4 2.06 23.8 2.31 26.8 2.44 27.6 2.48 30.9 2.60
NOTE: 1. IDB : Intake air dry-bulb temperature
TC : Total Capacity (x10
3
Btu/h) TPC : Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch or press any button on the remote con-
troller.
3) HEATING CAPACITY CORRECTIONS
Refrigerant piping length (one way: ft.)
Model 25 (std.) 40 65 100
MUZ-HM09NA
MUZ-HM09NA2
MUZ-HM12NA
MUZ-HM12NA2
MUZ-HM15NA
MUZ-HM15NA2
1.0 0.997 0.993
MUZ-HM18NA
MUZ-HM18NA2
MUZ-HM24NA
MUZ-HM24NA2
1.0 0.997 0.993 0.987
OBH747D
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66

Mitsubishi Electric MUZ-HM15NA2 Owner's manual

Category
Split-system air conditioners
Type
Owner's manual
This manual is also suitable for