Hytronik HCD405-BT Microwave Motion Sensor User manual

Category
Motion detectors
Type
User manual
Installation and Instruction Manual
3. Installation
Mechanical Structure & Dimensions
HCD405/BT
Microwave Motion Sensor with 5.0 SIG Mesh
2. Download the App
Free App for set-up and commissioning
HCD405/BT-20230203-A0
1. Technical Specifications
DALI Output
Protocol
4 dBm
2.4 GHz - 2.483 GHz
Operation frequency
Transmission power
Range (Typical indoor)
10~30m
Stand-by power
Operating voltage
<
1W
220~240VAC 50/60Hz
Load ratings
20sWarming-up
30mA (max.15 devices)
EMC standard (EMC)
Safety standard (LVD)
Certification
EN55015, EN61000-3-2/-3-3, EN61547
CE ,RED, RCM, UKCA
EN61347-1/-2-11
RED EN300328, EN301489-1/-17,
EN300440,EN301489-3
30°~150°
Ta:-20
OC~+55OC
Sensor principle
Detection range (Max.)*
Detection angle
Operation temperature
IP20 IP rating
5.0 SIG
Mesh
Max installation height: 6m
Max detection range 10m (diameter)
High Frequency (microwave)
Tc:+75°Case temperature(MAX.)
5.0 SIG mesh
Web app/platform: www.iot.koolmesh.com
Koolmesh Pro app for iPad
Smartphone app for both iOS & Android platform
for iOS for Android
for iPad
for Web
Web
iOS
Android
4.2
36.5
65
71.7
80.5
26
12.1
23.8
24.9
50
43.8
36.5
26
23.8
65
4.2
Antenna module
Photocell AdvanceTM
Daylight sensor
Bluetooth module
NL
DA–
DA+
Installation hole
Antenna module
Photocell AdvanceTM
Daylight sensor
NLInstallation
hole
DA–
DA+
Bluetooth module
HCD405/BT-20230203-A0
Subject to change without notice.
5. Additional Information / Documents
4. Detection Pattern
Wiring Diagram
Wire Preparation
Ceiling mounted detection pattern (m)
Ceiling mounted height(m)
50
6
10%
30%
75%
50%
Wall mounted height (m)
Wall mounted detection pattern (m)
9
4
0
10%
30%
75%
50%
1. For full explanation of Hytronik Photocell AdvanceTM technology, please kindly refer to www.hytronik.com/download ->knowledge ->Introduction of Photocell Advance
2. To learn more about detailed product features/functions, please refer to www.hytronik.com/download ->knowledge ->Introduction of App Scenes and Product Functions
3. Regarding precautions for Bluetooth product installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->Bluetooth Products - Precautions for Product Installation and Operation
4. Regarding precautions for microwave sensor installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->Microwave Sensors - Precautions for Product Installation and Operation
5. Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetooth technology ->Bluetooth Sensors
6. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy
Control Gear
Control Gear
L N DA- DA+
Control Gear
N
L
DA –
DA +
N
L
N
L
DA –
DA +
N
L
DA –
DA +
To make or release the wire from the terminal,
use a screwdriver to push down the button.
1. 200 metres (total) max. for 1mm² CSA(Ta = 50)
2. 300 metres (total) max. for 1.5mm² CSA(Ta = 50)
0.75~1.5mm
8mm