Thank you for purchasing this Samsung Product.
Before operating this unit, please read this installation manual carefully and retain it for future
reference.
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 1 2020-01-15 오후 4:06:39
2
English
PREPARATION
Safety Information
This installation manual explains how to install COMM KIT that connects
control unit and outdoor unit. Please read this manual thoroughly before
installing the product. (Please refer to appropriate installation for any
optional product installation.)
WARNING
Hazards or unsafe practices that may result in severe personal injury or
death.
CAUTION
Hazards or unsafe practices that may result in minor personal injury or
property damage.
Follow directions. Do NOT attempt.
Make sure the machine is grounded to prevent electric shock.
Unplug the power plug from the wall socket.
Do NOT disassemble.
FOR INSTALLATION
WARNING
Consult qualified installer or service center for installation.
If not, there is risk of product malfunction, water leakage, electric
shock or fire.
Make sure to use the supplied cables.
If not, there is risk of fire or damage to the product.
PREPARATION
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 2 2020-01-15 오후 4:06:39
3
English
PREPARATION
Make sure that all wiring work is done by qualified person
complying regional standards and instructions in this manual.
If the installation is done by unqualified person, there is risk of
product malfunction, electric shock or fire caused by incorrect
installation.
Check if the installation was done properly according to the
installation manual.
There is risk of electric shock or fire if the product is installed
incorrectly.
CAUTION
Make sure there is no tension to the cable during installation.
Cable may get cut and cause fire.
When installing the product in hospitals or other places, make sure
that the product does not interrupt with other products.
Abnormal operation may occur.
Do not install the product in a place where flammable gas leaks or if
there is possible chance of leakage.
There is risk of fire or explosion.
Do not install the product in a place where it will be exposed to oil or
vapor etc.
If the product is used in a place where it is exposed to oil, vapor or
sulphur dioxide, parts of the product may get damaged or product
may function abnormally.
Do not install the product in a place where special spray or acid/
alkali solution is used.
There is risk of electric shock or abnormal operation.
PREPARATION
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 3 2020-01-15 오후 4:06:39
4
English
PREPARATION
For operation
WARNING
Do not attempt to repair, disassemble, or modify the product
yourself.
There is potential risk of product damage, electric shock or fire. When
repair is needed, consult qualified installer or service center.
Contact the service center when you need to dispose the product.
Do not attempt to move or re-install the product that is already
installed.
If not, there is risk of electric shock or fire.
CAUTION
Do not allow water to enter the product.
If not, there is risk of electric shock or fire.
Do not connect the power cable to the communication cable
terminal.
There is risk of fire.
Safety Information
Installation
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 4 2020-01-15 오후 4:06:39
5
English
Installation
Accessories
Item COMM KIT
DC power
cable (12 V)
Communication
cable
Flow switch
Screw (M4) Bracket
Only for MIM-E02EN
Quantity
1 1 2 1 1 1
Shape
CN4
CN3
RED
CN2
BLK
Diagram of connection between COMM KIT and outdoor unit
MIM-E02EN (5kW Outdoor Unit)
1. Fix the COMM KIT PBA at case.
2. Open the control cover of the outdoor unit
(5kW).
3. Mount the COMM KIT on the COMM KIT CASE
with 1 screw noting the assembly direction.
COMM KIT Installation
Installation
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 5 2020-01-15 오후 4:06:40
6
English
Installation
MIM-E02FN (8/16kW Outdoor Unit)
1. Open the right hand of the front cabinet of
outdoor unit (8/16kW).
A
A
VIEW A-A
2. Mount the COMM KIT on the case’s EMI fixing
hooks noting the assembly direction.
(Attach the COMM KIT and the terminal of
PCB DC power cable to be on the left side.)
COMM KIT Installation
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 6 2020-01-15 오후 4:06:40
7
English
Installation
Connecting COMM KIT to the outdoor unit
MIM-E02EN (5kW Outdoor Unit)
1. Connect the DC power cable connector (Blue) to CN303 of SUB PCB in the EHS outdoor unit by using a
DC power cable.
2. Disconnect the F1 and F2 wires from the terminal block in the outdoor unit. Then, connect the
disconnected cable to a communication cable with red connector, and connect it to the communication
connector of the COMM KIT.
3. Connect the F1-F2 terminal block to the communication block of the COMM KIT, by using the
communication cable with the ring terminal.
4. Connect the communication cable from the indoor unit to the F1 and F2 terminal blocks in the outdoor
unit.
1
2
3
4
F1
F2
Communication cable
with ring terminal
COMM KIT
DC Power cable
Communication terminal
block of outdoor unit (2P)
Control Unit
Communication cable with red
connector
<Indoor Unit>
Sub PCB
Flow Switch
Outdoor Unit
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 7 2020-01-15 오후 4:06:40
8
English
Installation
MIM-E02FN (8/16kW Outdoor Unit)
1. Connect the DC power cable connector (Blue) to CN12 of Main PCB in the EHS outdoor unit by using a DC
power cable.
2. Disconnect the F1 and F2 wires from the terminal block in the outdoor unit. Then, connect the disconnected
cable to a communication cable with red connector, and connect it to the communication connector of the
COMM KIT.
3. Connect the F1-F2 terminal block to the communication block of the COMM KIT, by using the communication
cable with the ring terminal.
4. Connect the communication cable from the indoor unit to the F1 and F2 terminal blocks in the outdoor unit.
1
2
3
4
CN4
CN3
RED
CN2
BLK
F1
F2
<Indoor Unit>
Communication cable
with ring terminal
Communication terminal
block of outdoor unit (2P)
Communication cable with
red connector
Main PCB
Control Unit
COMM KIT
DC Power cable
Outdoor Unit
Flow Switch
CAUTION
The control unit terminal block of COMM KIT (MIM-E02EN / MIM-E02FN) must be fixed with M3 sized
screws, and its toque must be 0.5 to 0.75 Nm.
The cable length between the control unit and the farthest COMM KIT must be within 1000 m.
Be sure to switch off the power supply before installation.
Wiring should be performed in accordance with the electric wiring regulations and must be placed in
the wall so that users cannot touch them.
COMM KIT Installation
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 8 2020-01-15 오후 4:06:40
9
English
Installation
Setting option switch
CN4
CN3
RED
CN2
BLK
SW4
SW 5
* ROTARY SWITCH
: No need of separate settings
ON
OFF
1 2
43
How to set option switches
Settings
Dip S/W(SW4) Dip S/W(SW5)
SW4 SW5
1 2 43
OFF
ON
1 2 3 4
ON - Device 31
Not using Flow
Switch
R-410A Model
OFF
Modbus
Communication
Device 30
Using Flow
Switch
R-32 Model
The initial settings for option switches are OFF in SW 4 and SW 5.
When operating two outdoor units with a single control unit, set No.2 of SW4 differently.
(UNIT 1 OFF → Device 30, UNIT 2 ON → Device 31)
OUTDOOR UNIT 1
OUTDOOR UNIT 2
Example)
COMM KIT DIP S/W
SW4 #2 : ON
COMM KIT DIP S/W
SW4 #2 : OFF
<Indoor Unit>
Control Unit
In order to change the setting of the option switch, reset the power of COMM KIT.
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 9 2020-01-15 오후 4:06:40
10
English
Installation
Checking Operation
LED Display
1. When you reset the power supply and find that the communication between the COMM KIT and outdoor
unit is valid, the Y-GRN LED blinks.
(Please wait until the communication between the COMM KIT and the outdoor unit becomes normal.)
CN4
CN3
RED
CN2
BLK
YEL
RED
Y-GRN
YEL
RED
Y-GRN
LED
2. When the communication between the COMM KIT and indoor unit is detected as valid, the RED LED
blinks.
NOTE
YEL LED is not in use.
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 10 2020-01-15 오후 4:06:41
11
English
Installation
7-SEGMENT display
1. When the power supply is initialized, the program codes appear.
Examples of the program code: 17 89 A3 16
2. Then the tracking of COMM KIT will proceed as the following:
Display in normal operation
If the value of the register number 40011 is 0 or there is no signal, "A" and "0" appear on the first and
second segments for 1 second.
Displays “3” and “0” or “1” for 1 second. (A030 device’s 30-Dip S/W #2 is OFF, A031 device’s 31-Dip
S/W #2 is ON.)
If the value of the register number 40011 is not 0, “A” is displayed on the first segment, and the
hundreds digit number of the register is displayed on the second segment for 1 second.
The tens digit number is displayed on the first segment, and the unit digit number is displayed on
the second segment for 1 second.
Example)
REGISTER NUMBER(#40011) DIP SWITCH(#2) SEGMENT
0 (or no entry) OFF
100 -
255 -
Display when an error occurs
"E” and “*” are displayed on the first and second segments for 1 second. → Displays "*” and ”*” for
1 second. (This action will repeat until the error is corrected)
Example)
ERROR CODE SEGMENT
E101
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 11 2020-01-15 오후 4:06:41
12
English
Installation
Error Codes
If the unit has some problems and does not work normally, error code is shown on the OUTDOOR UNIT
MAIN PCB.
Display Explanation Error Source
E101
Communication error between the indoor and outdoor units
(when indoor unit cannot receive signals)
COMM KIT
OUTDOOR UNIT
E108
Duplicate channel addresses - overlapping of unit channel
addresses on a system.
OUTDOOR UNIT
E109 Communication error due to indoor unit address incomplete.
COMM KIT
OUTDOOR UNIT
E111
Modbus communication error
(when COMM KIT cannot receive signals)
COMM KIT
OUTDOOR UNIT
E162 EEPROM H/W ERROR COMM KIT
E177 Emergency Error
COMM KIT
OUTDOOR UNIT
E201
COMM KIT/OUTDOOR UNIT communication error
(Matching error)
OUTDOOR UNIT
E202 COMM KIT/OUTDOOR UNIT communication error (3 min) OUTDOOR UNIT
E203 Communication error between INVERTER and MAIN MICOM (6 min) OUTDOOR UNIT
E221 OUTDOOR UNIT temperature sensor error OUTDOOR UNIT
E231 Condenser temperature sensor error OUTDOOR UNIT
E251 Discharge temperature sensor error OUTDOOR UNIT
E320 OLP sensor error OUTDOOR UNIT
E403
Detection of OUTDOOR UNIT compressor freezing
(During cooling operation)
OUTDOOR UNIT
E404
Protection of OUTDOOR UNIT when it is overload
(during Safety Start, Normal operation state)
OUTDOOR UNIT
E407 Comp down due to high pressure OUTDOOR UNIT
E416 Discharge of a compressor is overheated OUTDOOR UNIT
E425 Power source line missing error (only for 3-phase model) OUTDOOR UNIT
E440 Heating operation blocked (outdoor temperature over 35°C) OUTDOOR UNIT
E441 Cooling operation blocked (outdoor temperature under 9°C) OUTDOOR UNIT
E458 OUTDOOR UNIT fan1 error OUTDOOR UNIT
E461 [Inverter] Compressor startup error OUTDOOR UNIT
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 12 2020-01-15 오후 4:06:41
13
English
Installation
Display Explanation Error Source
E462 [Inverter] Total current error/PFC over current error OUTDOOR UNIT
E463 OLP is overheated OUTDOOR UNIT
E464 [Inverter] IPM over current error OUTDOOR UNIT
E465 Compressor V limit error OUTDOOR UNIT
E466 DC LINK over/low voltage error OUTDOOR UNIT
E467 [Inverter] Compressor rotation error OUTDOOR UNIT
E468 [Inverter] Current sensor error OUTDOOR UNIT
E469 [Inverter] DC LINK voltage sensor error OUTDOOR UNIT
E470 Outdoor unit EEPROM Read/Write Error OUTDOOR UNIT
E471 Outdoor unit EEPROM Read/Write Error(OTP error) OUTDOOR UNIT
E474 IPM(IGBT Module) or PFCM temperature sensor Error OUTDOOR UNIT
E475 OUTDOOR UNIT fan2 error OUTDOOR UNIT
E483 H/W DC_Link Over Voltage Error OUTDOOR UNIT
E484 PFC Overload Error OUTDOOR UNIT
E485 Input current sensor error OUTDOOR UNIT
E488 AC Input Voltage Sensor Error OUTDOOR UNIT
E500 IPM is overheated OUTDOOR UNIT
E554 Gas leak error OUTDOOR UNIT
E590 Inverter EEPROM CheckSum Error OUTDOOR UNIT
E901 Water inlet (PHE) temperature sensor error(open/short) OUTDOOR UNIT
E902 Water outlet (PHE) temperature sensor error(open/short) OUTDOOR UNIT
E906 Refrigerant gas inlet (PHE) temperature sensor (open/short) OUTDOOR UNIT
E911 Flow Swtich Open Error COMM KIT
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 13 2020-01-15 오후 4:06:41
14
English
Installation
MEMO
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 14 2020-01-15 오후 4:06:41
15
English
Installation
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 15 2020-01-15 오후 4:06:41
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 16 2020-01-15 오후 4:06:41
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Samsung MIM-E02EN Installation guide

Category
Split-system air conditioners
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI