Potter CPS-24N Conventional Photoelectric Smoke Detector Owner's manual

Category
Smoke detectors
Type
Owner's manual
CPS-24N
Conventional Photoelectric Smoke Detector
8830138 - REV A 08/17 PAGE 1 OF 2
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
Features
• 360° view of detector status LED
• Lowprole,2”high(withbase)
• 2or4wirebasecompatibility,relaybasesavailable
• Highlystableoperation,RF/Transientprotection
• Lowstandbycurrent,59μAat24VDC
• Onebuilt-inpower/sensitivitysupervision/alarmLED
• AutomaticSensitivitywindowvericationfunctionmeets
outlinedrequirementsinNFPA72,Chapter2&7,Inspection,
TestingandMaintenance.
• WithoutMagneticTestFeature
LightSource GaAIAsInfraredEmittingDiode
RatedVoltage 12or24VDC
WorkingVoltage 8-35.0VDC
MaximumVoltage 42VDC
SupervisoryCurrent 59μA@24VDC
SurgeCurrent 160μAmax.@24VDC
AlarmCurrent 150mAmax.@24VDC
AirVelocityRange 0-4000fpm
Ambient
Temperature 32°Fto120°F(0°Cto49°C)
SensitivityTest
Feature
AutomaticSensitivitywindowvericationtest
Mounting RefertoPotterSBSeriesSmokeDetectorBaseseries,bulletinno.
8840008.
Description
TheCPS-24Nisareliable,highqualityPhotoelectricSmoke
Detector.ItcanbeusedinallopenareaswherePhotoelectricSmoke
Detectorsarerequired,includingin-ductapplications.Thecomputer-
designedsmokechambermakestheCPS-24Nwellsuitedfor
detectingsmolderingresaswellasfast-amingres.
Operation
TheCPS-24Nphotoelectricsmokedetectorutilizesonebicolored
LEDforindicationofstatus.Inanormalstandbyconditionthe
LEDashGreenevery3seconds.Whenthedetectorsensesthatits
sensitivityhasdriftedoutsidetheULlistedsensitivitywindowthe
LEDwillashRedevery3seconds.Whenthedetectorsensessmoke
andgoesintoalarmthestatusLEDwilllatchonRed.
ThedetectorutilizesaninfraredLEDlightsourceandsilicon
photodiodereceivingelementinthesmokechamber.Inanormal
standbycondition,thereceivingelementreceivesnolightfrom
thepulsingLEDlightsource.Intheeventofare,smokeenters
thedetectorsmokechamberandlightisreectedfromthesmoke
particlestothereceivingelement.Thelightreceivedisconvertedinto
anelectronicsignal.
FireJudgementsignalsareprocessedandcomparedtoareference
level,andwhenveconsecutivesignalsexceedingthereferencelevel
arereceivedwithinaspeciedperiodoftime,thetimedelaycircuit
triggerstheSCRswitchtoactivatethealarmsignal.ThestatusLED
lightscontinuouslyduringthealarmperiod.
Technical Specications
firealarmresources.com
8830138 - REV A 08/17 PAGE 2 OF 2
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
CPS-24N
Conventional Photoelectric Smoke Detector
The contractor shall furnish and install where indicated on the plans,
Potter Electric Signal CPS-24N photoelectric smoke detectors. The
combination detector head and twist-lock base shall be UL listed
compatiblewithaULlistedrealarmpanel.
The base shall permit direct interchange with  Potter CPS-24VN
combinationphotoelectricsmokedetector.Thebaseshallbeappropriate
twist-lockbaseSBSeries.Intheeventofpartialorcompleteretrot,
the CPS-24N may be used in conjunction with, or as a replacement
for, Potter detectors (PS-24, PS-24H and the IS-24) on most SB base
applications.
The smoke detector shall have one ashing status LED for visual
supervision.Whenthedetectorisin standby condition the LEDwill
ash Green. When the detector is outside the UL listed sensitivity
window the LED will ash Red. When the detector is actuated, the
ashingLEDwilllatchonRed.Thedetectormayberesetbyactuating
thecontrolpanelresetswitch.
The sensitivity of the detector shall be capable of being measured.
The sensitivity of the detector shall be monitored automatically and
continuously to verify that it is operating within the listed sensitivity
range. To facilitate installation, the detector shall be non-polarized.
VoltageandRFtransientsuppressiontechniquesshallbeemployedto
minimizefalsealarmpotential.AuxiliarySPDTrelaysshallbeinstalled
whereindicated.
Specications
Ordering Information
CPS-24N Sensitivity Test Feature
The Potter CPS-24N Photoelectric Smoke Detector has a built-in
automaticsensitivitytestfeature.
1.Innormalcondition,thestatusLEDashesgreen.
2.Whenthesensitivitydriftsoutsideofitssensitivitylimits,thestatus
LEDashesred.
3.Inthealarmstate,thestatusLEDisredcontinuously.
4. When the sensitivity drifts outside of its sensitivity limits and the
statusLEDashesred,thedeviceneedstobecleanedorreturnedtothe
factoryforcleaningorcalibration.
Model Description Stock No.
CPS-24N
Conventional Photoelectric Smoke
Detector without magnetic test
feature
1430037